Plan Review Details - Permit 02050144
Plan Review Stops For Permit 02050144
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-08-29 Cont ID  
Sent By jwitmer Date 2002-08-29 Time 08:04 Rev Time 1.00
Received By jwitmer Date 2002-08-29 Time 08:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-07-15 Cont ID  
Sent By jwitmer Date 2002-07-15 Time 07:34 Rev Time 1.50
Received By jwitmer Date 2002-07-15 Time 07:33 Sent To  
Notes
2002-07-15 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02050144
 ADD: 2505 W METROCENTE
 CONT: PROJECT CONTROL
 TEL: (561) 445-8588
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SEE TABLE 705.1.2 EXIT DOORS 302 &
 304 REQUIRE 1HR PROTECTIVE.
  
 2) MISSING INFORMATION ON TENANT ACCESS
 CORRIDOR DOORS, DOOR #, AND RATING.
  
 3) THE LARGE SUITE INDICATES SIDELITES
 BETWEEN THE DOUBLE FRONT DOORS, THERE IS
 NO INFORMATION ON THE WINDOW PROTECTIVES
  
 4) NOTE: TABLE 705.1.2 NOTE 6 SEE EXEMPT
 IONS UNDER BUILD FOR RATING OF RESTROOM
 DOORS PROVIDED (A-D)
  
 5) ROOM 332 SHOWER SHALL REQUIRE SAFETY
 GLASS IN SWING DOOR, HAZARDOUS LOCATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-15 Cont ID  
Sent By jwitmer Date 2002-05-15 Time 09:01 Rev Time 0.00
Received By jwitmer Date 2002-05-15 Time 07:34 Sent To  
Notes
2002-05-15 00:00:00BUILDING PLAN REVIEW
 PRMIT# 02050144
 2505 W METROCENTRE BLVD
 CONT: PROJECT CONTROLS OF FL
 TEL:(305) 637-8000
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 2)1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.
 2001 FL BLD CODE ALLOWS FOR 1/3RD THE
 DISTANCE FOR SPRINKLERED BUILDINGS. THE
 LARGER OF THE 2 OFFICES HAS 16' BETWEEN
 THE EGRESS DOORS, 32.33' IS REQUIRED.
 IF BOTH UNITS ARE CONSIDERED AS ONE
 LARGE UNIT SINCE THERE IS A ADJOINING
 DOOR THE DIAGONAL DISTANCE IS 128'
 REQUIRING 42.66' BETWEEN EGRESS OPENINGS
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. SEE 4.13.6 FOR THE FOLLOWING
 DOORS:
 336A EXT SIDE
 336B INT SIDE
 34345 DEGREE ANGLE DOESN'T GIVE THE
 REQUIRED CLEARENCES
  
 5) RESTROOMS 314 THE CONFIGURATION ISNOT
 CORRECT NOR INSWING DOOR.4.22.2 DOORS
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE. SEE FIG-
 URE 28 FOR THE ENTRY FOR WATER CLOSETS
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412
 OT

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-09-16 Cont ID  
Sent By dpalmer Date 2002-09-16 Time 13:40 Rev Time 0.50
Received By dpalmer Date 2002-09-16 Time 13:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-08-28 Cont ID  
Sent By dpalmer Date 2002-08-28 Time 20:37 Rev Time 0.30
Received By dpalmer Date 2002-08-28 Time 20:37 Sent To  
Notes
2002-08-28 00:00:00*********** NOTE ****************
  
  
 COVER SHEET WAS NOTED THAT ALL OLD/VOID-
 ED SHEETS NEED TO BE REMOVED BY
 CONTRACTOR TO COMPLETE TWO CLEAN SETS
 FOR FILE AND FIELD.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-18 Cont ID  
Sent By dpalmer Date 2002-07-18 Time 13:05 Rev Time 0.00
Received By dpalmer Date 2002-07-18 Time 12:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-21 Cont ID  
Sent By dpalmer Date 2002-05-21 Time 17:54 Rev Time 0.00
Received By dpalmer Date 2002-05-21 Time 17:54 Sent To  
Notes
2002-05-21 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT SEPARATE PLANS
 FOR SEPARATE TENANT SPACES.
 PLEASE NOTE PERMIT APPLICATION DOES NOT
 HAVESUITE #`S ON IT. NEEDS TO BE
 SEPARATED.
  
 2)NOTE: PLEASE NOTE FIRE /BLDG REVIEW
 COMMENTS WILL HAVE CHANGES TO ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-08-22 Cont ID  
Sent By mcarsill Date 2002-08-22 Time 10:06 Rev Time 0.00
Received By mcarsill Date 2002-08-22 Time 10:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-07-19 Cont ID  
Sent By mcarsill Date 2002-07-19 Time 14:55 Rev Time 0.00
Received By mcarsill Date 2002-07-19 Time 14:55 Sent To  
Notes
2002-07-19 00:00:001) SEE BUILDING PLAN REVIEWER COMMENTS.
 THIS OFFICE CONCURS WITH THESE
 COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-05-14 Cont ID  
Sent By mcarsill Date 2002-05-14 Time 12:09 Rev Time 0.00
Received By mcarsill Date 2002-05-14 Time 12:09 Sent To  
Notes
2002-05-14 00:00:001) DESIGN CRITERIA FOR FIRE SPRINKLER
 REMODEL NOTED ON PAGE F1-1 IS INCORRECT.
 IT SHOULD READ NFPA 13, 1999 EDITION.
  
