Plan Review Details - Permit 02041733
Plan Review Stops For Permit 02041733
Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-30 Cont ID  
Sent By jleech Date 2002-05-30 Time 19:11 Rev Time 0.50
Received By jleech Date 2002-05-30 Time 19:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-07 Cont ID  
Sent By kstevens Date 2002-05-07 Time 13:54 Rev Time 0.00
Received By kstevens Date 2002-05-07 Time 13:54 Sent To  
Notes
2002-05-07 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL CODE
  
 1) PROPER LICENCE IS REQUIRED FOR LP GAS
 CFC LICENCE IS ONLY GOOD FOR NATURAL GAS
 2) INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC FUEL GAS CODE SEC.
 3) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE FBC-
 2001 FUEL GAS CODE. NO LISTED AGENCY
 APPROVAL ON SUBMITTED SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377