Plan Review Details - Permit 02050217
Plan Review Stops For Permit 02050217
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-15 Cont ID  
Sent By jwitmer Date 2002-05-15 Time 13:15 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-05-15 00:00:00BUILDING PLAN REVIEW
 PROVISO
 02050217/ 700 NORTHPOINT PKWY/ 500
  
 THE PLANS DO NOT INDICATE ANY PENETRA-
 TIONS OF FIRE RATED WALLS NOR HORIZONTAL
 ASSEMBLIES (FLOORS). IF PENETRATIONS ARE
 REQUIRED, SUBMITTAL FOR THROUGH PENETRA-
 TIONS FOR FIRE RATED WALLS SHALL COMPLY
 WITH 705.5.1.1OR 705.5.1.2.
 PENETRATIONS THROUGH HORIZONTAL ASSEM-
 BLIES SHALL COMPLY WITH 705.6.1.1 OR
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-22 Cont ID  
Sent By dpalmer Date 2002-05-22 Time 06:04 Rev Time 0.00
Received By dpalmer Date 2002-05-22 Time 05:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-30 Cont ID  
Sent By mcarsill Date 2002-05-30 Time 13:02 Rev Time 0.00
Received By mcarsill Date 2002-05-30 Time 13:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-29 Cont ID  
Sent By pkrauss Date 2002-05-29 Time 09:54 Rev Time 0.40
Received By pkrauss Date 2002-05-29 Time 09:43 Sent To  
Notes
2002-05-29 00:00:00PROVISO:
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 PRESSURE DIFFERNTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001" WC OR
 LESS. PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH PRESSURE
 ZONE TO THE LOW ZONE.
  
 AS PER 2001 FBC(M) 602.2.1, MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NON -
 COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND SMOKE -
 DEVELOPED INDEX OF NOT MORE THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84.
  
 FIRE DAMPERS (NEW OR EXISTING) ARE NOT
 IDENTIFIED ON PLAN.PLEASE REVISE PLANS
 TO INDICATE LOCATIONS OF ALL FIRE OR
 FIRE/SMOKE DAMPERS.2001 FBC(M) 607.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-05-30 Cont ID  
Sent By mcarsill Date 2002-05-30 Time 13:03 Rev Time 0.00
Received By mcarsill Date 2002-05-30 Time 13:03 Sent To  
Notes
***NONE***