 2) PLEASE EXPLAIN EXITING RATIONALE FOR
 LARGE SPACE LOCATED ON THE THIRD FLOOR.
 EXIT DOORS DO NOT APPEAR TO BE PROPERLY
 SEPARATED FROM ONE ANOTHER. A SINGLE
 FIRE COULD BLOCK BOTH EXITS. DURING THE
 PLAN REVIEW FOR THE SHELL, CITY STAFF
 EXPRESSED CONCERNS ABOUT FUTURE EXITING
 FROM THE TENANT SPACES.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE
 WALLS AND CEILINGS.
  
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM REMODELS WITHIN
 THE TENANT SPACES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-08-29 Cont ID  
Sent By ndenmark Date 2002-08-29 Time 09:39 Rev Time 0.33
Received By ndenmark Date 2002-08-29 Time 09:39 Sent To  
Notes
2002-08-29 00:00:00PROVISO;
  
 IF EQUIPMENT FAN CAPACITY CAN EXCEED
 2000CFM OR IF AIR IS INTERMIXED WHERE
 SEVERAL UNITS COMBINED IS GREATER THAN
 2000 CFM FAN SHUT DOWN BY DUCT SMOKE
 DETECTOR WILL BE REQUIRED.
 PROVIDE EQUIPMENT MANUFACTURES
 INFORMATION SHOWING THAT THE EQUIPMENT
 CAN UNDER NO CONFIGURATION PRODUCE
 GREATER THAN 20000CFM FOR THE 5 TON
 UNITS PRIOR TO FINAL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-07-25 Cont ID  
Sent By pkrauss Date 2002-07-25 Time 08:21 Rev Time 0.45
Received By pkrauss Date 2002-07-25 Time 07:33 Sent To  
Notes
2002-07-25 00:00:00DENIED:2ND REQUEST
  
 REFERENCE PLAN REVIEW BY NANCY DENMARK
 DATED 5/30/02.
  
 ITEM #3 - PROVIDE OUTSIDE ARI CALCS AS
 PER ASHRAE 62-89.PLEASE INDICATETHE
 NUMBER OF PEOPLE PER AREA TO VERIFY THE
 AMOUNT OF OUTSIDE AIR PROVIDED.
  
 ITEM #4 - FAN SHUTDOWN BY DUCT SMOKE
 DETECTOR TO BE TESTED.PLEASE IDENTIFY
 LOCATION OF ALL DUCT SMOKE DETECTORS ON
 THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-30 Cont ID  
Sent By ndenmark Date 2002-05-30 Time 12:16 Rev Time 0.50
Received By ndenmark Date 2002-05-30 Time 07:42 Sent To  
Notes
2002-05-30 00:00:00DENIED:
 1) FLOOR PLAN A1-1 INDICATES TWO SPACES
 SEPARATED BY RATED PARTITION. MECH PLAN
 HAS FIRE DAMPER LOCATIONS NOT IN RATED
 WALL PER THE FLOOR PLAN. PLEASE SHOW
 FIRE DAMPERS IN ALL DUCTS PENETRATING
 RATED WALLS.
 2) WHERE IS VAV- 2-2?
 3) PROVIDE OUTSIDE AIR CALCULATIONS FOR
 EACH SPACE PER ASHRAE 62-89 OR TABLE
 403.3 FMC
 4) FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 TO BE TESTED.
  
 NANCY DENMARK
 CHIEF MECHANICAL INSPECTOR
 (561) 659-8096 EXT 8221

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-09-16 Cont ID  
Sent By kstevens Date 2002-09-16 Time 10:53 Rev Time 0.00
Received By kstevens Date 2002-09-16 Time 10:53 Sent To  
Notes
2002-09-16 00:00:00PASSED/PROVISO
  
 LAV CABINET SHALL BE REMOVABLE IN ROOM
 #332 FOR ADAPTABILITY.

