Plan Review Details - Permit 02041748
Plan Review Stops For Permit 02041748
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-09-12 Cont ID  
Sent By hpiskura Date 2002-09-12 Time 16:03 Rev Time 0.00
Received By hpiskura Date 2002-09-12 Time 14:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-08-21 Cont ID  
Sent By hpiskura Date 2002-08-21 Time 16:01 Rev Time 0.00
Received By hpiskura Date 2002-08-21 Time 15:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-15 Cont ID  
Sent By hpiskura Date 2002-05-15 Time 09:57 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-09-05 Cont ID  
Sent By dpalmer Date 2002-09-05 Time 06:27 Rev Time 0.50
Received By dpalmer Date 2002-09-05 Time 06:27 Sent To  
Notes
2002-09-05 00:00:00************* NOTE ***********
  
 PLEASE NOTE, NEW ELECTRICAL SHEETS WERE
 REVIEWED AND SIGNED OFF.
 PLEASE ALSO NOTE THAT PLANS WERE RE-
 -SUBMITTED WITHOUT HAVING OLD SHEETS
 TAKEN OUT AND NEW SHEET INSTALLED INTO
 TWO COMPLETE SETS.
 PLEASE REMOVE OLD, AND INSERT NEW.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-08-22 Cont ID  
Sent By dpalmer Date 2002-08-22 Time 06:18 Rev Time 1.00
Received By dpalmer Date 2002-08-22 Time 06:06 Sent To  
Notes
2002-08-22 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE NOTE A REVISED RISER
 DIAGRAM IS SUBMITTED. PLEASE NOTE THAT
 AIC RATINGS FOR MAIN AND PANELS ARE
 NOT SUBMITTED. IT IS NOTED THAT BRKRS
 ARE TO BE RATED FOR MAX, BUT NO RATING
 ACTUALLY SHOWN. 110-9/215-5
  
 2)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM FIRST REVIEW WERE ADDRESSED.
  
 3)NOTE: PLEASE NOTE WIRE SIZES ARE NOT
 SHOWN ON PANEL SCHEDULES.?
  
 4)NOTE: PLEASE NOTE, RISER DIAGRAM
 SHOWS PANEL "S" BEING IN SPACE 102 AND
 YET IS STILL SHOWN IN SPACE 104 ON E-1?
 PLEASE CLARFIY. E-2 DOES NOT SHOW IN
 THIS SPACE?
  
 5)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 WERE NOT SUBBITTED. PLEASE SHOW WATTS/
 SQ.FT, RECEPTS..180VA EACH, PLEASE
 SHOW ALL CONTINUOUS LOADS AT 125%.
 215-5,220-3,220-10,220-11,220-13,230-42
 215-3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-07 Cont ID  
Sent By dpalmer Date 2002-05-07 Time 06:20 Rev Time 0.00
Received By dpalmer Date 2002-05-07 Time 06:20 Sent To  
Notes
2002-05-07 00:00:00***************UNSAT ***************
  
 1)NOTE; PLEASE NOTE THAT SECOND SERVICE
 IS NOT PERMITTED UNLESS ALL IS MET UNDER
 230-2. 2HR SEPARATION FOR ADDITIONAL
 SERVICE MAYBE REQ`D FROM OTHER TENANTS.
 2)NOTE: PLEASE NOTE GROUPING OF MAINS
 PER 230-72, IF ALL THE REQ`MENTS FOR
 230-2 CAN BE MET.
  
 3)NOTE: PLEASE NOTE THAT PANEL SCHEDULE
 FOR PANEL "S" WAS SUBMITTED WHICH APPEAR
 S TO HAVE NOTHING TO DO WITH THIS TENAT
 SPACE? OR DOES IT? PLEASE ALSO NOTE THAT
 PANEL "S" IS SHOWING A NEW AHU (MS-1)??
 PLEASE CALRIFY WHERE THIS IS SHOWN? AND
 WIRING FOR UNIT ON RISER.
  
 4)NOTE: PLEASE ALSO NOTE THAT PANEL
 SCHEDULE FOR PANEL "N" IS SHOWING TWO
 NEW COND UNITS??? PLANS/RISER ONLY SHOW
 ONE NEW CU #1? PLEASE CLARIFY.
  
 5)NOTE: PLEASE NOTE PANEL SCHEDULE FOR
 PANEL "N" HAS A FEED (2P 80) FOR "T2"??
 PLEASE CLARIFY.
  
 6)NOTE: PLEASE NOTE THAT PANEL MR1 IS
 NOT SHOWN ON PANEL SCHEDULE "N"?
 PLEASE CLARIFY.
  
 7)NOTE: PLEASE NOTE/CLARIFY ADDITIONAL
 AHU SHOWN AS 1POLE 20A?? ON PANEL "N"??
  
 8)NOTE: PLEASE CLARIFY NEW OR EXISTING
 RECEPT FOR ROOFTOP A/C EQUIPMENT? 210-63
  
 9 )NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
  
 10)NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 215-2,215-3,230-42
  
 11)NOTE: PLEASE NOTE NO WIRE SIZES ARE
 SHOWN ON PANEL SCHEDULES??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-17 Cont ID  
Sent By mcarsill Date 2002-05-17 Time 10:38 Rev Time 0.00
Received By mcarsill Date 2002-05-17 Time 10:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-20 Cont ID  
Sent By pkrauss Date 2002-05-20 Time 15:05 Rev Time 0.45
Received By pkrauss Date 2002-05-20 Time 15:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-09-05 Cont ID  
Sent By kstevens Date 2002-09-05 Time 18:23 Rev Time 0.00
Received By kstevens Date 2002-09-05 Time 18:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-08-23 Cont ID  
Sent By kstevens Date 2002-08-23 Time 10:14 Rev Time 0.00
Received By kstevens Date 2002-09-05 Time 18:23 Sent To  
Notes
2002-08-23 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED. PLEASE SEE ATTACHED COMMENTS.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-18 Cont ID  
Sent By kstevens Date 2002-05-18 Time 13:43 Rev Time 0.00
Received By kstevens Date 2002-05-18 Time 13:43 Sent To  
Notes
2002-05-18 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING.
  
 1) SHT A-3, BREAKROOM SINK. PLEASE SHOW
 DETAIL FOR SINK. SHOW COMPLIANCE FOR
 11-4.24.2HEIGHT, 4.24.3 KNEE CLEARANCE,
 4.24.5 CLEAR FLOOR SPACE, & 4.24.6 EX-
 POSED PIPES AND SURFACES.
 2) TABLE 403.1 REQUIRES A SERVICE SINK
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377