| 2002-06-10 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) FBC* 104.2.4SITE SURVEY.A SIGNED |
| | AND SEALED SURVEY DRAWING PREPARED BY A |
| | QUALIFIED SURVEYOR IS REQUIRED. |
| | |
| | 3) THE 2001 FBC SECTION 1606.1.7 |
| | REQUIRES THE FOLLOWING INFORMATION TO BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS: |
| | - BASIC WIND SPEED, MPH. |
| | - WIND IMPORTANCE FACTOR(1) AND BUILDING |
| | CATEGORY. |
| | - WIND EXPOSURE- IF MORE THAN ONE WIND |
| | EXPOSURE IS USED THE WIND EXPOSURE AND |
| | APPLICABLE WIND DIRECTION SHALL BE |
| | INDICATED. |
| | - THE APPLICABLE INTERNAL PRESSURE |
| | COEFFICIENT |
| | - COMPONENTS AND CLADDING. THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF, TO BE |
| | USED FOR THE DESIGN OF EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED |
| | DESIGN PROFESSIONAL. |
| | PLEASE UPDATE THE DESIGN ASSUMPTIONS AND |
| | PARAMETERS ON S1. |
| | |
| | 4) PLEASE INDICATE THE POSITIVE AND |
| | NEGATIVE WINDLOAD PRESSURES FOR THE |
| | SKYLIGHT AND THE 25 SH WINDOW IN THE |
| | GARAGE. |
| | |
| | 5) PLEASE REVISE NOTE #2 ON A1 TO THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 6) PLEASE REVISE THE BUCK DETAIL #2 ON |
| | A4 TO COMPLY WITH FBC 1707.4.4.2. |
| | |
| | 7) PLEASE UPDATE THE FOLLOWING NOTES ON |
| | S4 TO REFERENCE THE 2001 FBC: |
| | - #3 & #4 UNDER GENERAL NOTES |
| | - #9 UNDER GENERAL NOTES TO ASCE 7-98 & |
| | 140MPH (3 SEC. GUST) |
| | - #1 UNDER SAFEGUARDS |
| | - #1 UNDER REINFORCED CONCRETE |
| | - #2 UNDER TRUSSES |
| | - #5 UNDER ROOF SHEATHING |
| | |
| | 8) PLEASE REVISE NOTE #7, THE CORRECT |
| | REFERENCE IS ASTM A 185. THE WELDED WIRE |
| | FABRIC IS REQUIRED TO BE SUPPORTED WITH |
| | APPROVED MATERIALS OR SUPPORTS PER FBC |
| | SEC. 1909.3. |
| | |
| | 9) THE NEGATIVE PRESSURE FOR THE 1/2-36 |
| | SINGLE HUNG KDI WINDOWS IN THE DEN AND |
| | THE LIVING ROOM EXCEEDS THE VALUE LISTED |
| | IN THE SBCCI PRODUCT EVALUATION REPORT. |
| | THE COMPARATIVE ANALYSIS CHART IS NOT |
| | VALID WITHOUT THE WET SIGNATURE AND |
| | EMBOSSED SEAL OF THE ENGINEER. |
| | |
| | 10) THE KEY PLAN AND INSTALLATION |
| | SCHEDULE SUBMITTED FOR THE STORM PANELS |
| | ARE FOR ANOTHER MODEL. PLEASE SUBMIT THE |
| | ONES FOR A "B" MODEL. |
| | |
| | 11) THE PRODUCT APPROVAL FOR ENTEGRA |
| | ROOF TILE IS EXPIRED. |
| | |
| | 12) PROVIDE PRODUCT APPROVALS FOR AN |
| | EXTERIOR DOOR WITH SIDELITE AS SHOWN ON |
| | PLANS. |
| | |
| | 13) PROVIDE THE CORRECT GARAGE DOOR |
| | DRAWING THE ONE ATTACHED TO THE PRODUCT |
| | APPROVAL IS FOR A 9 FOOT WIDE DOOR |
| | MAXIMUM. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |