Plan Review Details - Permit 02041653
Plan Review Stops For Permit 02041653
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-07-25 Cont ID  
Sent By hpiskura Date 2002-07-25 Time 14:05 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
2002-07-25 00:00:00OKAY SUBJECT TO ALL FEES AND OTHER
 APPROVALS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-29 Cont ID  
Sent By hpiskura Date 2002-05-29 Time 13:42 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-29 00:00:00PLAN REVIEW, (NOT A PERMIT
 APPLICATION),FOR LIGHTHOUSE POINT AT
 BAYWINDS.THE PLANS PROPOSE A SERIES
 OF TOWNHOUSES IN 6 AND 4 UNIT CLUSTERS.
  
 EACH TOWNHOUSE UNIT WILL REQUIRE A
 SEPARATE PERMIT.
  
 THE SBCCI REPORT #9755 FOR THE AMARR
 GARAGE DOORS IS EXPIRED.
  
 THE FOLLOWING MIAMI DADE REPORTS ARE
 EXPIRED:
  
 PCA 98-1228.01PCA 95-1212.01
 PCA 99-1203.02
  
 SHEET T1.00 GENERAL NOTES 1 AND 5 ARE
 NOT IN AGREEMENT.ONE DECLARES
 "TOWNHOUSES" (R3) AND 5 CALLS OUT "R2"
 PLEASE REVISE AS NECESSARY.SEE FBC 311
 AND FBC 704.4.
  
 ALSO THE CONSTRUCTION TYPE IS NOTED
 AS"II" TYPE VI IS IN AGREEMENT WITH THE
 PLANS. PLEASE REVISE AS NECESSARY.
  
 SHEET SP 1.01 HAS THE WRONG DIMENSIONS
 ON THEM.PLEASE CLARIFY.
  
 THE PLANS HAVE VARIOUS REFERENCES TO THE
 FORMER SOUTH FLORIDA BUILDING CODE.
 PLEASE REVISE AND ENSURE COMPLIANCE
 WITH THE FLORIDA BUILDING CODE, 2001.
  
 SHEET A3.03 SHOWS VENTS IN THE GARAGE
 DOOR.THESE MUST BE COVERED IN THE
 PRODUCT TEST REPORTS AND ACCEPTANCE
 NOTICE.
  
 SHEET 4/A6.01 SHOWS THE FRT SHEATHING
 MEASURED FOUR FEET FROM THE PARTY WALL
 CENTER LINE. FBC REQUIRES THE
 PROTECTION TOBE FOUR FEET TO EACH SIDE
 OF THE WALL, REVISE AS NECESSARY.SEE
 FBC 704.4.
  
 SHOW THE WIND PRESSURE ZONES FOR THE
 ROOF.
  
 SECTION 2 A/601 SHOWS A STEP AT THE
 FRONT ENTRANCE PORCH WHICH IS IN
 CONFLICT FOR AN ACCESSIBLE ENTRANCE
 WITH THE FAIR HOUSING ACT.PLEASE
 REVISE AS NECESSARY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-16 Cont ID  
Sent By dpalmer Date 2002-07-16 Time 17:04 Rev Time 0.00
Received By dpalmer Date 2002-07-16 Time 16:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-17 Cont ID  
Sent By dpalmer Date 2002-05-17 Time 12:24 Rev Time 0.00
Received By dpalmer Date 2002-05-17 Time 12:24 Sent To  
Notes
2002-05-17 00:00:00**************** UNSAT *************
  
  
 1)NOTE: PLEASE NOTE FHAR 24 CFR 100.205
 ON PLANS.
  
 2)NOTE: PLEASE NOTE MISSING SEAL BY
 ENG OF RECORD ON SHEET(S). PLEASE CHECK.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-07-26 Cont ID  
Sent By rmcdouga Date 2002-07-26 Time 10:26 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-02 Cont ID  
Sent By mcarsill Date 2002-07-02 Time 09:52 Rev Time 0.00
Received By mcarsill Date 2002-07-02 Time 09:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-06-05 Cont ID  
Sent By mcarsill Date 2002-06-05 Time 11:17 Rev Time 0.00
Received By mcarsill Date 2002-06-05 Time 11:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-16 Cont ID  
Sent By ndenmark Date 2002-07-16 Time 11:11 Rev Time 0.50
Received By ndenmark Date 2002-07-16 Time 11:11 Sent To  
Notes
2002-07-16 00:00:00PROVISO:
  
