Plan Review Details - Permit 02050107
Plan Review Stops For Permit 02050107
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-30 Cont ID  
Sent By btrobaug Date 2002-05-13 Time 13:53 Rev Time 0.00
Received By btrobaug Date 2002-05-13 Time 13:37 Sent To P
Notes
2002-05-13 00:00:00~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~~
 NOT ENOUGH INFORMATION FOR
 REVIEW.PLEASE PROVIDE INFORMATION ON
 THE SERVICE.
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PROVIDE A RISER DIAGRAM.
  
 3} PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-17 Cont ID  
Sent By pkrauss Date 2002-05-17 Time 07:48 Rev Time 0.35
Received By pkrauss Date 2002-05-17 Time 07:15 Sent To R
Notes
2002-05-17 00:00:00MECH PERMIT 02050110

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-16 Cont ID  
Sent By btrobaug Date 2002-05-30 Time 14:47 Rev Time 0.00
Received By kstevens Date 2002-05-16 Time 14:31 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-05-30 Cont ID  
Sent By pkrauss Date 2002-05-17 Time 07:49 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-09 Cont ID  
Sent By sgraham Date 2002-05-09 Time 15:15 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***