| Plan Review Stops For Permit 02041238 |
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-05-19 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-05-19 |
Time |
11:46 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-19 00:00:00 | 5-19-02 APPR WITH REVISION,UNDER"F".PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-05-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-06 |
Time |
19:31 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-06 |
Time |
19:31 |
Sent To |
|
|
| Notes |
| 2002-05-06 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. TYPE OF GAS, (LP OR NATURAL) | | | 2. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE. | | | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 GAS CODE. (SUBMITTED SHEETS DO | | | NOT SHOW APPROVAL FROM LISTED AGENCY.) | | | 4) RECHECK ALL PIPE SIZES | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
|