Plan Review Details - Permit 02041645
Plan Review Stops For Permit 02041645
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-07-25 Cont ID  
Sent By hpiskura Date 2002-07-25 Time 14:08 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
2002-07-25 00:00:00OKAY SUBJECT TO PAYMENT OF FEES AND ALL
 OTHER APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-29 Cont ID  
Sent By hpiskura Date 2002-05-29 Time 15:25 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-29 00:00:00PLEASE SEE NOTES UNDER 02041653

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-16 Cont ID  
Sent By dpalmer Date 2002-07-16 Time 14:33 Rev Time 0.00
Received By dpalmer Date 2002-07-16 Time 13:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-17 Cont ID  
Sent By dpalmer Date 2002-05-17 Time 12:12 Rev Time 0.00
Received By dpalmer Date 2002-05-17 Time 12:11 Sent To  
Notes
2002-05-17 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT A NOTE NEEDS TO
 BE PLACED ON PLANS TO MEET FHAR 24 CFR
 100.205
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW
 IF THEREARE ANY QUESTIONS, PLEASE CALL
  
  
 DEWEY PALMER
 ELECTRICALPLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-07-26 Cont ID  
Sent By rmcdouga Date 2002-07-26 Time 10:25 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-16 Cont ID  
Sent By mcarsill Date 2002-07-16 Time 12:54 Rev Time 0.00
Received By mcarsill Date 2002-07-16 Time 12:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-06-05 Cont ID  
Sent By mcarsill Date 2002-06-05 Time 10:55 Rev Time 0.00
Received By mcarsill Date 2002-06-05 Time 10:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-16 Cont ID  
Sent By ndenmark Date 2002-07-16 Time 11:45 Rev Time 0.50
Received By ndenmark Date 2002-07-16 Time 11:45 Sent To  
Notes
2002-07-16 00:00:00PROVISO:
  
 1. OVERFLOW PROTECTION FOR ALL AIR
 HANDLING EQUIPMENT IS REQUIRED. AS
 SHOWN ON P101 DOES NOT COMPLY WITH THIS
 REQUIREMENT. FLOAT SWITCHES TO SHUT OF
 UNIT DOES COMPLY OR PROVIDE ALTERNATE
 TO PLAN REVIEW FOR REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-30 Cont ID  
Sent By pkrauss Date 2002-05-30 Time 12:45 Rev Time 2.00
Received By pkrauss Date 2002-05-30 Time 11:12 Sent To  
Notes
2002-05-30 00:00:00MASTER PERMIT 02041645
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 PRESSURE DIFFERNTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001" WC OR
 LESS. PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH PRESSURE
 ZONE TO THE LOW ZONE.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.PLAN SHEET P-201
 INDICATES OVERFLOW TERMINATING OUTSIDE.
 CODE DICTATES "CONSPICUOUS POINT TO
 SERVE AS ALARM WHICH INDICATES THAT THE
 PRIMARY DRAIN IS RESTRICTED".CLARIFY
 HOW HOME OWNER WILL KNOW PRIMARY DRAIN
 IS RESTRICTED WHEN THE TERMINATION POINT
 IS OUTSIDE NEXT TO THE PRIMARY DRAIN.
  
 PLAN SHEET M-204 - AHU MOUNTING DETAIL,
 DETAIL INDICATES 3" BETWEEN DUCT AND
 DRYWALL.AS PER 2001 FBC(M) 603.1.3,
 SPACE PROVIDED - TO ASSURE ADEQUATE
 ACCESS FOR (1) CONSTRUCTION & SEALING
 IN ACCORDANCE WITH THE REQUIREMENTS OF
 SECTION 603.1 FBC(M) (2) INSPECTION.A
 MINIMUM OF 4" IS CONSIDERED SUFFICIENT
 SPACE.
  
 PLAN SHEET M-202 & 203, NOTE FOR DRYER
 EXHAUST INDICATES 4" UP THRU ROOF W/WP
 CAP, INSECT SCREEN & B.D.D.DRYER EXHAUST
 IS TO BE "NON-SCREENED" WITH B.D.D.
 PLEASE CORRECT ALSO WORDING ON PLAN M204
  
 SHOW COMPLIANCE TO THE 2001 FBC(M) 303.4
 & 304.4, PROTECTION FOR EQUIPMENT IN
 PRIVATE GARAGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-18 Cont ID  
Sent By kstevens Date 2002-07-18 Time 17:35 Rev Time 0.00
Received By kstevens Date 2002-07-18 Time 17:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-20 Cont ID  
Sent By kstevens Date 2002-05-20 Time 14:31 Rev Time 0.00
Received By kstevens Date 2002-05-20 Time 14:31 Sent To  
Notes
2002-05-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 1) SHT A3.02 UNITS B/B-REV PLEASE SHOW
 CLEAR FLOOR SPACE FOR ALL FIXTURES.
 2) SHT A3.02 UNITS B/B-REV INDICATE
 SPECIFICATION A OR B REQUIREMENT 7. SEE
 EXAMPLES PAGES 7.36 & 7.37.
 3) SHT A3.03 UNITS C/C-REV INDICATE
 SPECIFICATION A OR B, REQUIREMENT 7
 4) SHT P-201 BLDG 2: PLUMBING LAYOUT
 PLAN, OUTSIDE UNITS. SECTION 504.7.1 THE
 DISCHARGE PIPE FROM THE RELIEF VALVE
 FROM THE WATER HEATER SHALL HAVE NO
 TRAPPED SECTIONS AND SHALL HAVE A VISIB-
 LE AIR GAP OR AIR GAP FITTING LOCATED IN
 THE SAME ROOM AS THE WATER HEATER. SEC.
 504.7.1
 5) SHT P-204 WATER RISERS, WATER HAMMER
 ARRESTORS ARE REQUIRED AT THE WASH MACH-
 INE. SEC 604.9
 6) SHT P-205 DRAIN PAN/RVD DISCHARGE DE-
 TAIL, SEC 504.7.1 NO TRAPPED SECTIONS IN
 RELIEF VALVE DISCHARGE.
 7) SHT P-205 BACKFLOW DETAIL. IF BACK-
 FLOW IS USED, THERMAL EXPANSION CONTROL
 SHALL BE REQUIRED. 607.3 - 607.3.2
 8) CONDENSATE LINES SHALL DISCHARGE AT
 LEAST 1 FOOT AWAY FROM THE STRUCTURE
 SIDEWALL. 1503.4.4 FBC
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-07-26 Cont ID  
Sent By hpiskura Date 2002-07-25 Time 14:09 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***