| Plan Review Stops For Permit 02050157 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-05-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-09 |
Time |
17:19 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-05-09 |
Time |
17:14 |
Sent To |
|
|
| Notes |
| 2002-05-09 00:00:00 | ~~~~~~~~~~~~~~~~~PROVISO!~~~~~~~~~~~~~~~ | | | | | | PLEASE COMPLY WITH THE FOLLOWING: | | | | | | 1} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 2} SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | IN THE VICINITY OF BEDROOMS AND CLOSE | | | PROXIMITY OF STIRWAYS. 2-5.2.1.3 | | | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 | | | | | | 3} PLEASE NOTE, EITHERMISSING | | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | | PER 210-70 OF THE NEC. | | | | | | 4} PLEASE INSTALL REQ`D ARC | | | FAULT PROTECTED CIRCUITS AND LIST SAME | | | ON PANEL SCHEDULE PER 210-10. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2002-05-07 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-07 |
Time |
06:35 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-05-07 |
Time |
06:23 |
Sent To |
|
|
| Notes |
|
|
|