Plan Review Details - Permit 02050452
| Plan Review Stops For Permit 02050452 |
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2002-06-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-13 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-13 |
Time |
09:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FS |
|
| Rev No |
2 |
Status |
P |
Date |
2002-06-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-13 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-13 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2002-06-13 00:00:00 | 1) FIRE SPRINKLER HEADS ARE TO BE | | | LOCATED IN THE CENTER OF THE TILE. | | | | | | 2) THE ENTIRE INSTALLATION IS TO | | | BE DONE IN QUALITY MANNER APPROVED BY | | | THE FIRE RESCUE DEPARTMENT. | | | | | | 3) THE BUILDINGS WET FIRE DEPARTMENT | | | CONNECTION IS TO BE POSITIONED SO WHEN | | | FIRE HOSE IS CONNECTED IT WILL NOT | | | KINK. | | | | | | 4) DRY STANDPIPE IS TO BE PROPERLY | | | SUPPORTED WITH RISER CLAMPS TO ENSURE | | | STABILITY. | | | | | | 5) ALL UNDERGROUND AND ABOVEGROUND | | | PIPING IS TO BE PRESSURE TESTED IN | | | ACCORDANCE WITH NFPA 24. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FS |
|
| Rev No |
1 |
Status |
F |
Date |
2002-05-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-28 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-28 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2002-05-28 00:00:00 | 1) PLEASE SHOW THE LOCATION OF THE | | | FIRE SPRINKLER, FIRE DEPARTMENT | | | CONNECTION AND THE LOCATION OF THE | | | FIRE HYDRANT USED TO SUPPORT THIS | | | DEVICE. PLEASE BE ADVISED THAT THE | | | FIRE DEPARTMENT CONNECTION IS TO BE | | | LOCATED NO FARTHER THAN 150 FEET FROM | | | IT. | | | | | | 2) IT WAS NOTED THAT CENTRAL FIRE | | | SPRINKLERS ARE PLANNED FOR USE. | | | PLEASE SEE WWW.SPRINKLERREPLACEMENT.COM | | | TO VERIFY THAT THE HEADS PLANNED FOR | | | USE ARE NOT ON THE VOLUNTARY RECALL | | | LIST. | | | | | | 3) PLEASE PROVIDE CUT SHEETS FOR | | | EQUIPMENT AND DEVICES PLANNED FOR | | | USE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2002-06-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-13 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-13 |
Time |
09:20 |
Sent To |
|
|
| Notes |
|
|
|