Plan Review Details - Permit 02050452
Plan Review Stops For Permit 02050452
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-06-13 Cont ID  
Sent By mcarsill Date 2002-06-13 Time 09:20 Rev Time 0.00
Received By mcarsill Date 2002-06-13 Time 09:20 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2002-06-13 Cont ID  
Sent By mcarsill Date 2002-06-13 Time 09:21 Rev Time 0.00
Received By mcarsill Date 2002-06-13 Time 09:21 Sent To  
Notes
2002-06-13 00:00:001) FIRE SPRINKLER HEADS ARE TO BE
 LOCATED IN THE CENTER OF THE TILE.
  
 2) THE ENTIRE INSTALLATION IS TO
 BE DONE IN QUALITY MANNER APPROVED BY
 THE FIRE RESCUE DEPARTMENT.
  
 3) THE BUILDINGS WET FIRE DEPARTMENT
 CONNECTION IS TO BE POSITIONED SO WHEN
 FIRE HOSE IS CONNECTED IT WILL NOT
 KINK.
  
 4) DRY STANDPIPE IS TO BE PROPERLY
 SUPPORTED WITH RISER CLAMPS TO ENSURE
 STABILITY.
  
 5) ALL UNDERGROUND AND ABOVEGROUND
 PIPING IS TO BE PRESSURE TESTED IN
 ACCORDANCE WITH NFPA 24.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FS  
Rev No 1 Status F Date 2002-05-28 Cont ID  
Sent By mcarsill Date 2002-05-28 Time 13:15 Rev Time 0.00
Received By mcarsill Date 2002-05-28 Time 13:15 Sent To  
Notes
2002-05-28 00:00:001) PLEASE SHOW THE LOCATION OF THE
 FIRE SPRINKLER, FIRE DEPARTMENT
 CONNECTION AND THE LOCATION OF THE
 FIRE HYDRANT USED TO SUPPORT THIS
 DEVICE. PLEASE BE ADVISED THAT THE
 FIRE DEPARTMENT CONNECTION IS TO BE
 LOCATED NO FARTHER THAN 150 FEET FROM
 IT.
  
 2) IT WAS NOTED THAT CENTRAL FIRE
 SPRINKLERS ARE PLANNED FOR USE.
 PLEASE SEE WWW.SPRINKLERREPLACEMENT.COM
 TO VERIFY THAT THE HEADS PLANNED FOR
 USE ARE NOT ON THE VOLUNTARY RECALL
 LIST.
  
 3) PLEASE PROVIDE CUT SHEETS FOR
 EQUIPMENT AND DEVICES PLANNED FOR
 USE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-06-13 Cont ID  
Sent By mcarsill Date 2002-06-13 Time 09:20 Rev Time 0.00
Received By mcarsill Date 2002-06-13 Time 09:20 Sent To  
Notes
***NONE***