Plan Review Details - Permit 02041770
Plan Review Stops For Permit 02041770
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-15 Cont ID  
Sent By btrobaug Date 2002-06-13 Time 14:58 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-13 Cont ID  
Sent By btrobaug Date 2002-06-13 Time 14:55 Rev Time 0.00
Received By btrobaug Date 2002-06-13 Time 13:21 Sent To B
Notes
2002-06-13 00:00:00HANDED TO LUIS MARTINEZ./WRT.
 PASSED ON RESUB WITH LOAD CALCS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-09 Cont ID  
Sent By kstevens Date 2002-05-08 Time 19:42 Rev Time 0.00
Received By btrobaug Date 2002-05-09 Time 05:58 Sent To B
Notes
2002-05-09 00:00:00~~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE A LOAD CALCULATION FOR
 THE SERVICE SHOWING THE ADDITIONAL
 EQUIPMENT LOAD,AND RESUBMIT FOR REVIEW.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-24 Cont ID  
Sent By kstevens Date 2002-06-24 Time 06:43 Rev Time 0.00
Received By kstevens Date 2002-06-24 Time 06:43 Sent To  
Notes
2002-06-24 00:00:00PASSED/PROVISO
  
 EXTERNAL HARTFORD LOOP REQUIRED - NO IN-
 TERNAL POSITIVE WATER RETENTION SHOWN.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-06-13 Cont ID  
Sent By kstevens Date 2002-06-13 Time 13:09 Rev Time 0.00
Received By kstevens Date 2002-06-13 Time 13:09 Sent To  
Notes
2002-06-13 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FROM PREVIOUS REVIEW - ENGINEERS RE-
 PORT ON CALCULATIONS FOR 1" VENT ARE FOR
 A 1HP PUMP, A 2HP PUMP IS BEING USED.
 SUBMIT CALCUALTIONS FOR A 2" PUMP OR USE
 1-1/2" VENT LINES.
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)FROM PREV-
 IOUS REVIEW.
 3) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 FROM PREVIOUS REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-08 Cont ID  
Sent By kstevens Date 2002-05-08 Time 19:35 Rev Time 0.00
Received By kstevens Date 2002-05-08 Time 19:35 Sent To E
Notes
2002-05-08 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING P00LS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL) VENT SHALL BE
 1-1/2" OR SUBMIT AN ENGINEER'S REPORT
 FOR 1" VENT LINES.
 3) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 4) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 5) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 6) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 7) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 8) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 9) FBC02001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2002-06-25 Cont ID  
Sent By sgraham Date 2002-06-25 Time 11:00 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-08 Cont ID  
Sent By sgraham Date 2002-05-08 Time 09:58 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***