Plan Review Details - Permit 02041275
Plan Review Stops For Permit 02041275
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-07-12 Cont ID  
Sent By lmartine Date 2002-07-12 Time 14:54 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-13 Cont ID  
Sent By rbrown Date 2002-06-13 Time 20:52 Rev Time 0.00
Received By rbrown Date 2002-06-13 Time 20:52 Sent To  
Notes
2002-06-13 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FBC 1606.1.4STOREFRONT ELEVATION
 A/A3 SHOWS THE REPLACEMENT OF EXISTING
 STOREFRONT FRAMING AND GLAZING.SUBMIT
 A PRODUCT APPROVAL FOR THE PROPOSED
 SYSTEM.
  
 3) FBC 11-4.16SHEET A3.1, EXISTING
 TOILET ROOM ELEVATIONS.ARE THE GRAB
 BARS AND OTHER FIXTURES EXISTING?
 IF NOT (REF. SHEET A8, SPECIFICATION
 ITEM 10), THEN THEY SHALL BE LOCATED AND
 INSTALLED TO COMPLY WITH THE
 REQUIREMENTS SHOWN IN FIG. 28, 29, 31
 AND 32.ANNOTATE AND DIMENSION THE
 PLANS TO DEMONSTRATE COMPLIANCE.THE
 GRAB RAIL BEHIND THE W.C. SHALL BE MIN.
 36" LONG.
  
 4) FBC 11-4.19SHEET A3.1ADD
 DIMENSIONS TO THE PLANS TO DEMONSTRATE
 COMPLIANCE WITH THE TOILET MIRROR
 MOUNTING HEIGHT REQUIREMENTS (FIG. 31).
  
 5) FBC 11-4.15 INTERIOR ELEVATION C/A3.1
 WORK ROOM DRINKING FOUNTAIN.ADD
 DIMENSIONS AND A SIDE ELEVATION OF THE
 DRINKING FOUNTAIN TO DEMONSTRATE
 COMPLIANCE WITH THE SPOUT HEIGHT AND LEG
 CLEARANCE REQUIREMENTS SHOWN IN FIG. 27
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-03 Cont ID  
Sent By jleahy Date 2002-06-03 Time 18:57 Rev Time 1.00
Received By jleahy Date 2002-06-03 Time 18:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-06-19 Cont ID  
Sent By mcarsill Date 2002-06-19 Time 16:05 Rev Time 0.00
Received By mcarsill Date 2002-06-19 Time 16:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-07 Cont ID  
Sent By ndenmark Date 2002-06-07 Time 10:26 Rev Time 0.33
Received By ndenmark Date 2002-06-07 Time 10:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-08 Cont ID  
Sent By kstevens Date 2002-07-08 Time 15:53 Rev Time 0.00
Received By kstevens Date 2002-07-08 Time 15:53 Sent To  
Notes
2002-07-08 00:00:00PASSED/PROVISO
  
 A CUP DISPENSER IS REQUIRED AT THE
 DRINKING FOUNTAIN FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 11-4.1.3(10)

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-15 Cont ID  
Sent By kstevens Date 2002-06-15 Time 09:53 Rev Time 0.00
Received By kstevens Date 2002-06-15 Time 09:53 Sent To  
Notes
2002-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT M1 WATER HEATER DETAIL. DIELECT-
 RIC UNIONS NOT APPROVED FOR WATER PIPE.
 2) SHT M1 WATER HEATER DETAIL. SHOWS
 DISCHARGE FROM P/T RELIEF VALVE TO FLOOR
 DRAIN. NOT APPROVED AS INDIRECT WASTE
 RECEPTOR.
 3) SHT M1 WATER HEATER DETAIL. THERMAL
 EXPANSION CONTROL MAY BE REQUIRED IF A
 BACKFLOW IS INSTALLED ON WATER SERVICE.
 SEC 607.3 - 607.3.2
 4) SHT M1 NOTE #4, AIR CHAMBERS ARE NOT
 APPROVED. SEC 604.9 WATER HAMMER ARREST-
 ORS.
 5) SHT A1.1 DRINKING FOUNTAIN. PLEASE
 PROVIDE DETAIL TO SHOW COMPLIANCE OF
 SECTION 4.15 AND ALL SUBSECTIONS.
 ALSO SEC 4.1.3(10) FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377