Plan Review Details - Permit 02050434
Plan Review Stops For Permit 02050434
Review Stop E ELECTRICAL
Rev No 7 Status N Date 2004-01-22 Cont ID  
Sent By dpalmer Date 2004-01-22 Time 09:57 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2004-01-22 00:00:00NO PLAN REVIEW
 ELECTRICAL FINAL WAS GIVEN ON 11/18/03

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2003-10-28 Cont ID  
Sent By dpalmer Date 2003-10-28 Time 11:34 Rev Time 0.25
Received By dpalmer Date 2003-10-28 Time 11:33 Sent To  
Notes
2003-10-28 00:00:00REV CAME IN W/OUT SECOND SET, TOLD
 CONT WHEN PLANS WERE SUBMITTED THAT WE
 NEEDED 2ND SET. NO REVIEW DONE.
 UNDER "R" WAITING.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2003-02-19 Cont ID  
Sent By csiegber Date 2003-10-24 Time 14:28 Rev Time 0.75
Received By dpalmer Date 2003-02-19 Time 07:41 Sent To  
Notes
2003-02-19 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEWS AND NOTES REDLINED ON PLANS.
 PLANS SHOW 3 WATER HEATERS, PANEL SCHED-
 -ULES SHOW 2, AND LOAD CALCUALTIONS DO
 NOT CORRELATE WITH LOADS SHOWN ON PANEL
 SCHEDULES??
  
 2)NOTE: PLEASE CLARIFY NOTE ON A-3P,
 MENTIONS SWITCH TO BUNKER RANCH RD??
 PLEASE EXPLAIN?
  
 3)NOTE: PLEASE SEE FS/ FAC,471.025/
 481.221. PLANS MUST BE RE-PRINTED AND
 SIGNED DATED AND SEALED BY THE ARCH/
 ENGINEER OF RECORD. PLEASE NOTE, ALL
 HAND WRITTEN CHANGES ON PLANS NEED TO
 GO BACK TO ARCH FOR PRINTING.
 PLEASE ALSO ADDRESS NOTES ABOVE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESITONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-08-16 Cont ID  
Sent By dpalmer Date 2003-02-12 Time 15:49 Rev Time 0.00
Received By dpalmer Date 2002-08-16 Time 13:29 Sent To  
Notes
2002-08-16 00:00:00REDLINED, 3 WATER HEATERS ON PANEL SCHED
 ONLY 2 SHOWN ON LOAD CALCS. OK.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-07-18 Cont ID  
Sent By dpalmer Date 2002-07-18 Time 09:43 Rev Time 0.00
Received By dpalmer Date 2002-07-18 Time 09:43 Sent To P
Notes
2002-07-18 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOTES THAT
 WERE REDLINED/PROVISO ON PREVIOUS PLANS
 WERE NOT ADDRESSED. PLEASE SEE PLANS
 AND PREVIOUS NOTES FOR COMMENTS.
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-24 Cont ID  
Sent By dpalmer Date 2002-06-24 Time 16:09 Rev Time 0.00
Received By dpalmer Date 2002-06-24 Time 16:09 Sent To P
Notes
2002-06-24 00:00:00********* NOTED/REDLINED *************
  
 PLEASE NOTE PLANS REDLINED FOR SOME
 CORRECTIONS.
  
 PLEASE NOTE PANEL SCHEDULES NEED TO
 CORRELATE OCP/WIRE/LOADS. WATER HEATERS,
 AND SUB-PANEL
  
 MISSING BATH GFI REC DOWNSTAIRS.
 210-52D/210-8
  
 NOTED CLOSET LT CLEARENCE REQ`D PER
 410-8.
  
 PLEASE NOTE THE ABOVE WAS REDLINED AS
 NOTES. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-24 Cont ID  
Sent By dpalmer Date 2002-05-24 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2002-05-24 Time 15:43 Sent To B
Notes
2002-05-24 00:00:00**************** UNSAT ****************
  
 1) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 2)NOTE: PLEASE NOTE THAT ALL GARAGE AND
 BATHS OUTLETS ARE TO BE SHOWN AS GFI/GFI
 PROTECTED.210-8
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED OUTLETS ON PANEL SCHEDULE.
 PER 210-12
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 4)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 5)NOTE: PLEASE NOTE MISSING EGRESS
 LIGHTING PER 210-70.
  
