Plan Review Details - Permit 02050051
Plan Review Stops For Permit 02050051
Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-07 Cont ID  
Sent By kstevens Date 2002-06-07 Time 08:44 Rev Time 0.00
Received By kstevens Date 2002-06-07 Time 08:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-19 Cont ID  
Sent By pschmitz Date 2002-05-19 Time 06:44 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-05-19 00:00:00PLUMBING PLAN REVIEW, DENIED.PES
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE STANDARD GAS CODE SECS. 305.2 THRU
 305.4 AND TABLES 305.4(A) THRU 305.4(E).
 3. TYPE OF GAS, (LP OR NATURAL)
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS, 561-659-8096