| Plan Review Stops For Permit 02041319 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-04-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-04-30 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-30 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2002-04-30 00:00:00 | 1) SMOKE DETECTORS ARE TO BE INSTALLED | | | A MINIMUM OF AT LEAST THREE FEET FROM | | | AIR HANDLING DIFFUSERS. | | | 2) THE EXISTING FIRE ALARM SYSTEM FOR | | | THE BUILDING IS TO REMAIN IN SERVICE | | | UNTIL THE NEW SYSTEM IS INSTALLED, | | | TESTED AND APPROVED BY THE FIRE RESCUE | | | DEPARTMENT. | | | 3) PLEASE INDICATE WHAT VOICE EVACUATION | | | MESSAGE IS PLANNED FOR THE BUILDING. | | | THE SPEC BOOKS INDICATE TWO STANDARD | | | MESSAGES FOR THE DIGITAL MESSAGE MODULE. | | | THIS INFORMATION IS TO BE PROVIDED IN | | | WRITING. | | | 4) ANY AND ALL FIRE WALL OR FLOOR | | | PENETRATIONS ARE TO BE SEALED IN AN | | | APPROVED MANNER. | | | 5) THE NEW FIRE ALARM SYSTEM IS TO BE | | | MONITORED BY LICENSED UL LISTED CENTRAL | | | STATION APPROVED BY THE FIRE RESCUE | | | DEPARTMENT. | | | 6) SMOKE DETECTORS ARE MISSING IN THE | | | VESTIBULES OF THE TRASH CHUTE ROOMS | | | ON PAGE FA-3. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|