Plan Review Details - Permit 02050463
Plan Review Stops For Permit 02050463
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-12-27 Cont ID  
Sent By jgomez Date 2002-12-27 Time 13:57 Rev Time 0.50
Received By jgomez Date 2002-12-27 Time 13:57 Sent To  
Notes
2002-12-27 00:00:00CHECKLIST:
 1-PERMIT #02050463 IS FOR WORK AT MAIN
 HOUSE. THIS GAZEBO IS COMPLETE NEW
 CONSTRUCTION. THEREFORE, A SEPARATE
 PERMIT AND SEPARATE REVIEWS BY ZONING
 AND BUILDING ARE REQUIRED.
 APPLY FOR A SEPARATE PERMIT.
  
 **NOTES:
 A) ARCHITECT TO PROVIDE ALL INFORMATION
 REQUIRED BY SECTION 1606.1.7 OF FBC
 2001.
 B) PLANS SUBMITTED ARE VERY INCOMPLETE.
 MISSING BEAMS, TRUSS CONNECTORS,
 ANCHOR BOLTS FOR COLUMNS TOP PLATE,
 CALCULATED UPLIFT LOADS FOR ROOF AND
 COLUMNS, SIZE OF COL. BOTT. PLATE.
 C) CLARIFY FOOTING SIZES FOR COLUMNS AND
 CONCRETE SLAB EDGES.
 D)ARCHITECT TO PROVIDE ALL HIS INFORMA-
 TION AS REQUIRED BY CHAPTER 481 OF
 FLORIDA STATUTES WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
  
  
 *************** REMAINDER *************
  
 PROVIDE INFORMATION REQUESTED ON PROVISO
 DATED 6-22-02 TO AVOID ANY DELAYS OR
 CONFLICTS TO OBTAIN THE FINAL C.O.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-25 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 08:54 Rev Time 3.00
Received By jgomez Date 2002-06-22 Time 16:59 Sent To  
Notes
2002-06-24 00:00:00APPROVED WITH PROVISO:
 1-THERE ARE TWO DIFFERENT GABLE END
 DETAILS. SEE SHEET A6 & A7. PROVIDE
 ONLY ONE DETAIL AND SPECIFY ALL
 STRUCTURAL MEMBERS AND ALL FASTENERS.
 **PROVIDE DIAGRAM AND CALCULATIONS
 SHOWING HOW IS GABLE END CONTINUOUS IN
 ORDER TO COMPLY WITH SECTION 2313.4.1
 FBC 2001.
 2-ARCHITECT TO PROVIDE ALL MINIMUM.
 INFORMATION REQUIRED ON DRAWINGS. SEE
 SECTION 1606.1.7 FBC 2001 FOR MINIMUM
 INFORMATION REQUIRED TO BE ON PLANS.
 3-SECTION A- A6 DOESN'T MATCH ENGINEERED
 TRUSS INFORMATION SUBMITTED. THESE ARE
 TWO COMPLETE DIFFERENT STRUCTURAL
 CONCEPTS.
 **ARCHITECT TO SPECIFY CONNECTORS OF
 TRUSS TO THE STRUCTURE.
 4-ARCHITECT TO SPECIFY HOW IS CONTINUOUS
 SUPPORT PROVIDED FOR GABLE END TRUSS @
 GABLE END TRUSS LOCATED ABOVE KITCHEN
 AREA. ALSO, SPECIFY ALL CONNECTORS.
 5-SPECIFY HOW ARE NEW TRUSSES ATTACHED
 TO EXISTING ROOF.
 6-PROVIDE COMPLETE ENGINEERED TRUSS
 PACKAGE WITH ORIGINAL SIGNATURE, SEAL
 AND DATE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES.
 **NOTE: ARCHITECT TO REVIEW ALL TRUSS
 DRAWINGS (USE REVIEW STAMP) PRIOR TO
 SUBMITTAL.
2002-06-22 00:00:00 
 1-ARCHITECT TO PROVIDE COMPLETE DETAIL/
 SPECS FOR ANCHORING GABLE END TRUSS
 THAT IS SITUATED BETWEEN EXISTING

