Plan Review Details - Permit 02050457
Plan Review Stops For Permit 02050457
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-08-01 Cont ID  
Sent By jwitmer Date 2002-08-01 Time 11:19 Rev Time 1.25
Received By jwitmer Date 2002-08-01 Time 11:19 Sent To  
Notes
2002-08-01 00:00:00*****BUILDING PROVISO*****
 PROVISO: PROVIDE PRODUCT TESTING REPORTS
 MISSING ARE:
 A) FIXED GLASS- LARGE MISSLE RESISTANT
 B) MULLIONS- LARGE MISSLE RESISTANT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-07-29 Cont ID  
Sent By jwitmer Date 2002-07-29 Time 15:11 Rev Time 2.00
Received By jwitmer Date 2002-07-29 Time 15:11 Sent To  
Notes
2002-07-29 00:00:00SEE COMMENT LIST FROM BEFORE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-03 Cont ID  
Sent By jwitmer Date 2002-06-03 Time 11:48 Rev Time 3.50
Received By jwitmer Date 2002-06-03 Time 11:48 Sent To  
Notes
2002-06-03 00:00:00BUILDING PLAN REVIEW
 PERMIT# 02050457
 10850 EGRET POINTE LANE
 CONT: TRICON LLC.
 TEL: (887) 777-1942
  
 FL BLDG CODE= 2001 FLORIDA BUILDING CODE
  
 1) TABLE 600/SINGLE STORY ADDITION:
 >3' TO 10' ALLOWABLE AREA 20%,(2) 25 SH
 WINDOWS 33.24 MO WITHOUT AREA OF CLERE-
 STORY ABOVE ADDED. ALLOWABLE AREA @ 20%
 IS 31.5 SQ FT.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, SHEET
 A-2 INDICATES A VAULTED CEILING OF 2.5/
 12 BUT SHEET A5 INDICATES THE CLERESTORY
 WINDOW PARALLEL TO THE ROOF LINE WHICH
 IS ON A 6/12 PITCH, IS THIS CORRECT,
 ABOVE THE CEILING LINE?
  
 3) SHEET A-2 DETAIL#1 INDICATES 8" ABOVE
 GRADE, PLAN INDICATES A FOOTING TYPE "A"
 WHICH IS 16"(W)X18"(H), THIS LEAVES 10"
 BELOW GRADE:
 1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR: GLAZED OPENINGS, ROOFING
 ASSEMBLIES AND STORM SHUTTERS,IF GLAZED
 OPENINGS DO NOT HAVE LARGE MISSLE IMPACT
 TESTING BY AN APPROVED TESTING AGENCY.
  
 5) 1707.4.5.1 MULLIONS OCCURING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 6)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 7) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 8)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 9) MISSING UPLIFT AND REACTION VALUES
 FOR TRUSSES & GIRDERS, ON 2 STORY ADD-
 ITION, THERE IS NO DETAIL AT ALL FOR THE
 1ST FLOOR ADITION!
  
 10) MISSING INFORMATION ON INSULATION
 FOR 2ND FLOOR INSULATION BENEATH 2ND
 FLOOR A ND GARAGE?
  
 11)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 12)- MISSING ELEVATIONS ON THE WALL
 SECTIOIN ON A-4. MISSING INFO ON STAIR
 DESIGN? MISSING ON SAME EXT WALL SECTION
 NO STRAPPING INFO FOR FLOOR TRUSS?
  
 13)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-14 Cont ID  
Sent By btrobaug Date 2002-05-14 Time 09:13 Rev Time 0.00
Received By btrobaug Date 2002-05-14 Time 08:41 Sent To Z
Notes
2002-05-14 00:00:00~~~~~~~~~~~~~~~~~~PROVISO!~~~~~~~~~~~~~~
  
 1} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
  
 2} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12,AND INSTALL SAME.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-06-11 Cont ID  
Sent By ndenmark Date 2002-06-11 Time 06:46 Rev Time 0.25
Received By ndenmark Date 2002-06-11 Time 06:46 Sent To  
Notes
2002-06-11 00:00:00NO MECHANICAL INFORMATION PROVIDED
 MECHANICAL PERMIT REQUIRED PRIOR TO
 BEGINNING ANY MECHANICAL WORK

Review Stop P PLUMBING
Rev No 2 Status N Date 2002-07-25 Cont ID  
Sent By kstevens Date 2002-07-25 Time 14:30 Rev Time 0.00
Received By kstevens Date 2002-07-25 Time 14:30 Sent To  
Notes
2002-07-25 00:00:00NO PLUMBING INFORMATION TO REVIEW.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-10 Cont ID  
Sent By kstevens Date 2002-06-10 Time 18:00 Rev Time 0.00
Received By kstevens Date 2002-06-10 Time 18:00 Sent To  
Notes
2002-06-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) NOT ENOUGH INFORMATION - PLEASE SUB-
 MITT A SANITARY RISER DIAGRAM. SHOW PIPE
 SIZES AND VENTS. FBC-2001 AMENDMENTS
 104.3.1.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-11 Cont ID  
Sent By btrobaug Date 2002-05-14 Time 09:14 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***