| 2002-05-31 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) INDICATE THE POSITIVE AND NEGATIVE |
| | PRESSURES FOR THE GLASS BLOCK OPENINGS |
| | AND THE SKYLIGHT ON THE PLANS. |
| | |
| | 3) PLEASE REVISE DETAIL 2 ON A4 TO SHOW |
| | BUCKS THAT EXTEND BEYOND THE FACE OF THE |
| | WINDOW FRAME AND THE FRAME ANCHORS |
| | THROUGH THE 1X AND INTO THE STRUCTURAL |
| | SUBSTRATE MATERIAL AS REQUIRED BY FBC |
| | SEC. 1707.4.4.2. |
| | |
| | 4) PLEASE UPDATE THE DESIGN CRITERIA ON |
| | SHEET S1 TO THE 2001 FBC, (ASCE 7-98, |
| | 140 MPH 3 SECOND GUST). |
| | THE 2001 FBC SECTION 1606.1.7 |
| | REQUIRES THE FOLLOWING INFORMATION TO BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS: |
| | - BASIC WIND SPEED, MPH. |
| | - WIND IMPORTANCE FACTOR(1) AND BUILDING |
| | CATEGORY. |
| | - WIND EXPOSURE- IF MORE THAN ONE WIND |
| | EXPOSURE IS USED THE WIND EXPOSURE AND |
| | APPLICABLE WIND DIRECTION SHALL BE |
| | INDICATED. |
| | - THE APPLICABLE INTERNAL PRESSURE |
| | COEFFICIENT |
| | - COMPONENTS AND CLADDING. THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF, TO BE |
| | USED FOR THE DESIGN OF EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED |
| | DESIGN PROFESSIONAL. |
| | |
| | 5) INDICATE ON THE PLANS THAT THE WELDED |
| | WIRE REINFORCEMENT FABRIC WILL BE |
| | SUPPORTED WITH APPROVED MATERIALS OR |
| | SUPPORTS PER THE 2001 FBC SEC. 1909.3. |
| | |
| | 6) PLEASE REVISE GENERAL NOTES (3) & (4) |
| | ON S4 FROM THE STANDARD TO THE FLORIDA |
| | BUILDING CODE. ALSO, REVISE NOTE (9) TO |
| | ASCE 7-98 (140 MPH) FROM ASCE 7-95 (145 |
| | MPH). |
| | |
| | 7) PLEASE REVISE DETAIL 4 ON A4 WHICH |
| | REFERENCES THE STANDARD BUILDING CODE. |
| | |
| | 8) PLEASE REVIEW AND CORRECT THE WALL |
| | AREA PERCENTAGE CALCULATIONS ON SHEET A2 |
| | THE LENGTH OF WALL AREA AT 20 PERCENT IS |
| | 33 FEET, WHICH IS ADJACENT TO LOT 46. |
| | |
| | 9) SBCCI EVALUATION REPORT # 9733 FOR |
| | KDI HAS BEEN REPLACED BY # 9733A. PLEASE |
| | SUBMIT THE CURRENT REPORT. |
| | |
| | 10) THE PRODUCT APPROVAL FOR ENTEGRA |
| | ROOF TILE EXPIRED ON 10-01-01. PLEASE |
| | SUBMIT THE CURRENT PRODUCT APPROVAL. |
| | |
| | 11) THE KEY PLAN AND INSTALLATION |
| | SCHEDULE SUBMITTED IS FOR A DIFFERENT |
| | MODEL. PLEASE SUBMIT THE ONES FOR THIS |
| | MODEL. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |