Plan Review Details - Permit 02050238
Plan Review Stops For Permit 02050238
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-18 Cont ID  
Sent By btrobaug Date 2002-06-18 Time 11:44 Rev Time 0.00
Received By btrobaug Date 2002-06-18 Time 11:33 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-28 Cont ID  
Sent By pkrauss Date 2002-06-17 Time 07:51 Rev Time 0.00
Received By btrobaug Date 2002-05-28 Time 07:40 Sent To R
Notes
2002-05-28 00:00:00PROVISO
 ~~~~~~~
 1} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 2} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-17 Cont ID  
Sent By pkrauss Date 2002-06-17 Time 07:43 Rev Time 0.35
Received By pkrauss Date 2002-06-17 Time 07:36 Sent To E
Notes
2002-06-17 00:00:00PROVISO:MECHANICAL PERMIT 02050244
  
 SHOULD GAS DRYER BE INSTALLED -
 SHOW COMPLIANCE FOR COMBUSTION AIR AS
 PER 2001 FBC(M) CHAPTER 7.PLEASE
 PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE VENTING OF ALL GAS
 APPLIANCES.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STOBE OR AREA
 SMOKE DETECTORS. 2001 FBC(M) 606.4.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-21 Cont ID  
Sent By hmoser Date 2002-05-21 Time 18:55 Rev Time 0.50
Received By hmoser Date 2002-05-21 Time 18:55 Sent To  
Notes
2002-05-21 00:00:00PLAN DENIED
 #1 ENERGY CALCS DO NOT MATCH PLANS
 #2 EQUIPMENT MATCH IS NOT IN ARI.MANUAL#
 #3 BTU.ON EQUIPMENT SCHEDULE DO NOT
 MATCH EQUIPMENT
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By kstevens Date 2003-02-07 Time 11:19 Rev Time 0.25
Received By kstevens Date 2003-02-07 Time 11:19 Sent To  
Notes
2003-02-07 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-13 Cont ID  
Sent By jleech Date 2002-05-13 Time 18:31 Rev Time 0.33
Received By jleech Date 2002-05-13 Time 18:31 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2002-07-30 Cont ID  
Sent By hpiskura Date 2002-07-30 Time 08:21 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-07-30 00:00:00SUBJECT TO FEES DUE

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2002-07-05 Cont ID  
Sent By rbrown Date 2002-07-05 Time 09:34 Rev Time 0.00
Received By rbrown Date 2002-07-05 Time 09:34 Sent To  
Notes
2002-07-05 00:00:00THE RESPONSE TO H. PISKURA'S BUILDING
 PLAN REVIEW OF 6/18/02 HAS BEEN REVIEWED
 AND COMMENTS ARE AS FOLLOWS:
  
 ENGINEERED MASONRY DESIGN (FBC 2103.1):
 THE COMMENT FROM THE PREVIOUS REVIEW HAS
 NOT BEEN FULLY ADDRESSED.DESIGN
 INFORMATION AND CALCULATIONS WERE
 REQUESTED (SEE CHAPTER 1 OF ACI 530) TO
 DEMONSTRATE COMPLIANCE WITH ACI 530.
 PLEASE SUBMIT.
  
 IMPACT FEES:
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE ACTUAL PERMIT PLANS
 MUST BE STAMPED BY THAT OFFICE, AND A
 COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.PLEASE CALL
 (561) 233-5025 FOR MORE INFORMATION.
  
 NOTICE OF COMMENCEMENT:
 A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENT MUST BE FILED WITH THE
 CITY PRIOR TO PERMIT ISSUANCE.
  
  
 PRODUCT APPROVALS:
  
 THE SIZES OF THE FIXED WINDOWS G,N,P,V,
 X AND BB ARE OUTSIDE THE SCOPE OF THE
 SUBMITTED NORANDEX WINDOW PRODUCT
 APPROVAL NOA# 00-0808.05 (SEE DRAWING NO
 01-0208, SHEET 1 OF 4).SUBMIT A
 PRODUCT APPROVAL APPLICABLE TO THE SIZE
 OF THESE WINDOWS.
  
 WINDOWS DD (MASTER BATH) & T (BREAKFAST)
 ARE DESCRIBED, ON SHEET A2-1, AS BUTT
 GLAZED.SUBMIT ENGINEERING FOR THESE
 WINDOWS.
  
 EXTERIOR DOORS A,H,R,U,W,Y AND Z.THE
 DRAWINGS SUBMITTED WITH THE PREMDOR
 PRODUCT APPROVAL NOA# 01-0314.26 ARE NOT
 THE SHEETS REFERENCED IN THAT APPROVAL
 AND ARE NOT RELEVANT TO THE PROPOSED
 DOORS.ALSO, THIS PRODUCT APPROVAL IS
 FOR A DOUBLE DOOR AND WILL NOT BE
 APPLICABLE TO THE SINGLE DOORS.SUBMIT
 COMPLETE AND APPROPRIATE PRODUCT
 APPROVALS.
