Plan Review Details - Permit 02041683
Plan Review Stops For Permit 02041683
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-08-07 Cont ID  
Sent By btrobaug Date 2002-08-07 Time 14:38 Rev Time 0.00
Received By btrobaug Date 2002-08-07 Time 14:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-07-18 Cont ID  
Sent By btrobaug Date 2002-07-18 Time 11:34 Rev Time 0.00
Received By btrobaug Date 2002-07-18 Time 08:58 Sent To P
Notes
2002-07-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING DICREPANCIES,
 CORRECT PLANS AND RESUBMIT FOR REVIEW:
  
 1} INCLUDE SMALL APPLIANCE CIRCUITS IN
 LOAD CALCULATIONS PER 220-30.
  
 2} SHOW KITCHEN CIRCUITS ON PANEL
 SCHEDULE.(APPLIANCE).
  
 3} CIRCUIT #18 IS LABELED "KITCHEN BATH
 RECEPT".PLEASE CLARIFY.
  
 4} THE MICROWAVE IN THE CALCULATIONS IS
 NOT LISTED ON THE PANEL SCHEDULE.
  
 5} PLEASE REMOVE THE SMOKE DETECTOR FROM
 THE BATHROOM PER NFPA-72 2-5.2.1.6.
  
 6} THE RANGE LISTED AT 5000W MUST COMPLY
 WITH 220-19.
  
 7} PLEASE REMOVE THE #4 GROUND FROM THE
 METER TO THE PANEL AS IT CREATES A
 PARALLEL PATH WITH THE
 GROUNDED(NEUTRAL) CONDUCTOR.
  
 8} PLEASE NOTE THAT ITEMS #1&2 WERE
 NOTED ON THE PREVIOUS TWO REVIEWS AND
 ARE SUBJECT TO FLORIDA STATUTE
 553.80(2)(B),SHOULD THEY NOT BE
 CORRECTED.SEE ATTACHED COPY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL:
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-07-09 Cont ID  
Sent By btrobaug Date 2002-07-09 Time 16:08 Rev Time 0.00
Received By btrobaug Date 2002-07-09 Time 15:19 Sent To R
Notes
2002-07-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE NOTE THE FOLLOWING
 DISCREPANCIES,CORRECT PLANS AND
 RESUBMIT FOR REVIEW:
  
 1} INCLUDE SMALL APPLIANCE CIRCUITS IN
 LOAD CLCULATIONS PER 220-30.
  
 2} SHOW KITCHEN CIRCUITS ON PANEL
 SCHEDULE.(APPLIANCE).
  
 3} A/C #1 AHU @ 10K,BREAKER & BRANCH
 CIRCUIT CONDUCTORS ARE UNDERSIZED PER
 424-3(B).
  
 4} THE RANGE LISTED AT 5000W MUST COMPLY
 WITH 220-19.
  
 PLEASE NOTE THAT ITEMS #1,2 & 3 WERE
 NOTED ON THE PREVIOUS REVIEW NOTES.IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-15 Cont ID  
Sent By btrobaug Date 2002-05-15 Time 06:44 Rev Time 0.00
Received By btrobaug Date 2002-05-15 Time 06:44 Sent To R
Notes
2002-05-15 00:00:00~~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~
  
 PLEASE NOTE THE FOLLOWING
 DISCREPANCIES,CORRECT PLANS AND
 RESUBMIT FOR REVIEW.
  
 1} INCLUDE SMALL APPLIANCE CIRCUITS IN
 LOAD CALCULATIONS PER 220-30.
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 3} SHOW KITCHEN CIRCUITS ON PANEL
 SCHEDULE.(APPLIANCE).
  
 4} A/C #1 AHU @ 10K,BREAKER & BRANCH
 CIRCUIT CONDUCTORS ARE UNDERSIZED
 PER424-3(B). 65% FOR CALCULATIONS
 ONLY,NOT B.C.& OCP.
  
 5} THE WASHER IS LISTED AT 3000W IN THE
 LOAD CALCS AND SHOWN ON A 20 AMP
 BREAKER WITH #12 WIRE ON THE PANEL
 SCHEDULE, PLEASE CLARIFY.
  
 6} OVEN SHOWN ON PANEL SCHEDULE BUT NOT
 IN LOAD CALCULATION,PLEASE CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392
 EXT.8

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-06 Cont ID  
Sent By mcarsill Date 2002-08-06 Time 13:26 Rev Time 0.00
Received By mcarsill Date 2002-08-06 Time 13:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-12-19 Cont ID  
Sent By pkrauss Date 2002-12-19 Time 07:59 Rev Time 0.20
Received By pkrauss Date 2002-12-19 Time 07:59 Sent To  
Notes
2002-12-19 00:00:00MECH PERMIT 02041692
 REVISED ENERGY CALCS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-10-16 Cont ID  
Sent By pkrauss Date 2002-10-16 Time 12:42 Rev Time 0.30
Received By pkrauss Date 2002-10-16 Time 12:31 Sent To  
Notes
2002-10-16 00:00:00REV MECH PERMIT 02041692

