Plan Review Details - Permit 02050118
Plan Review Stops For Permit 02050118
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-30 Cont ID  
Sent By hpiskura Date 2002-05-30 Time 15:30 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-30 00:00:00PROVIDE TWO SETS OF THE SAMEPLAN.
  
 THE ADDITION OF THE MEZZANINES IS NEW
 FLOOR AREA AND IS SUBJECT TO IMPACT
 FEES COLLECTED BY THE COUNTY.THE
 PERMIT PLANS MUST BE STAMPED BY THAT
 OFFICE AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 CALL 561-233-5025 FOR MORE INFORMATION.
  
 SHEET A1 CITES THE WRONG CODES UNDER
 THEBUILDING DATA HEADING.REVISE AS
 NECESSARY AND ENSURE COMPLIANCE WITH
 THE 2001 FBC.
  
 PROVIDE A CONSTRUCTION DETAIL FOR THE
 MEZZANINES INCLUDING THE FIRE
 PROTECTION.ALSO, SHOW THE DETAILS AND
 LOAD REQUIREMENT FOR THE GUARDRAIL.
  
 SHOW SPECIFIC CONNECTION DETAILS FOR
 THEVARIOUS SOFFIT CONSTRUCTIONS SUBJECT
 TO GRAVITY LOADS.
  
 SHOW THE SPIRAL STAIR DETAILS IN
 ACCORDANCE WITH FBC 1007.8.2.1.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-22 Cont ID  
Sent By dpalmer Date 2002-05-22 Time 20:09 Rev Time 0.00
Received By dpalmer Date 2002-05-22 Time 19:51 Sent To  
Notes
2002-05-22 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE NOTE TWO DIFFERENT SETS
 PLANS WERE SUBMITTEDFOR REVIEW. PLEASE
 SUBMIT ONLY ONE SET. PLEASE ALSO NOTE
 CIRCUIT #`S ON SETS NEED TO CORRELATE
 WITH SUBMITTED PANEL SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-05 Cont ID  
Sent By mcarsill Date 2002-06-05 Time 09:50 Rev Time 0.00
Received By mcarsill Date 2002-06-05 Time 09:50 Sent To  
Notes
2002-06-05 00:00:001) PLEASE PROVIDE MORE DETAILS ON
 SPIRAL STAIRS.
  
 2) PLEASE INDICATE FIRE PROTECTION FOR
 MEZZANINE.
  
 3) PLEASE PROVIDE DETAILS ON THE
 PRESCRIPTIVE CODE REQUIREMENTS FOR
 THE HANDRAILS.
  
 4) DIFFERENT PLANS SUBMITTED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-29 Cont ID  
Sent By ndenmark Date 2002-05-29 Time 15:39 Rev Time 0.33
Received By ndenmark Date 2002-05-29 Time 15:39 Sent To  
Notes
2002-05-29 00:00:00DENIED:
 REQUIRE TWO SETS OF THE SAME PLAN FOR
 REVIEW
 NOTE THE CONDENSATE DRAIN LINE SHALL NOT
 TIE INTO THE SANITARY SEWER
  
  
 QUESTIONS CALL:
 NANCY DENMARK
 CHIEF MECHANICAL INSPECTOR
 (561) 659-8096 EXT 8221

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-25 Cont ID  
Sent By kstevens Date 2002-05-25 Time 14:42 Rev Time 0.00
Received By kstevens Date 2002-05-25 Time 15:12 Sent To  
Notes
2002-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PLEASE NOTE THAT TWO DIFFERENT SETS
 OF PLANS HAVE BEEN SUBMITTED FOR PLAN
 REVIEW. SUBMIT ONLY ONE SET OF PLANS.
 2) PLEASE SUBMIT DETAILS FOR SINK. SEC
 4.24.3 KNEE SPACE, 4.24.5 CLEAR FLOOR
 SPACE, & 4.24.6 EXPOSED PIPES. PARALLEL
 APPROACH EXCEPTABLE IF SINK CENTERED IN
 48" MEASURMENT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377