Plan Review Details - Permit 02041639
Plan Review Stops For Permit 02041639
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-25 Cont ID  
Sent By dpalmer Date 2002-06-25 Time 14:57 Rev Time 0.00
Received By dpalmer Date 2002-06-25 Time 14:56 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-15 Cont ID  
Sent By btrobaug Date 2002-05-15 Time 12:22 Rev Time 0.00
Received By btrobaug Date 2002-05-15 Time 08:52 Sent To R
Notes
2002-05-15 00:00:00~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~~
  
 PLEASE NOTE THE FOLLOWING
 DISCREPANCIES,CORRECT PLANS AND
 RESUBMIT FOR REVIEW.
  
 1} SIZE THE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66 NEC.
  
 2} ELECTRICAL PLAN SHOWS "MAIN
 DISC"OUTSIDE,"ELEC PANEL W/DISC"INSIDE
 AND THE RISER DIAGRAM SHOWS A MAIN
 DISCONNECT WITH A MLO PANEL.PLEASE
 REDRAW TO CLARIFY INTENT.
  
 3} THE PANEL SCHEDULE AND THE LOAD
 CALCULATIONS PANEL DO NOT CORRELATE.
  
 4} WASHER IS LISTED @ 3000W IN THE LOAD
 CALCULATIONS AND SHOWN ON A 20 AMP
 BREAKER WITH #12 CONDUCTORS ON THE
 PANEL SCHEDULE. PLEASE CLARIFY.
  
 5} THERE IS AN OVEN LISTED ON THE PANEL
 SCHEDULE BUT NOT IN THE LOAD
 CALCS.PLEASE CLARIFY.
  
 6} A/C #1 AHU @ 10K,THE BREAKER & BRANCH
 CIRCUIT CONDUCTORS ARE UNDERSIZED PER
 424-3(B).
  
 7} CAN'T DISCERN THE WALL LINE BETWEEN
 THE MASTER BED ROOM & THE W.I.C.,COMPLY
 WITH 210-52(A)(1).
  
 IF THERE ARE QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-24 Cont ID  
Sent By pkrauss Date 2002-06-24 Time 16:40 Rev Time 0.35
Received By pkrauss Date 2002-06-24 Time 16:40 Sent To  
Notes
2002-06-24 00:00:00MECHANICAL PERMIT 02041641

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-11 Cont ID  
Sent By hmoser Date 2002-05-11 Time 12:07 Rev Time 0.50
Received By hmoser Date 2002-05-11 Time 12:07 Sent To  
Notes
2002-05-11 00:00:00PLAM DENIED
 #1 CFM.DON'T MATCH TOTAL CFM.ON PLANS
 #2 MISSING RETURN AIR SIZE
 #3 NEED TYPE OF VENTILATION &
 CALCULATIONS
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-08 Cont ID  
Sent By dpalmer Date 2002-06-25 Time 14:57 Rev Time 0.33
Received By jleech Date 2002-05-08 Time 18:29 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-06-28 Cont ID  
Sent By rmcdouga Date 2002-06-28 Time 15:25 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-03 Cont ID  
Sent By btrobaug Date 2002-05-15 Time 12:26 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To Z
Notes
2002-06-03 00:00:00BUILDING DENIED
  
 SAME COMMENTS AS 02041656.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-03 Cont ID  
Sent By rmcdouga Date 2002-06-03 Time 12:11 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***