| Plan Review Stops For Permit 02050442 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-06-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-25 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-06-03 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-06-03 |
Time |
14:14 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2002-06-03 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2002-06-03 00:00:00 | DENIED: | | | | | | 1. EXHAUST AIR EQUALS 1000CFM AND | | | OUTSIDE AIR EQUALS 240 CFM WHICH HAS | | | THIS BUILDING APPARENTLY 760 CFM | | | NEGATIVE. PROVIDE INFORMATION ON WHERE | | | ADDITIONAL OUTSIDE IS FROM TO AVOID | | | NEGATIVE PRESSURE ON BUILDING. | | | | | | 2. FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED FOR AHU, WITH NOTIFICATION BY | | | BY BUILDING ALARM SYSTEM. | | | | | | 3. NOTE: AHU LOCATION SHALL BE IN | | | RESPECT TO BUILDING CONSTRUCTION TO | | | ALLOW FOR SERVICE AND REPLACEMENT OF | | | EQUIPMENT WITHOUT RESTRICTION OR | | | REMOVAL OF BUILDING COMPONENTS. |
|
|
|