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-12 Cont ID  
Sent By btrobaug Date 2002-06-21 Time 14:21 Rev Time 3.00
Received By jgomez Date 2002-06-12 Time 15:13 Sent To  
Notes
2002-06-12 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY
 AFTER CORRECTIONS ARE DONE TO ORIGINAL
 DWGS. BRING STAMPED DWGS & PD. RECEIPT
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE SECTIONS, DETAILS AND
 SPECS AT KITCHEN AREA WHERE EXISTING
 BEARING WALL IS REMOVED TO ALLOW FOR
 KITCHEN EXPANSION. SPECIFY SHORING,
 NEW BEAM, BEAM SUPPORTS ETC.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-REVISE UPDATE ALL PLANS AS REQ'D AND
 PROVIDE ALL MIN. INFORMATION. SECTION
 1606.1.7 FBC/01. SEE COMMENTS ON PLANS
 5-CONNECTORS SPECIFIED ON TRUSS ANCHOR
 SCHEDULE DON'T THE RESIST THE UPLIFT
 LOADS CALCULATED ON ROOF FRAMING PLAN.
 REVISE AS REQ'D. SEE COMMENTS ON PLANS
 6-PROVIDE SOIL TEST REPORT. SECTION
 1804.2.2 CITY AMENDMENTS TO FBC 2001.
 7-PROVIDE GABLE END DETAILS THAT COMPLY
 WITH SECTION 2313.4.3 FBC 2001 FOR
 CONTINUOUS CONSTRUCTION.
 NOTE: CONSIDER THE TWO NEW GABLE ENDS
 ON RIGHT HAND ELEVATION.
 8-OWNER/AGENT TO SIGN AND DATE BOTTOM OF
 ENERGY CALCULATIONS.
  
 NOTE:
 PLEASE, RETURN REVIEWED SETS AFTER
 ORIGINAL DWGS ARE REVISED TO EXPEDITE
 THE REVIEW PROCESS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-09-26 Cont ID  
Sent By btrobaug Date 2002-09-26 Time 12:36 Rev Time 1.00
Received By btrobaug Date 2002-09-26 Time 11:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-06-21 Cont ID  
Sent By btrobaug Date 2002-06-21 Time 14:21 Rev Time 0.00
Received By btrobaug Date 2002-06-20 Time 13:03 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-05-22 Cont ID  
Sent By dpalmer Date 2002-05-22 Time 18:13 Rev Time 0.00
Received By dpalmer Date 2002-05-22 Time 17:48 Sent To P
Notes
2002-05-22 00:00:00************ UNSAT ********************
  
 1)NOTE: PLEASE SHOW ALL EXISTING
 ELECTRICAL FOR HOUSE. PLEASE NOTE
 BRINGING SD`S UP TO CODE INSIDE AND
 OUTSIDE ALL EXISTING BEDROOMS ALSO PER
 NFPA-72 2-2.1.1.1.
  
  
 2)) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 3 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 6)NOTE: PLEASE NOTE OUTLET SPACING FOR
 KITCHEN COUNTERSPACE AND PENINSULAR.
 210-52-C-1,2,3,4,5
  
 7)NOTE: PLEASE NOTE OCP SHOWN FOR AHU`S
 NEEDS TO MEET 424-3B
  
 8)NOTE: PLEASE NOTE OTHER OCP SIZES
 EXCEED MAX 150% OCP FOR WATER HEATER AND
 DRYER. PLEASE VERIFY LOAD SHOWN FOR
 DRYER, SHOWN AS 4KW(UNCOMMON LOAD)??
  
 9)NOTE: PLEASE SHOW ON RISER DIAGRAM
 FOOTER STEEL AS SHOWN ON NOTE#7.
  
 10)NOTE: PLEASE SHOW SECOND AHU ON PLANS
  
 11)NOTE: PLEASE SHOW SERVICE LOCATION
 ON PLANS/PANEL/METER/.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-06-25 Cont ID  
Sent By btrobaug Date 2002-05-13 Time 16:02 Rev Time 0.00
Received By jgomez Date 2002-05-13 Time 16:02 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-27 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 08:54 Rev Time 0.00
Received By dpalmer Date 2002-12-27 Time 08:54 Sent To B
Notes
2002-12-27 00:00:00TO JULIO GOMEZ

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-13 Cont ID  
Sent By pkrauss Date 2002-09-13 Time 09:35 Rev Time 0.40
Received By pkrauss Date 2002-09-13 Time 09:34 Sent To  
Notes
2002-09-13 00:00:00PROVIDE DUCT SIZE ON PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-30 Cont ID  
Sent By pkrauss Date 2002-05-30 Time 16:19 Rev Time 0.35
Received By pkrauss Date 2002-05-30 Time 16:11 Sent To B
Notes
2002-05-30 00:00:00PROVISO:
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-29 Cont ID  
Sent By btrobaug Date 2002-09-26 Time 11:33 Rev Time 0.50
Received By jleech Date 2002-05-29 Time 17:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-16 Cont ID  
Sent By jgomez Date 2002-06-25 Time 14:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved