Plan Review Details - Permit 02041743
Plan Review Stops For Permit 02041743
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-07-02 Cont ID  
Sent By jwitmer Date 2002-07-02 Time 11:32 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-03 Cont ID  
Sent By jwitmer Date 2002-06-03 Time 16:54 Rev Time 4.00
Received By jwitmer Date 2002-06-03 Time 16:54 Sent To  
Notes
2002-06-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02041743
 ADD: 1031 SUNSET RD
 CONT: BRIGHTSTONE BUILDERS
 TEL: (561) 753-9351
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)- 1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED, INCLUDING GLASS BL.
 SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE DESIGN
 PROFESSIONAL OF RECORD.(NATIONAL CERTI-
 FIED TESTING LABORATORIES).
  
 3)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
 1707.4.5.1 .MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 4)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 5) FOUNDATION PAD #1 (P1) 1803.1.3
 EXCAVATIONS FOR ANY PURPOSE SHALL NOT EX
 TEND WITHIN 1 FT. OF THE ANGLE OF REPOSE
 OR NATURAL SLOPE OF THE SOIL UNDER ANY
 FOOTING OR FOUNDATION, UNLESS SUCH FOOT-
 ING IS FIRST PROPERLY UNDERPINNED OR PRO
 TECTED AGAINST SETTLEMENT.
  
 6) MEAN ROOF HEIGTH NOT GIVEN!
  
 7) SHEET DE-1 DOES NOT GIVE BUCK ATTACH-
 MENTS FOR WOOD FRAME DORMER WINDOWS.
  
 8) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-11-21 Cont ID  
Sent By dpalmer Date 2002-11-21 Time 16:01 Rev Time 0.25
Received By dpalmer Date 2002-11-21 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-11-19 Cont ID  
Sent By dpalmer Date 2002-11-19 Time 12:35 Rev Time 0.75
Received By dpalmer Date 2002-11-19 Time 12:35 Sent To  
Notes
2002-11-19 00:00:00************** UNSAT *****************
  
 PLEASE NOTE THAT DUE TO THE FACT THAT
 PLANS ARE IN FOR FINAL REVIEWAND
 FOR FINAL INPSECTION, THE FOLLOWING ITEM
 -S NNED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SHOW AIC RATINGS FOR
 NEW EQUIPMENT/MAINS/BRKRS. 110-9/215-5
  
 2)NOTE: PLEASE NOTE, OCP FOR 10KW AHU
 NEEDS TO BE SIZED TO A MIN 125%. PER
 424-3
  
 3)NOTE: PLEASE NOTE, MISSING REQ`D ARC
 FAULT PROTECTED CIRCUITS PER 210-12.
 PLEASE LIST ON PANEL SCHEDULE.
  
 4)NOTE: PLEASE NOTE MISSING REQ`D BATH
 CIRCUIT(S) PER 210-11-C3
 #12, 20A.
  
 5)NOTE: PLEASE NOTE, PANEL SCHEDULE
 SHOWS 4 CIRCUITS FOR SMALL APPLIANCES
 AND ONLY 3 ON LOAD CALCS?
 PLEASE CORRELATE.
  
 6)NOTE: PLEASE NOTE, PANEL "A" HAS SUB
 FEED. PLEASE ALSO NOTE,
 THERE IS NOTHING SHOWN ON PANEL "A'
 FOR SUB-FEED OF PANEL "B". BRKR SIZE,
 WIRE SIZE, CONDUIT, LOCATION ETC.
  
 7)NOTE: PLEASE NOTE, SD IN BEDROOM #3
 IS TO BE A MIN OF 3' FROM BATHS.
 NFPA-72 8-1.4.1.6
  
 PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-27 Cont ID  
Sent By hmoser Date 2002-07-01 Time 17:31 Rev Time 0.00
Received By btrobaug Date 2002-06-27 Time 14:08 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-21 Cont ID  
Sent By pkrauss Date 2002-06-20 Time 10:31 Rev Time 0.00
Received By btrobaug Date 2002-05-21 Time 14:01 Sent To R
Notes
2002-05-21 00:00:00UNSAT!
 ~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} CONTACT FPL REGARDING THE 2"METAL
 CONDUIT SHOWN ON THE RISER DIAGRAM,
 THEY NORMALLY SUPPLY PVC.
  
 3} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 4} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} THERE IS NO CALCULATION INCLUDED OR
 LISTING ON THE PANEL SCHEDULE FOR THE
 STEAM GENERATOR,PLEASE CLARIFY.
  
 6} PLEASE COMPLY WITH NFPA-72 2-2.1.1.1
 DROOM #3
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-07-01 Cont ID  
Sent By hmoser Date 2002-07-01 Time 17:48 Rev Time 0.50
Received By hmoser Date 2002-07-01 Time 17:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-20 Cont ID  
Sent By pkrauss Date 2002-06-20 Time 09:59 Rev Time 0.40
Received By hmoser Date 2002-06-20 Time 09:52 Sent To E
Notes
2002-06-20 00:00:00PROVISO:
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 DRYER INSTALLATIONS EXHASUTING MORE THAN
 200 CFM SHALL BE PROVIDED WITH MAKEUP
 AIR AS PER 2001 FBC(M) 504.5
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-18 Cont ID  
Sent By hmoser Date 2002-05-18 Time 14:28 Rev Time 0.33
Received By hmoser Date 2002-05-18 Time 14:28 Sent To  
Notes
2002-05-18 00:00:00PLAN DENIED
 NO DUCT SIZES,GRILL SIZE,OR CFM.ON PLAN
 DO NOT INSTALL RETURN AIR IN BATHROOM OR
 LAUNDRYROOM
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-29 Cont ID  
Sent By jleech Date 2002-06-29 Time 10:07 Rev Time 0.50
Received By jleech Date 2002-06-29 Time 10:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-11 Cont ID  
Sent By btrobaug Date 2002-06-27 Time 14:56 Rev Time 0.50
Received By jleech Date 2002-05-11 Time 09:55 Sent To  
Notes
2002-05-11 00:00:00DENIED;
 1.PAGE A-9 3" HORIZONTAL DRY VENT FOR
 W/C NOT PERMITED.
 2.MASTER BATH 2" DRY VENT FOR SHOWER NOT
 TO CODE. SAFEWASTE FOR STEAM GENERATOR
 CANNOT TIE INTO W/C STUB UP. INSTALL
 A FLOOR DRAIN WITH A TRAP PRIMER OR
 A DEEP SEAL TRAP. FLOOR DRAIN SHALL BE
 VENTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2002-06-03 Cont ID  
Sent By btrobaug Date 2002-05-21 Time 14:56 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-07 Cont ID  
Sent By sgraham Date 2002-05-07 Time 15:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***