 6)NOTE: PLEASE NOTE THAT ALL A/C CU`S,
 AHU`S NEED TO BE SHOWN ON ELECTRICAL
 PLANS.
 PLEASE SHOW ALL REQ`D DISC`S PER 440-11
  
 7)NOTE: PLEASE NOTE A/C NOTES UNDER ELEC
 RISER MENTION 3-A/C SYSTEMS AND ONLY
 TWO ARE SHOWN ON PANEL SCHEDULES AND ON
 LOAD CALCULATIONS. PLEASE ALSO NOTE
 A/C LOAD NEED TO CORRELATE WITH PANEL
 SCHEDULES.
  
 8)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC`S
 AND PANELS. SIZE PER 250-122
  
 9)NOTE: PLEASE NOTE SOME CLOSET LIGHTS
 SHOWN WHERE PROHIBITED PER 410-8.
  
 10)NOTE: PLEASE NOTE ELECTRICAL WATER
 HEATERS NOT SHOWN ON E-SHEETS.?DISC`S?
  
 11)NOTE: PLEASE NOTE THAT ALL ROOM
 DESIGNATIONS NEED TO BE SHOWN ON
 ELECTRICAL PLANS.
  
 12)NOTE: PLEASE NOTE KITCHEN COUNTER-
 LAYOUT AND OUTLETS SPACING NOT COMPLETE.
 210-52 C
 PLEASE CALRIFY SWICHES SHOWN AS GFI`S??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-01-22 Time 11:58 Rev Time 0.00
Received By csiegber Date 2004-01-22 Time 11:58 Sent To B
Notes
2004-01-22 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 14:28 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 14:28 Sent To E
Notes
2003-10-24 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-16 Cont ID  
Sent By csiegber Date 2003-10-16 Time 10:07 Rev Time 0.00
Received By csiegber Date 2003-10-16 Time 10:07 Sent To B
Notes
2003-10-16 00:00:00TO JW DESK/RE-STAMP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-12 Cont ID  
Sent By dpalmer Date 2003-02-12 Time 15:49 Rev Time 0.00
Received By dpalmer Date 2003-02-12 Time 15:49 Sent To E
Notes
2003-02-12 00:00:00TO DVP'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-13 Cont ID  
Sent By dpalmer Date 2002-11-13 Time 16:11 Rev Time 0.00
Received By dpalmer Date 2002-11-13 Time 16:11 Sent To Z
Notes
2002-11-13 00:00:00SENT TO ZONING FOR RE-STAMP.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-18 Cont ID  
Sent By hmoser Date 2002-05-18 Time 13:55 Rev Time 0.50
Received By hmoser Date 2002-05-18 Time 13:55 Sent To  
Notes
2002-05-18 00:00:00PROVISO
 #1 VARIFY TYPE OF VENTILATION USED
 [FRESH AIR]NATURAL SECTION 402 OR
 MECHANICAL SECTION 403
 @2 NEED CALCULATIONS FOR TYPE OF
 VENTILATION USED
 #3 REFER TO SECTION 601.4 BALANCED
 RETURN AIR
 #4 CONDENSATE DRAIN MUST TERMINATE
 12IN.FROM BUILDING
 #5 REFER TO SECTION 402.3.1 BATHROOM
 VENTILATION.NO WINDOW EXCEPTION
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-07-25 Cont ID  
Sent By dpalmer Date 2002-08-07 Time 13:20 Rev Time 0.00
Received By kstevens Date 2002-07-25 Time 13:02 Sent To  
Notes
2002-07-25 00:00:00REVISION OK - CHNG BATH/LAUNDRY LAYOUT -
 CHANGE O/SIDE SHOWER

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-29 Cont ID  
Sent By dpalmer Date 2002-07-18 Time 09:45 Rev Time 0.50
Received By jleech Date 2002-06-29 Time 10:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-25 Cont ID  
Sent By kstevens Date 2002-05-25 Time 16:08 Rev Time 0.00
Received By kstevens Date 2002-05-25 Time 16:08 Sent To  
Notes
2002-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-25 Cont ID  
Sent By jleech Date 2002-05-11 Time 13:10 Rev Time 0.25
Received By kstevens Date 2002-05-11 Time 13:10 Sent To  
Notes
2002-05-11 00:00:00ADDITIONAL INFORMATION NEEDED TO DO A
 PLUMBING PLAN REVIEW. NO RISER DIAGRAM.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2004-01-27 Cont ID  
Sent By jwitmer Date 2004-01-27 Time 12:55 Rev Time 0.50
Received By jwitmer Date 2004-01-27 Time 12:55 Sent To  
Notes
2004-01-27 00:00:00ELEVATOR SHOP DRAWINGS01-27-04 JW

