Plan Review Details - Permit 02050306
Plan Review Stops For Permit 02050306
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2002-11-06 Cont ID  
Sent By jwitmer Date 2002-11-06 Time 09:36 Rev Time 1.25
Received By jwitmer Date 2002-11-06 Time 09:36 Sent To  
Notes
2002-11-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02050306
 ADD: 319 E LAKEWOOD
 CONT: ROYAL PALM COLLECTION
 TEL: (561)718-1135
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 REVISION: OCT 21/02***DENIED***
  
 1) NO PRODUCT TESTING REPORTS,
 REQUIRED FOR WIND EVEN IF GLAZED OPEN-
 INGS SHALL HAVE STORM SHUTTERS.
  
 2) REVISION DOESN'T INDICATE ANY CUT
 SECTIONS FOR CARRYING THE LOADS THAT
 MUST BE TRANSFERRED OVER THE NEW OPEN-
 INGS (HEADER, AMOUNT OF JACK STUDS &
 FULL LENGTH STUDS REQUIRED @ EACH OPEN-
 ING. NO INDICATION AS TO HOLD DOWN
 DEVICES NOR STRAPPING REQUIREMENTS.
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-07-25 Cont ID  
Sent By jwitmer Date 2002-07-25 Time 11:02 Rev Time 1.00
Received By jwitmer Date 2002-07-25 Time 11:02 Sent To  
Notes
2002-07-25 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02050306
 ADD: 319 E. LAKEWOOD AVE
 CONT: ROYAL PALM BUILDERS
 TEL: (561)791-4494
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 *****PROVISO******
 1) A SEPERATE STORM SHUTTER PERMIT SHALL
 BE REQUIRED W/ ASSOCIATE FEES & REVIEWS
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-07-24 Cont ID  
Sent By jwitmer Date 2002-07-24 Time 17:39 Rev Time 0.66
Received By jwitmer Date 2002-07-24 Time 17:39 Sent To  
Notes
2002-07-24 00:00:00COMMENTS 3, 11 & 12 FROM THE PREVIOUS
 REVIEW NOT COMPLETED.JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-29 Cont ID  
Sent By jwitmer Date 2002-06-29 Time 11:33 Rev Time 1.00
Received By jwitmer Date 2002-06-29 Time 11:33 Sent To  
Notes
2002-06-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02050306
 ADD: 319 LAKEWOOD AVE
 CONT: ROYAL PALM COLLECTION INC
 TEL: (561) 791-4494
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE GUEST COTTAGE IS SHOWN ON PLANS, IS
 THERE ANY WORK TO TAKE PLACE IN THIS
 UNIT?
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) WINDOWS
 B) EXTERIOR DOORS
 C) ROOFING ASSEMBLIES
 TILE AS WELL AS THE BASE
 SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 4) THE DETAILS ARE NOT CLEAR IF THERE IS
 TO BE A MULLION USED BETWEEN ADJOINING
 WINDOWS, IF SO:
 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 5)1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 6)2304.5 CLEARENCE BETWEEN WOOD SIDING
 & EARTH ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6" EXCEPT WHERE
 SIDING, SHEATHING AND FRAME WALL ARE OF
 APPROVED DURABLE WOOD OR APPROVED PRE-
 SERVATIVE TREAATED WOOD.
  
 7) 2305.1 FIREBLOCKING, MISSING AT THE
 CONNECTION (LEDGER) FIRST FLOOR WALL/
 CEILING LINE.
  
 8) PLANS INDICATE A ROOF SCUPPER, 1511.
 6.4.3 REQUIRES ADDITIONAL EMERGENCY
 OVERFLOW SCUPPER.
  
 9) SHEET A-4 DETAIL 1 ENCLOSING A HALL-
 WAY, THE PLAN INDICATE A KNEE BRACE THAT
 WILL ATTACH TO "ASSUMED" DOUBLE STUDS,
 WILL THIS CONNECTION BE VERIFFIED?
  
 10) ON THE HALLWAY EXTENTION THERE IS NO
 INFORMATION AS TO THE SPACING OF THE
 CEILING JOIST OR RAFTERS, SIZE OR TIE-
 DOWNS?
  
 11)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 12)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-08-14 Cont ID  
Sent By btrobaug Date 2002-08-14 Time 10:17 Rev Time 0.00
Received By btrobaug Date 2002-08-14 Time 10:17 Sent To  
Notes
2002-08-14 00:00:00ELECTRICAL PLANS PAGES E-1 & E-2 DATED
 7/15/02 VOIDED,THE PLANS I REVIEWED ON
 5/13/02 ARE NOT IN THE FILE COPY./WRT

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-13 Cont ID  
Sent By btrobaug Date 2002-05-13 Time 15:53 Rev Time 0.00
Received By btrobaug Date 2002-05-13 Time 15:00 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-06-20 Cont ID  
Sent By lmartine Date 2002-06-20 Time 10:04 Rev Time 0.25
Received By pkrauss Date 2002-06-20 Time 10:04 Sent To P
Notes
2002-06-20 00:00:00NO MECHANICAL PLANS OR ENERGY CALCS
 SUBMITTED FOR REVIEW.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-23 Cont ID  
Sent By kstevens Date 2002-07-23 Time 10:33 Rev Time 0.00
Received By kstevens Date 2002-07-23 Time 10:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-24 Cont ID  
Sent By kstevens Date 2002-06-24 Time 18:12 Rev Time 0.00
Received By kstevens Date 2002-06-24 Time 18:12 Sent To  
Notes
2002-06-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM S/1 DOES NOT
 MEET CODE. TOILET ROOM FROM 2ND FLOOR
 CAN NOT DRAIN INTO THE BATHROOM GROUP OF
 THE FIRST FLOOR. 1ST FLOOR BATH FLOOR
 PLAN SHOWS A W/C, LAV, AND A SHOWER. BUT
 THE RISER SHOWS 4 FIXTURES. SHOWER IN
 2ND FLOOR BATH NOT VENTED.
 2) SANITARY RISER DIAGRAM S/2 TUB NOT
 VENTED AND A 3" VTR IS REQUIRED.
 3) SANITARY RISER DIAGRAM S/3 HORIZONTAL
 DRY VENT IS NOT APPROVED.
  
 PLEASE SEE ATTACHED SHEET FOR COMPLIANCE
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2002-06-19 Cont ID  
Sent By sgraham Date 2002-06-19 Time 10:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-06-10 Cont ID  
Sent By btrobaug Date 2002-05-13 Time 15:53 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-06-10 00:00:00DENIED, 1ST FLOOR OF GARAGE APT MUST
 HAVE A SPACE TO PARK A CAR