Plan Review Details - Permit 02041939
Plan Review Stops For Permit 02041939
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-03 Cont ID  
Sent By btrobaug Date 2002-05-03 Time 09:50 Rev Time 0.00
Received By btrobaug Date 2002-05-03 Time 09:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-01 Cont ID  
Sent By btrobaug Date 2002-05-01 Time 14:50 Rev Time 0.00
Received By btrobaug Date 2002-05-01 Time 14:28 Sent To  
Notes
2002-05-01 00:00:00~~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~
  
 PLEASE DESIGNATE THE ROOMS BEING RE
 WIRED ON THE PLAN SO IT CAN BE
 DETERMINED WHICH CODE ARTICLES ARE
 APPLICABLE.
  
 1) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 2)NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12,AND FURNISH A PANEL
 SCHEDULE
  
 3) PLEASE SUBMIT LOAD CALCAULATION
 -S.PER 220,215-5.
  
 4) INDICATE THE RATING AND TYPE OF
 EXISTING PANEL.
  
 5) SHOW SMOKE DETECTORS ON PLAN.
 PLEASE PROVIDE THE ABOVE MENTIONED
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392