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2003-10-21 Cont ID  
Sent By jwitmer Date 2003-10-21 Time 10:21 Rev Time 1.55
Received By jwitmer Date 2003-10-21 Time 10:21 Sent To  
Notes
2003-10-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 0205434
 ADD: 5501 S FLAGLER DR
 CONT: ROGER THOMAS
 TEL: (561)339-0573
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: RESTAMP : DENIED
  
 PLANS INDICATE REV # 10 GENERAL REVIS-
 IONS, REVISIONS ARE NOT CIRCLED OR HIGH-
 LIGHTED.
 ELECTRICAL REVISIONS ARE SHOWN IN PEN
 NOT THROUGH THE ARCHITECT OF RECORD.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-11-26 Cont ID  
Sent By jwitmer Date 2002-11-26 Time 08:41 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-11-26 00:00:00RESTAMP PLANS + REV 8-09-02JW

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-07-02 Cont ID  
Sent By jwitmer Date 2002-07-02 Time 13:22 Rev Time 0.00
Received By jwitmer Date 2002-07-02 Time 12:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-12 Cont ID  
Sent By jwitmer Date 2002-06-12 Time 17:12 Rev Time 4.00
Received By jwitmer Date 2002-06-12 Time 17:12 Sent To  
Notes
2002-06-12 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02040434
 ADD: 5501 S. FLAGLER
 CONT: ROGER G THOMAS GEN CONT INC
 TEL: 575-1389
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) THE FINISHED FLOOR LEVEL SHALL BE
 VERIFIED BY A SIGNED AND SEALED
 ELEVATION CERTIFICATE REQUIRED, ELEVA-
 TION OF FIRST FLOOR, POOL PUMP SLAB &
 A/C CONDENSER SLAB TO BE ABOVE 7'-6".
 A-5 FLOOD ZONE, CITY CODE REQUIRES AN
 ADDITIONAL 6", OR 7'-6".
  
 2)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 THIS INFORMATION IS TO BE ON THE DESIGN
 DOCUMENTS! PREASURE ZONES ON PLANS!
  
 4) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
 THE MANUAL "J" PROVIDED BUT NOT FORM
 600A-2001, RESIDENTIAL WHOLE BUILDING
 PERFORMANCE METHOD A.
  
 5)1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) CUSTOM ENTRY FRONT DOOR& FRAME
 SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE DESIGN
 PROFESSIONAL OF RECORD.
 B) GARAGE OVERHEAD DOOR, HIGHLIGHT THE
 MANUFACTURER & MODEL.
 C)ROOFING REPORT, MISSING 7 PAGES.
  
 7) PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR. 1997 SBC 1005.4
 THE WINDOW SCHEDULE LIST WINDOW"H"
 AS A PR 2'-0"X6'-0" CASEMENT WINDOW. THE
 REPORT PROVIDED LIST THE FRAME AS
 2.25", X2= 4.5"OR 19.5" LESS THE LIGHT
 AND FRAME.
  
 8)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED. IDENTIFY
 WHICH MULLIONS ARE TO BE USED IN EACH
 CASE, EXAMPLE VETICAL WINDOW "H" A 1X3
 MULLION, AS PART OF THE WINDOW SCHEDULE.
 WINDOW INSTALLER MAY CHOOSE A MULION
 NOT SPECIFIED BY ARCHETECT.
  
 9) S-3ROOF FRAMING PLAN, MISSING THE
 MAGNITUDE,AND DIRECTION OF LOADS TO BE
 RESISTED. THE PLAN INDICATES THE USE OF
 HUGHES & SEMCO THEY HAVE BEEN OUT OF
 BUSINESS FOR 2 YEARS.PROVIDE MANUFACT-
 URER AND MODEL OF ANCHOR.
  
 10)-1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 11) 2806.1.2. FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH AND
 MEET THE REQUIREMENTS OF UL 127. PROVIDE
 MANUFACTURERS SPEC.
  
 12) 2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/
 ING ASSEMBLIES SEPERATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS.
  
 13) 2305.1.4 (1) FIREBLOCKING SHALL BE
 INSTALLED IN WOOD FRAME CONSTRUCTION IN-
 CLUDDING FURRED SPACES AT CEILING &
 FLOOR LEVELS.
  
 IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-14 Cont ID  
Sent By dpalmer Date 2002-11-13 Time 16:11 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***