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-11 Cont ID  
Sent By hmoser Date 2002-07-11 Time 17:08 Rev Time 0.33
Received By hmoser Date 2002-07-11 Time 17:08 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-11 Cont ID  
Sent By hmoser Date 2002-05-11 Time 11:10 Rev Time 0.33
Received By hmoser Date 2002-05-11 Time 11:09 Sent To  
Notes
2002-05-11 00:00:00PRIVISO
 NEED TO KNOW TYPE OF FRESH AIR
 402 NATURAL,403 MECHANICAL.
 NEED CALCULATIONS FOR TYPE OF FRESH AIR

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-18 Cont ID  
Sent By kstevens Date 2002-12-18 Time 08:38 Rev Time 0.10
Received By kstevens Date 2002-12-18 Time 08:38 Sent To  
Notes
2002-12-18 00:00:00SUBMITTAL LETTER - DELETE REQUIREMENTS
 TO INSULATE HOT WATER LINES.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-08 Cont ID  
Sent By btrobaug Date 2002-07-26 Time 08:43 Rev Time 0.33
Received By jleech Date 2002-05-08 Time 17:34 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-07-12 Cont ID  
Sent By btrobaug Date 2002-07-18 Time 12:02 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-12 00:00:00************BUILDING PROVISO************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-03 Cont ID  
Sent By btrobaug Date 2002-07-09 Time 16:08 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To Z
Notes
2002-06-03 00:00:00BUILDING DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES FOR THE SKYLIGHT ON THE PLANS.
  
 3) PLEASE REVIEW THE M.O. LISTED FOR THE
 1/2 33SH WINDOW, IT APPEARS TO BE TOO
 LARGE.
  
 4) PLEASE REVIEW THE POSITIVE AND
 NEGATIVE PRESSURES THAT ARE GIVEN FOR
 THE WINDOW AND DOOR OPENINGS, SOME OF
 THEM APPEAR TO BE TOO HIGH.
  
 5) INDICATE COMPLIANCE WITH TABLE 600
 (PERCENTAGE OF WALL AREA ALLOWED AS
 OPENINGS) FOR THE MASTER BEDROOM WALL
 WITH SLIDING GLASS DOOR AND AND THE
 LIVING ROOM WALL WITH THE SLIDING GLASS
 DOOR. ALSO REVIEW THE AREAS OF THE
 OPENINGS USED IN THE CALCULATIONS ON
 SHEET A2.
  
 6) INDICATE ON THE PLANS THAT THE WELDED
 WIRE REINFORCEMENT FABRIC WILL BE
 SUPPORTED WITH APPROVED MATERIALS OR
 SUPPORTS PER 2001 FBC SEC. 1909.3.
  
 7) REVISE ITEM #2 ON A1 TO REFERENCE THE
 FLORIDA BUILDING CODE.
  
 8) PLEASE REVISE DETAIL 2 ON A4 TO SHOW
 BUCKS EXTENDING BEYOND THE FACE OF THE
 WINDOW/ DOOR FRAMES TO PROVIDE FULL
 SUPPORT AND THE FRAME ANCHORS EXTENDING
 THROUGH THE 1X BUCKS INTO THE STRUCTURAL
 SUBSTRATE MATERIAL AS REQUIRED BY 2001
 FBC SECTION 1707.4.4.2.
  
 9) PLEASE UPDATE THE STRUCTURAL DESIGN
 PARAMETERS AND ASSUMPTIONS ON S1 TO
 REFLECT THE 2001 FBC AND ASCE 7-98.
 THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 10) PLEASE UPDATE THE NOTES ON S4 IN
 SEVERAL PLACES TO REFERENCE THE 2001
 FLORIDA BUILDING CODE AND ASCE 7-98.
  
 11) PLEASE SUBMIT THE CURRENT SBCCI
 EVALUATION REPORT FOR THE KDI DOORS AND
 WINDOWS. REPORT # 9733A.
  
 12) PROVIDE AN ORIGINAL SIGNED, SEALED
 AND DATED ANALYSIS CHART WITH THE
 ENGINEER'S CALCULATIONS FOR THE KDI
 SINGLE HUNG WINDOWS.
  
 13) THE PRODUCT APPROVAL FOR THE ENTEGRA
 ROOF TILE EXPIRED ON 10-01-01. PLEASE
 SUBMIT CURRENT PRODUCT APPROVALS.
  
 14) PLEASE REVIEW THE OPENING SIZES ON
 STORM PANEL INSTALLATION SCHEDULE AND
 CORRECT AS NECESSARY. (BATHROOM WINDOW)
  
 NOTE: TRUSS DRAWINGS AND LAYOUT ARE NO
 LONGER REQUIRED TO BE SUBMITTED FOR
 PLAN REVIEW. A SIGNED,SEALED AND DATED
 SET OF DRAWINGS AND LAYOUT WILL BE
 REQUIRED FOR REVIEW IN THE FIELD BY THE
 BUILDING INSPECTOR AT TIME OF TRUSS
 INSPECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-05 Cont ID  
Sent By rmcdouga Date 2002-06-10 Time 14:05 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***