Plan Review Details - Permit 02050091
| Plan Review Stops For Permit 02050091 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-06-28 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2002-06-28 |
Time |
12:46 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-05-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-15 |
Time |
11:54 |
Rev Time |
1.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-28 00:00:00 | *******************FAILED************* | | | | | | THE CURRENT CODE FOR PALM BEACH COUNTY | | | IS THE FBC 2001. DESIGN FOR WINDLOAD | | | IS 140 MPH. | | | | | | 1.DRAWINGS DO NOT REFERENCE THE CORRECT | | | BUILDING CODE | | | 2. ALL PRODUCT APPROVALS SUBMITTED ARE | | | EXPIRED.NEED "TWO" COPIES OF ALL | | | PRODUCT APPROVALS: WINDOWS, DOORS, ROOF | | | MATERIALS. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH: BUILDING PLANS EXAMINER | | | 659-8096 EXT. 8394 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-05-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-13 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-05-10 |
Time |
07:12 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-05-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-15 |
Time |
11:47 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-05-15 |
Time |
11:21 |
Sent To |
B |
|
| Notes |
| 2002-05-15 00:00:00 | PROVIDE THE FOLLOWING INFORMATION WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | PROVIDE INFORMATION FOR EQUIPMENT BEING | | | INSTALLED (MAKE, MODEL, BTU, SEER ETC) | | | | | | PLEASE NOTE MAXIMUM DEVELOPED LENGTH FOR | | | THE DRYER EXHAUST SHALL NOT EXCEED 25 | | | FT FROM DRYER LOCATION TO OUTLET WITH A | | | 5 FT REDUCTION FOR EA 90 DEGREE BEND & | | | 2 1/2 FT REDUCTION FOR EA 45 DEGREE | | | BEND. 2001 FBC(M) 504.6. | | | | | | PROVIDE A BACKDRAFT DAMPER AS PER 2001 | | | FBC(M) 504.4. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-05-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-13 |
Time |
12:23 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2002-05-13 |
Time |
19:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-05-06 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-05-06 |
Time |
12:23 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|