Plan Review Details - Permit 02050217
| Plan Review Stops For Permit 02050217 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2002-05-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-05-15 |
Time |
13:15 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-15 00:00:00 | BUILDING PLAN REVIEW | | | PROVISO | | | 02050217/ 700 NORTHPOINT PKWY/ 500 | | | | | | THE PLANS DO NOT INDICATE ANY PENETRA- | | | TIONS OF FIRE RATED WALLS NOR HORIZONTAL | | | ASSEMBLIES (FLOORS). IF PENETRATIONS ARE | | | REQUIRED, SUBMITTAL FOR THROUGH PENETRA- | | | TIONS FOR FIRE RATED WALLS SHALL COMPLY | | | WITH 705.5.1.1OR 705.5.1.2. | | | PENETRATIONS THROUGH HORIZONTAL ASSEM- | | | BLIES SHALL COMPLY WITH 705.6.1.1 OR | | | ANY QUESTIONS PLEASE CALL, | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | DEPARTMENT OF CONSTRUCTION SERVICES | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT. 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-05-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-22 |
Time |
06:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-22 |
Time |
05:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-05-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-30 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-30 |
Time |
13:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-05-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-29 |
Time |
09:54 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-05-29 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2002-05-29 00:00:00 | PROVISO: | | | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | PRESSURE DIFFERNTIALS ACROSS CLOSED | | | DOORS WHERE RETURNS ARE CENTRALLY | | | LOCATED SHALL BE LIMITED TO .001" WC OR | | | LESS. PROVIDE AIR DUCT PATHWAYS OR AIR | | | TRANSFER PATHWAYS FROM THE HIGH PRESSURE | | | ZONE TO THE LOW ZONE. | | | | | | AS PER 2001 FBC(M) 602.2.1, MATERIALS | | | EXPOSED WITHIN PLENUMS SHALL BE NON - | | | COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD | | | INDEX OF NOT MORE THAN 25 AND SMOKE - | | | DEVELOPED INDEX OF NOT MORE THAN 50 WHEN | | | TESTED IN ACCORDANCE WITH ASTM E 84. | | | | | | FIRE DAMPERS (NEW OR EXISTING) ARE NOT | | | IDENTIFIED ON PLAN.PLEASE REVISE PLANS | | | TO INDICATE LOCATIONS OF ALL FIRE OR | | | FIRE/SMOKE DAMPERS.2001 FBC(M) 607.6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2002-05-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-30 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-30 |
Time |
13:03 |
Sent To |
|
|
| Notes |
|
|
|