Plan Review Details - Permit 02050313
| Plan Review Stops For Permit 02050313 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-07-12 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-07-12 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-05-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-05-17 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-17 00:00:00 | PLEASE PROVIDE CURRENT TEST AND OR | | | NOTICE OF ACCEPTANCE REPORTS FOR THE | | | EXTERIOR GLAZED STORE FRONT SYSTEM | | | INTENDED TO BE INSTALLED WITH THIS | | | PERMIT.ALTERNATIVELY, A SEPARATE | | | PERMIT AND FEES WILL BE REQUIRED FOR | | | THE INSTALLATION. | | | | | | PROVIDE FOR THE EXTENSION OF THE FIRE | | | SPRINKLER SYSTEM TO THE PROPOSED | | | ENCLOSURE. | | | | | | THE EXISTING BUILDING IS OF TYPE V CONST | | | RUCTION AND IS REQUIRED BY FBC 607 TO HA | | | VE EXTERIOR WALLS OF NONCOMBUSTIBLE CONS | | | TRUCTION.SHEET A3 INDICATES THE USE OF | | | PLYWOOD SHEATHING.SEE FBC 1403.6.7. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-05-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-21 |
Time |
19:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-21 |
Time |
19:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-06-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-26 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-26 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-05-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-30 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-30 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2002-05-30 00:00:00 | 1) NO MENTION OF EXTENDING FIRE | | | SPRINKLER PROTECTION INTO NEW AREA | | | OF EXISTING LOCATION. | | | | | | 2) NEW VESTIBULE CAN ONLY BE USED FOR | | | INGRESS AND EGRESS TO THE EXTERIOR | | | EXIT DOORS AND FOR NOT OTHER USES. | | | | | | 3) SEE COMMENTS FROM BUILDING PLAN | | | REVIEWER. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-05-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-30 |
Time |
09:39 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-05-30 |
Time |
09:39 |
Sent To |
|
|
| Notes |
|
|
|