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-08-29 Cont ID  
Sent By kstevens Date 2002-08-29 Time 18:47 Rev Time 0.00
Received By kstevens Date 2002-08-29 Time 18:33 Sent To  
Notes
2002-08-29 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A4-2 PLEASE PROVIDE DETAILS FOR
 BACKING IN ADAPTABLE TOILET ROOM #332.
 SEE SECTION 11-4.26.3(2)(3)(4). ALSO
 SHOW THE GUAGE OF THE GALVANIZED SHEET
 METAL.
 2) SHT A4-2 W/C SHALL BE 18" OFF WALL.
 3) SHT A4-2 LAV SHALL BE 15" OFF WALL &
 CABINETS SHALL BE REMOVABLE FOR CLEAR
 FLOOR SPACE OR 2' OFF WALL AND PARALLEL
 APPROACH. HEIGHT SHALL BE 34"
 4) SHT P2-1 MANUFACTURE INFORMATION NOT
 SUBMITTED SHOWING NSF APPROVAL. (SEE #6
 FROM PREVIOUS REVIEW)
 5) SHT P1-3 BACKFLOW ON WATER SERVICE
 SHALL BE MAXIMUM OF 4'0" OFF FLOOR FOR
 SERVICE AND SHALL DRAIN INTO A FLOOR
 SINK OR OTHER ACCEPTABLE RECEPTICLE.
 6) SHT P1-3 WATER HAMMER ARRESTORS SHALL
 BE LOCATED NEAR THE FIXTURES IN AN EFF-
 ECTIVE RANGE" NOT AT THE TOP OF THE DROP
 OR ON THE MAIN ABOVE THE CEILING. (SEE
 #10 FROM PREVIOUS REVIEW)
 7) FROM PREVIOUS REVIEW, FIXTURE UNITS
 FOR RISERS TO BE SHOWN ON SANITARY RISER
 DIAGRAM. SHOW ACCUMULATED DFU'S IN SYS-
 TEM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-07-22 Cont ID  
Sent By kstevens Date 2002-07-22 Time 18:50 Rev Time 0.00
Received By kstevens Date 2002-07-22 Time 18:50 Sent To  
Notes
2002-07-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED.
 2) SHT A1-1 ROOM #332, SHOWER BATHROOM
 SHALL BE ADAPTABLE. 11-4.1.3(11) PLEASE
 PROVIDE DETAILS.
 3) SHT A1-1 SEPARATE TENANTS, MINIMUM
 FACILITIES REQUIRE A DRINKING FOUNTAIN
 AND SERVICE SINK. SERVICE SINK NOT FOUND
 IN TENANT "B" SPACE, AND DRINKING FOUNT-
 AINS NOT FOUND IN SPACE "A" OR "B".
 4) SHT A2-1 DETAILS #7 RM #312 & #16 RM
 #345, SINKS SHALL COMPLY WITH 11-4.24
 AND ALL SUBSECTIONS. PROVIDE DETAILS.
 5) SHT P1-3 FLOOR DRAIN AT WATER HEATER
 NOT APPROVED. ALL INDIRECT WASTE SHALL
 DRAIN INTO A FLOOR SINK. SEC 802.3
 6) SHT P2-1 MANUFACTURE INFORMATION RE-
 QUIRED FOR FILTER. MUST BE NSF APPROVED.
 7) HEATER PAN REQUIRED SEC. 504.8
 8) BACKFLOW REQUIRED ON WATER SERVICE.
 9) BACKFLOW REQUIRED FOR 3/4" LINE TO
 LASIK MACHINE.
 10) WATER RISER DIAGRAM REQUIRED. WATER
 HAMMER ARRESTORS ARE REQUIRED FOR QUICK
 CLOSING VALVES. 604.9 - LOCATE NEAR FIX-
 TURE NOT AT TOP OF DROP.
 11) THERMAL EXPANSION CONTROL REQUIRED
 PER SEC 607.3 & 607.3.2. SHOW ON HEATER
 DETAIL.
 12) SANITARY RISER DIAGRAM REQUIRED FOR
 ENTIRE BLDG. SHOW FIXTURE UNITS FOR EACH
 RISER AS IT ACCUMULATES IN DRAIN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-03 Cont ID  
Sent By kstevens Date 2002-06-03 Time 13:43 Rev Time 0.00
Received By kstevens Date 2002-06-03 Time 13:43 Sent To  
Notes
2002-06-03 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A1-1 ROOM #332, SHOWER BATHROOM
 SHALL BE ADAPTABLE. 11-4.1.3(11) PLEASE
 PROVIDE DETAILS.
 2) SHT A1-1 SEPARATE TENANTS, PLEASE
 PROVIDE MINIMUM FACILITIES CALCULATIONS
 FOR EACH TENANT SPACE. PROVIDE SQUARE
 FOOTAGE FOR EACH SPACE SO FIXTURES CAN
 BE CALCULATED. DRINKING FOUNTAINS AND
 SERVICE SINKS REQUIRED ECT.
 3) SHT A2-1 DETAILS #7 RM #312 & #16 RM
 #345 SINKS SHALL COMPLY WITH 11-4.24 AND
 ALL SUBSECTIONS.
 4) SHT A1-1 TOILET ROOM #314, DOOR SHALL
 NOT OPEN INTO THE CLEAR FLOOR SPACE OF
 ANY FIXTURE. 11-2.22.2
 5) SHT P1-3 FLOOR DRAIN AT WATER HEATER
 NOT APPROVED. ALL INDIRECT WASTE SHALL
 DRAIN INTO A FLOOR SINK. SEC 802.3
 6) SHT P2-1 MANUFACTURE INFORMATION RE-
 QUIRED FOR THE POINT OF USE WATER HEATER
 FOR LISTING BY APPROVED AGENCY.
 7) SHT P2-1 MANUFACTURE INFORMATION RE-
 QUIRED FOR FILTER. MUST BE NSF APPROVED.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377