Plan Review Details - Permit 02041170
Plan Review Stops For Permit 02041170
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-13 Cont ID  
Sent By hpiskura Date 2002-05-13 Time 13:20 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-30 Cont ID  
Sent By dpalmer Date 2002-04-30 Time 08:11 Rev Time 0.00
Received By dpalmer Date 2002-04-30 Time 08:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-10 Cont ID  
Sent By mcarsill Date 2002-05-10 Time 12:43 Rev Time 0.00
Received By mcarsill Date 2002-05-10 Time 12:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-06 Cont ID  
Sent By pkrauss Date 2002-05-06 Time 11:08 Rev Time 0.50
Received By pkrauss Date 2002-05-06 Time 10:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-08-12 Cont ID  
Sent By pschmitz Date 2002-08-12 Time 09:45 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-08-12 00:00:00MEDICAL GAS REVISION,APPR PES.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-11 Cont ID  
Sent By kstevens Date 2002-05-11 Time 11:37 Rev Time 0.00
Received By kstevens Date 2002-05-11 Time 11:37 Sent To  
Notes
2002-05-11 00:00:00PASSED/PROVISO
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-1 PLUMBING NOTES #'S 1&2 CODE
 COMPLIANCE NOT STANDARD CODE BUT FBC.
 2) AIR CHAMBERS NOT APPROVED
 3) LOCATE WATER HAMMER ARRESTORS NEAR
 FIXTURE NOT AT TOP OF DROP AS SHOWN
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377