Plan Review Details - Permit 02041430
Plan Review Stops For Permit 02041430
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-07-16 Cont ID  
Sent By jgomez Date 2002-07-16 Time 13:57 Rev Time 0.00
Received By jgomez Date 2002-07-16 Time 13:57 Sent To  
Notes
2002-07-16 00:00:00APPROVED WITH PROVISO:
 1-ENGINEER OF RECORD TO PROVIDE DETAIL
 FOR 2X STRUCTURAL BUCK AS REQUIRED BY
 SWING DOOR PRODUCT APPROVAL. SEE
 COPY OF PRODUCT APPROVAL REVIEWED BY
 THE ENGINEER.
 2-PROVIDE PRODUCT APPROVAL FOR SINGLE
 HUNG WINDOWS. MAKE SURE DRAWINGS ARE
 LEGIBLE.
  
 NOTE: PROVIDE ALL THIS INFORMATION PRIOR
 TO INSTALLATION TO AVOID DELAYS OR
 CONFLICTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-06-19 Cont ID  
Sent By jgomez Date 2002-06-19 Time 10:35 Rev Time 1.50
Received By jgomez Date 2002-06-19 Time 10:35 Sent To  
Notes
2002-06-19 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-AFTER ORIGINAL DRAWINGS ARE CORRECTED
 BRING THEM TO PALM BEACH COUNTY TO PAY
 THE IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 3-REVISE DWG A1. MIXING FBC 2001 AND SBC
 FOR 110MPH. SEE COMMENTS ON PLANS.
 ALSO, THERE AREN'T SLIDING GLASS DOORS
 ON THIS PROJECT.
 4-REVISE ATTIC INSULATION VALUE. SEE THE
 ENERGY CALCULATIONS.
 5-FOOTING F1 IS 16" DEEP. FBC 2001 SEC.
 1804.1.3 REQUIRES 12" MINIMUM BELOW
 FINISHED GRADE. CLARIFY HOW IS THIS
 GOING TO BE ACHIEVED IF CONCRETE SLAB
 IS +/- 12" ABOVE GRADE.
 6-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF SHINGLES.
 B)FRENCH DOORS WITH LEGIBLE DRAWINGS.
 C)SINGLE HUNG WINDOWS WITH LEGIBLE DWGS.
  
 7-STORM SHUTTERS:
 A)INSTALLATION SCHEDULE SUBMITTED DOES
 NOT MATCH ARCHITECTURAL PLANS. MISSING
 FRENCH DOORS.
 B)CLEARLY INDICATE ON STORM SHUTTERS
 MOUNTING CONDITIONS TO BE USED IN THIS
 PROJECT.
 CLEARLY INDICATE ON INSTALLATION
 SCHEDULE SPECIFIC ANCHOR AND SPACING
 TO BE USED ACCORDING TO THE MEAN ROOF
 HEIGHT, DESIGN PRESSURES, PANEL SPAN,
 CONNECTION TYPE, EDGE DISTANCE AND
 STRUCTURE TO BE ATTACHED TO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-21 Cont ID  
Sent By jgomez Date 2002-05-21 Time 14:08 Rev Time 2.50
Received By jgomez Date 2002-05-21 Time 14:08 Sent To  
Notes
2002-05-21 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-AFTER ORIGINAL DRAWINGS ARE CORRECTED
 BRING THEM TO PALM BEACH COUNTY TO PAY
 THE IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 3-REVISE STRUCTURAL GABLE END DETAIL TO
 COMPLY WITH SECTION 2117 FBC 2001.
 (CONTINUOUS WALL).
 4-CONCRETE SLAB: SPECIFY JOINTS AS REQ'D
 BY SECTION 1909.3 FBC 2001.
 5-PERCENTAGE OF EXTERIOR OPENINGS AT
 ADDITION EXCEEDS THE PERCENTAGE THAT
 IS ALLOWED BY TABLE 600 FBC 2001.
 REVISE WEST ELEVATION AS REQUIRED.
 6-PROVIDE DETAILS/SPECS FOR ATTACHMENT
 OF NEW ROOF TO EXISTING ONE. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-SPECIFY FIREBLOCKING AS REQUIRED BY
 SECTION 705.3.1.3 FBC 2001.
 8-UPDATE PLANS AND NOTES TO FBC 2001.
 SEE COMMENTS ON PLANS AND PLEASE
 RETURN REVIEWED SET AFTER CORRECTIONS
 ARE DONE TO THE ORIGINAL DRAWINGS TO
 EXPEDITE THE REVIEW PROCESS.
 9-FOOTING F1 IS 16" DEEP. FBC 2001 SEC.
 1804.1.3 REQUIRES 12" MIN BELOW FINISH
 GRADE. CLARIFY HOW IS THIS ACHIEVED IF
 CONCRETE SLAB IS +/- 12" ABOVE GRADE.
 10-PROVIDE DOORS AND WINDOWS COMPLETE
 BUCK DETAIL. SEE SEC. 1707.4.4.2 FBC
 2001 FOR BUCK REQUIREMENTS.
 11-PROVIDE PRODUCT APPROVAL FOR:
 A)FRENCH DOORS WITH LEGIBLE DRAWINGS.
 B)SINGLE HUNG WINDOWS WITH LEGIBLE DWGS.
  
 12-STORM SHUTTERS:
 A)NEED PRODUCT APPROVAL W/ LEGIBLE DWGS.
 B)CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS TO BE USED.
 PROVIDE KEY PLAN AND ANCHOR SCHEDULE
 INDICATING ANCHOR TYPE AND SPACING TO
 BE USED. SEE ATTACHED SAMPLE.
 13-OWNER/AGENT TO SIGN AND DATE BOTTOM
 FORM OF ENERGY CALCULATIONS.
 14-OWES $332.69 FOR UPDATE CONSTRUCTION
 VALUE AND RADON FEES.
 15-ENGINEER OF RECORD TO HAVE ALL HIS
 INFORMATION IN ALL DRAWINGS AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORD

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-03 Cont ID  
Sent By btrobaug Date 2002-05-03 Time 06:57 Rev Time 0.00
Received By btrobaug Date 2002-05-03 Time 06:37 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-05-06 Cont ID  
Sent By kstevens Date 2002-05-06 Time 11:56 Rev Time 0.30
Received By pkrauss Date 2002-05-06 Time 16:02 Sent To  
Notes
2002-05-06 00:00:00FLA ENERGY CODE - PRESCRIPTIVE METHOD C,
 FORM 600C-01 - ITEM #11 COOLING SYSTEM
 INDICATES A ROOM UNIT 8.5 SEER.FOR THE
 ADDITION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-05-06 Cont ID  
Sent By btrobaug Date 2002-05-03 Time 06:58 Rev Time 0.00
Received By kstevens Date 2002-05-06 Time 11:56 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-03 Cont ID  
Sent By sgraham Date 2002-05-03 Time 11:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***