Plan Review Details - Permit 02041445
Plan Review Stops For Permit 02041445
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-05 Cont ID  
Sent By hpiskura Date 2002-06-05 Time 09:59 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-06-05 00:00:00PLANS DATED 5/21/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-08 Cont ID  
Sent By hpiskura Date 2002-05-08 Time 12:07 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-05 Cont ID  
Sent By dpalmer Date 2002-06-05 Time 06:48 Rev Time 0.00
Received By dpalmer Date 2002-06-05 Time 06:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-06 Cont ID  
Sent By dpalmer Date 2002-05-06 Time 20:35 Rev Time 0.00
Received By dpalmer Date 2002-05-06 Time 20:35 Sent To  
Notes
2002-05-06 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
  
 2)NOTE: PLEASE NOTE THAT CIRCUIT #`S ON
 PLANS AND PANEL SCHEDULES NEED TO
 CORRELATE. PLEASE NOTE THAT THERE ARE
 CIRCUITS ON PLANS THAT ARE SHOWN AS
 "SPACE" ON SCHEDULE. THERE ARE CIRCUITS
 SHOWN ON PLANS THAT DO NOT FIGURE UP TO
 180VA FOR RECEPTS PER 220-3B-9
 PLEASE GO OVER PLANS AND CORRELATE AND
 LOAD CALCULATIONS NEED TO BE SHOWN NOT
 JUST CONNECTED LOADS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-05-31 Cont ID  
Sent By mcarsill Date 2002-05-31 Time 12:16 Rev Time 0.00
Received By mcarsill Date 2002-05-31 Time 12:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-15 Cont ID  
Sent By mcarsill Date 2002-05-15 Time 11:39 Rev Time 0.00
Received By mcarsill Date 2002-05-15 Time 11:39 Sent To  
Notes
2002-05-15 00:00:001) ANOTHER EXIT SIGN IS NEEDED IN
 CORRIDOR 43, ADJACENT TO CRYPTO ROOM.
  
 2) SECURITY DEVICES ON EXIT DOORS TO
 COMPLY WITH DELAYED EGRESS OR ACCESS
 CONTROLLED EGRESS DOORS.
  
 3) INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS TO COMPLY WITH
 APPLICABLE FIRE CODE VIOLATIONS.
  
 4) IF FIRE SPRINKLERS ARE PRESENT,
 SEPARATE PLANS AND PERMITS REQUIRED FOR
 REMODEL.
  
 5) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYTEM REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-28 Cont ID  
Sent By ndenmark Date 2002-05-28 Time 14:23 Rev Time 0.50
Received By ndenmark Date 2002-05-28 Time 14:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-21 Cont ID  
Sent By kstevens Date 2002-06-21 Time 09:30 Rev Time 0.00
Received By kstevens Date 2002-06-21 Time 09:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-06-15 Cont ID  
Sent By kstevens Date 2002-06-15 Time 13:44 Rev Time 0.00
Received By kstevens Date 2002-06-15 Time 13:44 Sent To  
Notes
2002-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PROVISIONS SHALL BE MADE FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING
 AT THE DRINKING FOUNTAINS PER SECTION
 11-4.1.3(10)
 2) DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE FOR ANY FIXTURE. (NEW DRINK-
 FOUNTAIN) SEC 11-4.17.5, 4.22.2, 4.23.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-15 Cont ID  
Sent By kstevens Date 2002-05-15 Time 19:21 Rev Time 0.00
Received By kstevens Date 2002-05-15 Time 19:21 Sent To  
Notes
2002-05-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 2, PER TABLE 403.1 TWO DRINKING
 FOUNTAINS ARE REQUIRED. SEE SEC 410.1
 2) SHT 4, HDCP SHOWER. PLEASE SHOW COM-
 PLIANCE FOR HDCP SHOWER PER SEC 11-4.21
 PROVIDE DETAILS FOR 11-4.21.2, 11-4.21.3
 11-4.21.4, 11-4.21.5, 11-4.21.6 AND 11-
 4.21.7
 3) SHT M1, WATER HEATER. PER SEC 504.7.1
 THE DISCHARGE PIPE SHALL NOT HAVE ANY
 TRAPPED SECTIONS AND SHALL HAVE A VISI-
 BLE AIR GAP OR AIR GAP FITTING LOCATED
 IN THE SAME ROOM AS THE WATER HEATER.
 4) SHT M1, WATER HEATER. PAN DRAIN SHALL
 BE A MINIMUM OF 3/4" AND SHALL BE IN-
 DIRECTLY DRAINED TO A FLOOR SINK NOT A
 FLOOR DRAIN.
 5) SHT M1, WATER ISOMETRIC. WATER HAMMER
 ARRESTORS ARE REQUIRED WHERE QUICK CLOS-
 ING VALVES ARE INSTALLED. (WASH MACHINES
 ICE MAKER, DISHWASHERS ECT., IF INSTALL-
 ED THEY SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT AT TOP
 OF THE DROP AS SHOWN.
 6) SHT M1, WATER ISOMETRIC. A MEANS OF
 CONTROLING THERMAL EXPANSION MAY BE RE-
 QUIRED PER SEC 607.3
 7) SHT 3, WATER HEATER SHALL BE PLACED
 SO AS TO PROVIDE AMPLE PROTECTION BET-
 WEEN THE APPLIANCE AND ADJACENT CONBUST-
 ABLE MATERIAL. NEC 422-17.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377