Plan Review Details - Permit 02041656
Plan Review Stops For Permit 02041656
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-24 Cont ID  
Sent By dpalmer Date 2002-06-24 Time 15:08 Rev Time 0.00
Received By dpalmer Date 2002-06-24 Time 15:08 Sent To M
Notes
2002-06-24 00:00:00OK

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-15 Cont ID  
Sent By dpalmer Date 2002-05-15 Time 06:20 Rev Time 0.00
Received By dpalmer Date 2002-05-15 Time 06:20 Sent To B
Notes
2002-05-15 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT THE OVEN THAT
 IS SHOWN ON PANEL SCHEDULE IS NOT SHOWN
 ON LOAD CALCUALTIONS. PLEASE CORRELATE.
  
 2)NOTE: PLEASE NOTE A 10KW LOAD SHOWN
 W/ 50A OCP AND #8 AWG. PLEASE SEE 424-3B
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION PER 210-12 ON PANEL SCHEDULE.
  
 4)NOTE: PLEASE CLARIFY, PLANS SAYS
 MAIN DISC NEXT TO METER AND PLANS SHOW
 NEXT TO PANEL INSIDE GARAGE? PLEASE
 CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 5)NOTE: PLEASE NOTE THAT GROUNDING
 ELECTRODE CONDUCTOR SIZED PER 250-66
 3/0`S.......

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-25 Cont ID  
Sent By dpalmer Date 2002-06-24 Time 15:32 Rev Time 0.30
Received By pkrauss Date 2002-06-25 Time 07:39 Sent To P
Notes
2002-06-25 00:00:00PROVISO:MECHANICAL PERMIT 02041660
  
 DRYER VENT LOCATION IS NOT INDICATED ON
 PLAN.DRYER EXHAUST SHALL BE A MINIMUM
 OF 4" AND COMPLY WITH 2001 FBC(M) 504.5
 & 504.6.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-11 Cont ID  
Sent By hmoser Date 2002-05-11 Time 09:58 Rev Time 0.33
Received By hmoser Date 2002-05-11 Time 09:58 Sent To  
Notes
2002-05-11 00:00:00PLAN DENIED
 #1 RETURN AIR DUCT NOT MARKED
 #2 VARIFY FRESH AIR
 #3 NEED DRYERVENT LOCATION
 #4 CFM. DON'T MATCH PLANS
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-25 Cont ID  
Sent By pkrauss Date 2002-06-25 Time 08:02 Rev Time 0.25
Received By jleech Date 2002-06-25 Time 16:29 Sent To  
Notes
2002-06-25 00:00:00RESUB STAMP REQUIRED

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-08 Cont ID  
Sent By jleech Date 2002-05-08 Time 17:41 Rev Time 0.33
Received By jleech Date 2002-05-08 Time 17:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-07-08 Cont ID  
Sent By rmcdouga Date 2002-07-08 Time 11:23 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-05-31 Cont ID  
Sent By rmcdouga Date 2002-05-31 Time 09:15 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To Z
Notes
2002-05-31 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES FOR THE GLASS BLOCK OPENINGS
 AND THE SKYLIGHT ON THE PLANS.
  
 3) PLEASE REVISE DETAIL 2 ON A4 TO SHOW
 BUCKS THAT EXTEND BEYOND THE FACE OF THE
 WINDOW FRAME AND THE FRAME ANCHORS
 THROUGH THE 1X AND INTO THE STRUCTURAL
 SUBSTRATE MATERIAL AS REQUIRED BY FBC
 SEC. 1707.4.4.2.
  
 4) PLEASE UPDATE THE DESIGN CRITERIA ON
 SHEET S1 TO THE 2001 FBC, (ASCE 7-98,
 140 MPH 3 SECOND GUST).
 THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 5) INDICATE ON THE PLANS THAT THE WELDED
 WIRE REINFORCEMENT FABRIC WILL BE
 SUPPORTED WITH APPROVED MATERIALS OR
 SUPPORTS PER THE 2001 FBC SEC. 1909.3.
  
 6) PLEASE REVISE GENERAL NOTES (3) & (4)
 ON S4 FROM THE STANDARD TO THE FLORIDA
 BUILDING CODE. ALSO, REVISE NOTE (9) TO
 ASCE 7-98 (140 MPH) FROM ASCE 7-95 (145
 MPH).
  
 7) PLEASE REVISE DETAIL 4 ON A4 WHICH
 REFERENCES THE STANDARD BUILDING CODE.
  
 8) PLEASE REVIEW AND CORRECT THE WALL
 AREA PERCENTAGE CALCULATIONS ON SHEET A2
 THE LENGTH OF WALL AREA AT 20 PERCENT IS
 33 FEET, WHICH IS ADJACENT TO LOT 46.
  
 9) SBCCI EVALUATION REPORT # 9733 FOR
 KDI HAS BEEN REPLACED BY # 9733A. PLEASE
 SUBMIT THE CURRENT REPORT.
  
 10) THE PRODUCT APPROVAL FOR ENTEGRA
 ROOF TILE EXPIRED ON 10-01-01. PLEASE
 SUBMIT THE CURRENT PRODUCT APPROVAL.
  
 11) THE KEY PLAN AND INSTALLATION
 SCHEDULE SUBMITTED IS FOR A DIFFERENT
 MODEL. PLEASE SUBMIT THE ONES FOR THIS
 MODEL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-03 Cont ID  
Sent By rmcdouga Date 2002-05-31 Time 15:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***