| Plan Review Stops For Permit 02041939 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-05-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-03 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-05-03 |
Time |
09:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-05-01 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-01 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-05-01 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2002-05-01 00:00:00 | ~~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~ | | | | | | PLEASE DESIGNATE THE ROOMS BEING RE | | | WIRED ON THE PLAN SO IT CAN BE | | | DETERMINED WHICH CODE ARTICLES ARE | | | APPLICABLE. | | | | | | 1) NOTE: PLEASE NOTE FRONT AND REAR | | | RECEPTS REQ`D PER 210-52E | | | | | | 2)NOTE: PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12,AND FURNISH A PANEL | | | SCHEDULE | | | | | | 3) PLEASE SUBMIT LOAD CALCAULATION | | | -S.PER 220,215-5. | | | | | | 4) INDICATE THE RATING AND TYPE OF | | | EXISTING PANEL. | | | | | | 5) SHOW SMOKE DETECTORS ON PLAN. | | | PLEASE PROVIDE THE ABOVE MENTIONED | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|
|
|