 1. OVERFLOW PROTECTION FOR AIR HANDLER
 UNITS TO BE PROVIDED FOR ALL EQUIPMENT.
 OVERFLOW RUN AS SHOWN DOES NOT COMPLY
 WITH THE REQUIREMENT FOR CONSPIQUOUS
 LOCATION. FLOAT SWITCH TO SHUT OF UNIT
 IN CASE PRIMARY DRAIN LINE STOPS IS
 ACCEPTABLE OR PROVIDE ALTERNATE METHOD
 FOR COMPLIANCE TO PLAN REVIEW FOR
 REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-30 Cont ID  
Sent By pkrauss Date 2002-05-30 Time 15:10 Rev Time 1.00
Received By pkrauss Date 2002-05-30 Time 14:15 Sent To  
Notes
2002-05-30 00:00:00MASTER PERMIT 02041653
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 PRESSURE DIFFERNTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001" WC OR
 LESS. PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH PRESSURE
 ZONE TO THE LOW ZONE.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4. PLAN SHEET P-101
 INDICATES OVERFLOW TERMINATING OUTSIDE.
 CODE DICTATES "CONSPICUOUS POINT TO
 SERVE AS ALARM WHICH INDICATES THAT THE
 PRIMARY DRAIN IS RESTRICTED".CLARIFY
 HOW HOME OWNER WILL KNOW PRIMARY DRAIN
 IS RESTRICTED WHEN THE TERMINATION POINT
 IS OUTSIDE NEXT TO THE PRIMARY DRAIN.
  
 PLAN SHEET M-105 - AHU MOUNTING DETAIL,
 DETAIL INDICATES 3" BETWEEN DUCT AND
 DRYWALL.AS PER 2001 FBC(M) 603.1.3,
 SPACE PROVIDED - TO ASSURE ADEQUATE
 ACCESS FOR (1) CONSTRUCTION & SEALING
 IN ACCORDANCE WITH THE REQUIREMENTS OF
 SECTION 603.1 FBC(M) (2) INSPECTION.A
 MINIMUM OF 4" IS CONSIDERED SUFFICIENT
 SPACE.
  
 PLANS M-102, 103 & 104, NOTE FOR DRYER
 EXHAUST INDICATES 4" UP THRU ROOF W/WP
 CAP, INSECT SCREEN & B.D.D.DRYER EXHAUST
 IS TO BE "NON-SCREENED" WITH B.D.D.
 PLEASE ALSO CORRECT WORDING ON PLAN M105
  
 SHOW COMPLIANCE TO THE 2001 FBC(M) 303.4
 & 304.4, PROTECTION FOR EQUIPMENT IN
 PRIVATE GARAGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-18 Cont ID  
Sent By kstevens Date 2002-07-18 Time 17:13 Rev Time 0.00
Received By kstevens Date 2002-07-18 Time 17:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-20 Cont ID  
Sent By kstevens Date 2002-05-20 Time 16:31 Rev Time 0.00
Received By kstevens Date 2002-05-20 Time 16:31 Sent To  
Notes
2002-05-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 1) SHT A3.01 UNITS A/A-REV, INDICATE
 SPECIFICATION A OR B REQUIREMENT 7.
 2) SHT A3.02 UNITS B/B-REV, INDICATE
 SPECIFICATION A OR B REQUIREMENT 7.
 SHOW CLEAR FLOOR SPACE FOR ALL REQUIRED
 FIXTURES.
 3) SHT A3.03 UNITS C/C-REV INDICATE
 SPECIFICATION A OR B REQUIREMENT 7.
 SHT P-101, BLDG 1 PLUMBING LAYOUT PLAN,
 OUTSIDE UNITS SECTION 504.7.1 THE DIS-
 CHARGE PIPE FROM THE RELIEF VALVE FROM
 THE WATER HEATER SHALL HAVE NOT TRAPPED
 SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING LOCATED IN THE
 SAME ROOM AS THE WATER HEATER.
 4) SHT P-105 WATER RISERS, WATER HAMMER
 ARRESTORS ARE REQUIRED AT THE WASH MACH-
 INE. 604.9
 5) SHT P-106 BACKFLOW /WATER HEATER DE-
 TAILS. IF A BACKFLOW IS INSTALLED ON THE
 WATER SERVICE, THERMAL EXPANSION CONTROL
 SHALL BE REQUIRED. 607.3 - 607.3.2.
 6) COND. SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-07-26 Cont ID  
Sent By hpiskura Date 2002-09-20 Time 13:26 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***