Plan Review Details - Permit 02041940
Plan Review Stops For Permit 02041940
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-24 Cont ID  
Sent By lmartine Date 2002-12-24 Time 14:24 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-07-23 Cont ID  
Sent By jwitmer Date 2002-07-23 Time 13:11 Rev Time 0.75
Received By jwitmer Date 2002-07-23 Time 13:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-15 Cont ID  
Sent By hpiskura Date 2002-05-15 Time 13:53 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-15 00:00:00THE EXIT DOOR FROM THE OPEN OFFICE AREA
 SHOWN WITH AN "EXISTING 6" STEP" IS
 PROHIBITTED BY FBC 1012.1.3.PLEASE
 REVISE AS NECESSARY.
  
 ALSO SEE FBC 1012.1.4 REGARDING THE
 DOORS ON THE TOILET ROOMS.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-12-03 Cont ID  
Sent By dpalmer Date 2002-12-03 Time 07:21 Rev Time 0.25
Received By dpalmer Date 2002-12-03 Time 07:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-11-14 Cont ID  
Sent By btrobaug Date 2002-11-14 Time 18:46 Rev Time 0.00
Received By btrobaug Date 2002-11-14 Time 18:43 Sent To P
Notes
2002-11-14 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE PENCILED IN RECEPTACLES ON SHEET
 E-2 ARE IN VIOLATION OF FS STATUTES.THE
 ENGINEER OF RECORD MUST MAKE ALL
 CHANGES.
  
 RESUBMIT FOR REVIEW AFTER ALL
 ENGINEERING CHANGES ARE COMPLETE,SIGNED
 AND SEALED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-08-30 Cont ID  
Sent By btrobaug Date 2002-08-30 Time 17:18 Rev Time 0.50
Received By btrobaug Date 2002-08-30 Time 17:10 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-16 Cont ID  
Sent By dpalmer Date 2002-07-16 Time 19:19 Rev Time 0.00
Received By dpalmer Date 2002-07-16 Time 19:19 Sent To  
Notes
2002-07-16 00:00:00*************** NOTE *****************
  
 NOTES REDLINED ON PLANS FOR ALL CONTINUO
 S LOADS TO REFIGURED AT 125% AS ASKED
 FOR ON FIRST REVIEW.
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-21 Cont ID  
Sent By dpalmer Date 2002-05-21 Time 16:51 Rev Time 0.00
Received By dpalmer Date 2002-05-21 Time 15:32 Sent To  
Notes
2002-05-21 00:00:00************UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%.
 215-2/-3,230-42
  
 2)NOTE: PLEASE NOTE AIC RATING IS SHOWN
 FOR PANEL BUT NEEDS TO SHOW MAIN DISC.
 110-9
  
 3)NOTE: PLEASE NOTE PLANS NEED TO HAVE
 "CITY PLACE" STAMP ON THEM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-12-19 Cont ID  
Sent By mcarsill Date 2002-12-19 Time 14:24 Rev Time 0.00
Received By mcarsill Date 2002-12-19 Time 14:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-02 Cont ID  
Sent By mcarsill Date 2002-07-02 Time 09:40 Rev Time 0.00
Received By mcarsill Date 2002-07-02 Time 09:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-05-17 Cont ID  
Sent By mcarsill Date 2002-05-17 Time 10:48 Rev Time 0.00
Received By mcarsill Date 2002-05-17 Time 10:48 Sent To  
Notes
2002-05-17 00:00:001) THE EXIT DOOR FROM THE OPEN AREA
 SHOWN WITH AN EXISTING 6" STEP IS
 NOT ALLOWED PER FFPC 7.2.1.3. PLEASE
 REVISE PLANS AS NECESSARY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-17 Cont ID  
Sent By sthyng Date 2003-03-17 Time 11:37 Rev Time 0.00
Received By sthyng Date 2003-03-17 Time 11:37 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-26 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 18:13 Rev Time 0.00
Received By btrobaug Date 2002-11-26 Time 18:13 Sent To  
Notes
2002-11-26 00:00:00COMM BOARD #32./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-14 Cont ID  
Sent By btrobaug Date 2002-11-14 Time 18:46 Rev Time 0.00
Received By btrobaug Date 2002-11-08 Time 18:46 Sent To E
Notes
2002-11-13 00:00:00ROUTED FOR RE-STAMP

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-03-17 Cont ID  
Sent By sthyng Date 2003-03-17 Time 11:38 Rev Time 0.35
Received By pkrauss Date 2003-03-17 Time 15:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-12-26 Cont ID  
Sent By pkrauss Date 2002-12-26 Time 11:25 Rev Time 0.35
Received By pkrauss Date 2002-12-26 Time 10:51 Sent To  
Notes
2002-12-26 00:00:00MECH REV PERMIT 02100784

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-23 Cont ID  
Sent By pkrauss Date 2002-12-23 Time 09:59 Rev Time 0.30
Received By pkrauss Date 2002-12-23 Time 09:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-15 Cont ID  
Sent By kstevens Date 2002-11-19 Time 12:58 Rev Time 0.33
Received By ndenmark Date 2002-07-15 Time 15:28 Sent To  
Notes
2002-07-15 00:00:00PROVISO:
  
 AHU TO BE INSTALLED WITH RESPECT TO
 BUILDING CONSTRUCTION TO ALLOW FOR
 SERVICE AND REPLACEMENT OF EQUIPMENT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-28 Cont ID  
Sent By ndenmark Date 2002-05-28 Time 14:34 Rev Time 0.50
Received By ndenmark Date 2002-05-28 Time 14:34 Sent To  
Notes
2002-05-28 00:00:00PLAN REVIEW NOTES: DENIED
  
 1. PROVIDE OUTSIDE AIR CALCULATIONS PER
 TABLE 403.3 FMC
  
 NOTE: AIR HANDLING UNIT TO BE INSTALLED
 IN RELATION TO BUILDING CONSTRUCTION TO
 ALLOW FOR SERVICE PER 306.1 FMC

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-12-19 Cont ID  
Sent By kstevens Date 2002-12-19 Time 10:17 Rev Time 0.75
Received By kstevens Date 2002-12-19 Time 10:17 Sent To  
Notes
2002-12-19 00:00:00REVISION - CHANGE ROOM LAY OUT
 PROVISO- WATER COOLER REQUIRED

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-11-19 Cont ID  
Sent By kstevens Date 2002-11-19 Time 12:54 Rev Time 0.50
Received By kstevens Date 2002-11-19 Time 12:54 Sent To M
Notes
2002-11-19 00:00:00RESTAMP SET OF PLANS FOR CONTRACTOR

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-18 Cont ID  
Sent By btrobaug Date 2002-11-14 Time 18:52 Rev Time 0.00
Received By kstevens Date 2002-07-18 Time 17:51 Sent To  
Notes
2002-07-18 00:00:00PASSED/PROVISO
  
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 BETWEEN LAST TWO FIXTURES NOT AT TOP OF
 DROP

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-25 Cont ID  
Sent By kstevens Date 2002-05-25 Time 10:43 Rev Time 0.00
Received By kstevens Date 2002-05-25 Time 10:43 Sent To  
Notes
2002-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-1 MINIMUM FACILITIES REQUIRE A
 SERVICE SINK. TABLE 403.1
 2) SHT P-2 WATER ISOMETRIC, WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECT RANGE" NOT AT TOP OF
 DROP AS SHOWN.
 3) SHT P-2 INSTANT HOT WATER HEATER,
 PLEASE SUBMIT MANUFACTURE INFORMATION
 SHOWING PRODUCT IS LISTED BY APPROVED
 TESTING AGENCY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377