| 2002-06-25 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) INDICATE THE APPLICABLE INTERNAL |
| | PRESSURE COEFFICIENT ON THE PLANS AS |
| | REQUIRED BY THE 2001 FBC SEC. 1606.1.7. |
| | |
| | 3) THE STRUCTURE IS LOCATED IN AN "A8" |
| | FLOOD ZONE AN ELEVATION CERTIFICATE IS |
| | REQUIRED. |
| | |
| | 4) PROVIDE SOIL BEARING TEST REPORT PER |
| | CITY OF WPB AMENDMENTS TO 2001 FBC SEC. |
| | 1804.2.2. |
| | |
| | 5) PROVIDE (2) COPIES OF INSTALLATION |
| | SCHEDULE FOR STORM PANELS. THESE ITEMS |
| | ARE REQUIRED AT TIME OF PERMIT OR YOU |
| | WILL BE REQUIRED TO PULL A SEPARATE |
| | PERMIT WITH ADDITIONAL FEES. |
| | |
| | 6) PROVIDE ADDITIONAL COPIES OF PRODUCT |
| | APPROVALS FOR THE FRONT DOOR AND GLASS |
| | BLOCK. TWO COPIES ARE REQUIRED. |
| | |
| | 7) PROVIDE TESTING INFORMATION WHICH |
| | INDICATES THAT THE GLASS BLOCK HAS A |
| | FIRE RATING OF ONE HOUR. |
| | |
| | 8) PLEASE CHANGE THE CALL SIZE OF THE |
| | EGRESS WINDOW (I) IN THE WINDOW SCHEDULE |
| | TO 24/5 SH WHICH CORRESPONDS TO THE |
| | DIMENSIONS GIVEN. |
| | |
| | 9) PLEASE CHANGE NOTE #6 UNDER GENERAL |
| | NOTES ON A2 TO REFERENCE THE 2001 |
| | FLORIDA PLUMBING CODE. |
| | |
| | 10) PROVIDE A DETAIL INDICATING ONE HOUR |
| | FIRE RATED ASSEMBLY BASED ON BOTH |
| | INTERIOR AND EXTERIOR FIRE EXPOSURE FOR |
| | THE GABLE END ON THE ZERO LOT LINE. |
| | |
| | 11) PLEASE INSERT THE REVISED SHEETS |
| | INTO THE PLANS. SUBMIT THE OLD SHEETS |
| | ALONG WITH THE PLANS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |