Plan Review Details - Permit 02050166
Plan Review Stops For Permit 02050166
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-06 Cont ID  
Sent By pkrauss Date 2002-05-06 Time 12:17 Rev Time 0.30
Received By pkrauss Date 2002-05-06 Time 12:01 Sent To  
Notes
2002-05-06 00:00:00PROVISO:
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 BALANCED AIR RETURN REQUIRED - PRESSURE
 DIFFERENTIALS ACROSS CLOSED DOORS WHERE
 RETURNS ARE CENTERALLY LOCATED SHALL BE
 LIMITED TO .001" WC OR LESS.PROVIDE
 AIR DUCT PATHWAYS OR AIR TRANSFER PATH-
 WAYS FROM HIGH PRESSURE ZONE TO LOW
 ZONE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.