Plan Review Details - Permit 02041746
Plan Review Stops For Permit 02041746
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-30 Cont ID  
Sent By hpiskura Date 2002-05-30 Time 13:00 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-13 Cont ID  
Sent By dpalmer Date 2002-05-13 Time 17:54 Rev Time 0.00
Received By dpalmer Date 2002-05-13 Time 17:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-17 Cont ID  
Sent By mcarsill Date 2002-05-17 Time 10:28 Rev Time 0.00
Received By mcarsill Date 2002-05-17 Time 10:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-08-29 Cont ID  
Sent By hmoser Date 2002-08-29 Time 16:42 Rev Time 0.50
Received By hmoser Date 2002-08-29 Time 16:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-30 Cont ID  
Sent By ndenmark Date 2002-05-30 Time 06:56 Rev Time 0.33
Received By ndenmark Date 2002-05-30 Time 06:56 Sent To  
Notes
2002-05-30 00:00:00PROVISO:
  
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 WITH HORN AND STROBE FOR NOTIFICATION
 REQUIRED.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR
 COOLER/FREEZER

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-08-29 Cont ID  
Sent By kstevens Date 2002-08-29 Time 09:54 Rev Time 0.00
Received By kstevens Date 2002-08-29 Time 09:54 Sent To  
Notes
2002-08-29 00:00:00REVISION OK - DUAL SAMPLE POINTS IN
 GREASE LINE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-07 Cont ID  
Sent By kstevens Date 2002-06-07 Time 14:35 Rev Time 0.00
Received By kstevens Date 2002-06-07 Time 14:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-18 Cont ID  
Sent By kstevens Date 2002-05-18 Time 14:30 Rev Time 0.00
Received By kstevens Date 2002-05-18 Time 14:29 Sent To  
Notes
2002-05-18 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-3 SAMPLE POINT SHALL BE FOR
 GREASE WASTE ONLY. SEPARATE 3-COMPART-
 MENT SINK, FLOOR DRAIN, AND MOP SINK
 THEN INSTALL SAMPLE POINT. AFTER SAMPLE
 POINT THEN TIE INTO SANITARY
 2) SHT A-3 SANITARY RISER DIAGRAM SHALL
 REFLECT THE FLOOR PLAN, TOILET ROOMS DO
 NOT TIE IN AFTER 3-COMP SINK ECT.
 3) SHT A-3 HUB DRAIN NOT APPROVED FOR
 INDIRECT WASTE. (ICE/SODA MACHINE) FLOOR
 SINK REQUIRED FOR ALL INDIRECT WASTE.
 SEC 802.3
 4) SHT A-3 WATER FILTRATION SYSTEM FOR
 ICE MACHINE SHALL BE NSF APPROVED.
 PLEASE PROVIDE MANUFACTURE INFORMATION.
 5) SHT A-3 DRINKING FOUNTAIN REQUIRED
 TABLE 403.1. ALSO SEE 410.1 BOTTLED
 WATER REQUIREMENT ARI-1010 IF USED SUB-
 MIT MANUF. INFO SHOWING COMPLIANCE.
 6) SHT A-3 TOILET ROOM ELEVATIONS, URNAL
 SHALL BE 17" TO LIP AFF MAX.
 7) SHT A-3 WATER RISER DIAGRAM, AIR
 CHAMBERS NOT APPROVED (NOTE #4).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377