  
 SINGLE HUNG WINDOWS I THRO' M AND O. THE
 DRAWINGS SUBMITTED WITH NORANDEX PRODUCT
 APPROVAL NOA# 00-0808.06 DO NOT CARRY
 THE MIAMI-DADE COUNTY PRODUCT CONTROL
 APPROVAL STAMP.SUBMIT COPIES OF THE
 APPROVED DRAWINGS.
  
 WINDOW AA.NOTE THAT THE WINDOW LOAD ON
 PLAN SHEET A2-1 EXCEEDS THE "DESIGN
 PRESSURE RATING, WITH 3/16" ANNEALED
 GLASS' STATED ON NORANDEX PRODUCT
 APPROVAL NOA# 01-0216.04 DRAWING NO.
 DADE-107,SHEET 1 OF 3 (RED LINED ON NOA)
  
 SLIDING GLASS DOORS.THE DRAWINGS
 SUBMITTED WITH NORANDEX PRODUCT APPROVAL
 NOA# 00-0823.03 DO NOT CARRY THE MIAMI-
 DADE COUNTY PRODUCT CONTROL APPROVAL
 STAMP.SUBMIT COPIES OF THE APPROVED
 DRAWINGS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-06-18 Cont ID  
Sent By hpiskura Date 2002-06-18 Time 14:40 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-06-18 00:00:00PLEASE PROVIDE THE DESIGN INFORMATION
 CONTAINED IN ACI 530 AND CALCULATIONS
 DEMONSTRATING COMPLIANCE WITH SAME.
 SEE FBC2103.1PLEASE DO NOT QUOTE THE
 CODE SECTIONS, BUT SHOW THE CRITERIA ON
 THE PLANS.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENTMUST BE FILED WITH THE
 CITY PRIOR TO PERMIT ISSUANCE.
  
 THE NORANDEX PRODUCT INFORMATION
 DECLARES 1997 STANDARD BUILDING CODE,
 THE 2001FBC IS CURRENTLY IN EFFECT, AND
 DOCUMENTS SUBMITTED FOR PUBLIC RECORD
 REQUIRE THE EMBOSSED SEAL AND ORIGINAL
 SIGNATURES OF THE DESIGN PROFESSIONALS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-06 Cont ID  
Sent By btrobaug Date 2002-06-18 Time 11:44 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
2002-06-06 00:00:00PROVISOS:
  
 SHEET SP1.IF THE DRIVEWAY IS INTENDED
 TO BE CONSTRUCTED UNDER THIS PERMIT,
 CONSTRUCTION DETAILS AND SPECIFICATIONS
 ARE NECESSARY.ALTERNATIVELY A
 SEPARATE PERMIT, FEES AND THE REQUISITE
 INFORMATION WILL BE REQUIRED.
  
 BATHROOMS #2, #3 AND #4 REQUIRE SAFETY
 GLAZING.SEE FBC 2405.1.
  
 IF THE METHOD OF HURRICANE MISSILE
 IMPACT RESISTANCE FOR THE GLAZED AREAS
 IN THE EXTERIOR BUILDING ENVELOPE IS
 NOT INCLUDED WITH THIS PERMIT
 APPLICATION, A SEPARATE PERMIT AND FEES
 ARE REQUIRED.
  
 MIAMI-DADE NOA 01-0317.26 "PREMDOOR
 ENTRY SYSTEMS" IS MISSING THE DRAWING
 STIPULATED IN THAT REPORT.
  
 THE NORANDEX PRODUCT SPECIFICATION CITES
 THE 1997 STANDARD BUILDING CODE, IS NOT
 SIGNED AND SEALED, AND DOES NOT HAVE
 THE SPECIFIC SIZES SELECTED.
  
 THE CLOPAY GARAGE DOOR SBCCI 9606 TEST
 REPORT IS NO LONGER VALID.SEE REPORT
 #9606C AND SELECT THE APPROPRIATE DOORS
 TO BE USED.
  
 SHEET T1 MASONRY NOTES DECLARES THAT THE
 WALLS ARE DESIGNED TO THE ASCE5/ACI
 530STANDARD, YET THE INFORMATION IN ACI
 5301.2.1 THAT IS DIRECTED TO APPEAR ON
 THE PROJECT DRAWINGS IS MISSING.
 THINGS LIKE F'M, GROUT TEST REQ. AND
 OTHERS.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561
 -233-5025 FOR MORE INFORMATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-10 Cont ID  
Sent By hpiskura Date 2002-06-06 Time 13:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***