Plan Review Details - Permit 02050364
Plan Review Stops For Permit 02050364
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-06-20 Cont ID  
Sent By hpiskura Date 2002-06-20 Time 11:14 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-06-20 00:00:00PROVISO:SHOW THE METHOD OF PROTECTION
 FOR HORIZONTAL ASSEMBLIES.SEE FBC 705.
 6

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-31 Cont ID  
Sent By pkrauss Date 2002-08-09 Time 11:37 Rev Time 0.00
Received By dpalmer Date 2002-07-31 Time 17:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-16 Cont ID  
Sent By pkrauss Date 2002-07-30 Time 12:18 Rev Time 0.00
Received By dpalmer Date 2002-05-16 Time 06:20 Sent To  
Notes
2002-05-16 00:00:00************ UNSAT ***********
  
 1)NOTE: PLEASE NOTE, NO LOAD CALCULATION
 S WERE SUBMITTED FOR ADDINGNEW
 LOADS TO EXISTING PANELS??
 ADDING 100A DISC TO PANEL "DP" NOTHING
 FOR DP SHOWN??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-08-09 Cont ID  
Sent By kstevens Date 2002-08-09 Time 11:33 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-06-19 Cont ID  
Sent By mcarsill Date 2002-06-19 Time 12:22 Rev Time 0.00
Received By mcarsill Date 2002-06-19 Time 12:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-30 Cont ID  
Sent By pkrauss Date 2002-07-30 Time 12:18 Rev Time 0.35
Received By pkrauss Date 2002-07-30 Time 12:05 Sent To E
Notes
2002-07-30 00:00:00PROVISO:MECHANICAL PERMIT 02050369
  
 REFERENCE PLAN SHEET M-2, CU 2
 SUPPORTEDFROM THE WALL.AS PER 2001
 FBC(M) 306.5 EQUIPMENT REQUIRING ACCESS
 THAT ARE INSTALLED ON ROOFS OR ELEVATED
 STRUCTURES AT A HEIGHT EXCEEDING 16 FT,
 SUCH ACCESS SHALL BE PROVIDED BY A
 PERMANENT APPROVED MEANS OF ACCESS.
 SUCH ACCESS SHALL NOT REQUIRE CLIMBING
 OVER OBSTRUCTIONS GREATER THAN 30".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-30 Cont ID  
Sent By pkrauss Date 2002-05-30 Time 10:11 Rev Time 0.50
Received By pkrauss Date 2002-05-30 Time 09:41 Sent To  
Notes
2002-05-30 00:00:00PLAN SHEET M-2 DETAIL 1 - PLAN NOTE #4,
 ROUTE 1" CONDENSATE TO HUB DRAIN LOCATED
 IN THE MECHANICAL ROOM.WHAT TYPE OF
 DRAIN IS THIS? SANITARY, DEDICATED
 CONDENSATE, STORM DRAIN?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-08-09 Cont ID  
Sent By kstevens Date 2002-08-09 Time 11:32 Rev Time 0.00
Received By kstevens Date 2002-08-09 Time 11:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-03 Cont ID  
Sent By kstevens Date 2002-06-03 Time 19:15 Rev Time 0.00
Received By kstevens Date 2002-06-03 Time 19:15 Sent To  
Notes
2002-06-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) CONDENSATE SHALL NOT DRAIN TO SANIT-
 ARY. DRAIN CONDENSATE SEPARATELY OUT OF
 BLDG TO STORM. RELIEF VENT REQUIRED AS
 CONDENSATE EXITS BLDG.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-08-09 Cont ID  
Sent By kstevens Date 2002-08-09 Time 11:32 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***