Plan Review Details - Permit 02050026
Plan Review Stops For Permit 02050026
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-10-17 Cont ID  
Sent By lmartine Date 2002-10-17 Time 17:36 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-10-17 00:00:00REVISION TO ADD LADDER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-30 Cont ID  
Sent By jwitmer Date 2002-05-15 Time 07:11 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-05-30 00:00:005/30/02 MEET WITH ARCH TODAY, WILL
 PROVISO, LETTER SHALL BE REQUIRED STAT-
 ING THAT THE 2ND FLOOR WILL NOT BE USED,
 THE STAIRS WILL BE REMOVED, ELECTRIC
 AND MECHICAL WILL BE REMOVED AND THE
 DOORWAY WALLED UP. THE FLOOR/CEILING
 ASSEMBLY REPLACED TO SATISFY THE
 REQUIRED RATING.
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412
 R
2002-05-15 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW# 02050026
 124 N DIXIE
 CONT: INTERNATIONAL CONSTRUCTION
 TEL: (305) 867-8127
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2)1004.1.2 EVERY ROOM OR TENANT SPACE
 SHALL BE PROVIDED WITH A MINIMUM OF ONE
 MEANS OF EGRESS. PLANS INDICATE A SECOND
 FLOOR ABOVE AND THE REMOVAL OF A STAIR-
 WELL. IS THERE EGRESS FROM A NOTHER
 RATED STAIR? IS THE REMOVAL OF THIS
 STAIR A MEANS OF EGRESS OR A SECONDARY
 STAIRWAY?
 MEANS OF EGRESS: A CONTINUOUS AND
 UNOBSTRUCTED WAY OF TRAVEL FROM ANY
 POINT IN A BUILDING OR STRUCTURE TO A
 PUBLIC WAY, CONSISTING OF THREE SEPERATE
 AND DISTINCT PARTS: (1) THE WAY OF THE
 EXIT ACCESS, (2) THE EXIT, AND (3) THE
 THE WAY OF OF THE EXIT DISCHARGE.
 A MEANS OF EGRESS COMPRISES THE VERTICAL
 AND HORIZONTAL WAYS OF TRAVEL AND
 INCLUDE THE INTERVENING ROOM SPACE,DOORS
 CORRIDORS,PASSAGEWAYS,BALCONIES, STAIRS,
 RAMPS, ENCLOSURES, LOBBIES, HORIZONTAL
 EXITS, COURTS AND YARDS.
  
 3)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 4) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-07-19 Cont ID  
Sent By dpalmer Date 2002-07-19 Time 15:52 Rev Time 0.00
Received By dpalmer Date 2002-07-19 Time 15:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-06-17 Cont ID  
Sent By dpalmer Date 2002-06-17 Time 18:03 Rev Time 0.00
Received By dpalmer Date 2002-06-17 Time 17:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-06-11 Cont ID  
Sent By dpalmer Date 2002-06-11 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2002-06-11 Time 18:26 Sent To  
Notes
2002-06-11 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT OLD SHEETS NEED
 TO BE TAKEN OUT AND HAVE NEW SHEETS
 ADDED. PLEASE CORRELATE AND MAKE TWO
 NEW REVISED SETS FOR REVIEW.
 THERE ARE SEPARATE SHEETS AND TWO SETS
 ECT. PLEASE NOTE ONE SET OF OLD SHEETS
 MAY BE STAPLED TOGETHER LABELED "OLD"
 AND SUBMITTED WITH NEW/REVISED.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-15 Cont ID  
Sent By dpalmer Date 2002-05-15 Time 15:50 Rev Time 0.00
Received By dpalmer Date 2002-05-15 Time 15:50 Sent To  
Notes
2002-05-15 00:00:00****************** UNSAT *************
  
 1 )NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
  
 2) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 215-2,215-3,230-42
  
 3)NOTE: PLEASE CORRELATE PANEL SCHEDULES
 W/ RISER DIAGRAM. ONE SHOWS NEW B AND
 OTHER NEW A ??
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-06-05 Cont ID  
Sent By mcarsill Date 2002-06-05 Time 08:53 Rev Time 0.00
Received By mcarsill Date 2002-06-05 Time 08:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-12 Cont ID  
Sent By pkrauss Date 2002-06-11 Time 14:08 Rev Time 0.35
Received By pkrauss Date 2002-06-11 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-28 Cont ID  
Sent By ndenmark Date 2002-05-28 Time 15:12 Rev Time 0.50
Received By ndenmark Date 2002-05-28 Time 15:12 Sent To  
Notes
2002-05-28 00:00:00PLAN REVIEW NOTES: DENIED
 1. PROVIDE BALANCED RETURN AIR PER 601.4
 FMC.
 2. SHOW LOCATION OF OUTSIDE AIR
 3. EXPLAIN WHAT DUCT THROUGH SECOND
 FLOOR TO BE SEALED.
 4. DOES EXHAUST DUCT PENETRATE THROUGH
 SECOND FLOOR?
 5. SERVICE TO AHU NOT TO BE OBSTRUCTED
 BY OTHER COMPONENTS OF BUILDING
 CONSTRUCTION

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-15 Cont ID  
Sent By kstevens Date 2002-06-15 Time 12:47 Rev Time 0.00
Received By kstevens Date 2002-06-15 Time 12:47 Sent To  
Notes
2002-06-15 00:00:00PASSED/PROVISO
  
 RPZ BACKFLOW REQUIRED ON WATER SERVICE

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-25 Cont ID  
Sent By kstevens Date 2002-05-25 Time 14:06 Rev Time 0.00
Received By kstevens Date 2002-05-25 Time 14:06 Sent To  
Notes
2002-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) ROUTE PLANS TO DEPT OF BUSINESS REGU-
 LATION HOTEL AND RESTAURANT DIVISION FOR
 REVIEW BEFORE RESUBMITTING TO WPB REVIEW
 2) SHT A-5/5 SANITARY RISER DIAGRAM,
 SAMPLE POINT REQUIRED FOR 3 COMPARTMENT
 SINK, FLOOR DRAINS (WORK AREA), AND MOP
 SINK. AFTER THESE FIXTURES INSTALL SAM-
 PLE POINT. AFTER SAMPLE POINT TIE INTO
 SANITARY DRAIN.
 3) SHT A-5/5 HUB DRAIN NOT APPROVED FOR
 INDIRECT WASTE. (ICE/SODA MACHINE) FLOOR
 SINK REQUIRED FOR ALL INDIRECT WASTE.
 SEC 802.3
 4) SHT A-5/5 WATER FILTRATION SYSTEM
 SHALL BE NSF APPROVED. PLEASE PROVIDE
 MANUFACTURE INFORMATION.
 5) SHT A5/5 DRINKING FOUNTAIN REQUIRED
 TABLE 403.1. ALSO SEE 410.1 BOTTLED
 WATER REQUIREMENT ARI-1010, IF USED SUB-
 MIT MANUF. INFO SHOWING COMPLIANCE.
 6) SHT A-1/5 MINIMUM SIZE OF HDCP TOILET
 ROOM SHALL BE 5'3". 5'2" SHOWN
 7) SHT A-5/5 PLUMBING NOTES #4 AIR CHAM-
 BERS ARE NOT APPROVED. LOCATE WATER HAM-
 MERS NEAR FIXTURES IN AN "EFFECTIVE
 RANGE" NOT AT TOP OF DROPS.
 8) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377