| Plan Review Stops For Permit 02041557 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-04-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-25 |
Time |
10:36 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-04-25 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2002-04-25 00:00:00 | PROVISO: | | | | | | SERVICE PANEL SHALL EXCEED 6 FT FROM | | | ACCESS OPENING. | | | | | | A DEVICE SHALL BE INSTALLED TO ALERT | | | THEOWNER OR SHUT THE UNIT DOWN WHEN THE | | | CONDENSATION DRAIN IS NOT WORKING | | | PROPERLY.2001 FBC CHAPTER 13 | | | 610.1.ABC.3.5.2. | | | | | | A LIGHT FIXTURE WITH RECEPTACLE OUTLET, | | | CONTROLLED BY SWITCH LOCATED AT THE | | | PASSAGEWAY AS PER 2001 FBC(M) 306.3.1. | | | | | | AS PER 2001 FBC 1503.4.4, CONDENSATE | | | SHALL TERMINATE A MINIMUM OF 12" AWAY | | | FROM THE BUILDING STRUCTURE. |
|
|
|