Plan Review Details - Permit 02041108
Plan Review Stops For Permit 02041108
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-15 Cont ID  
Sent By btrobaug Date 2002-05-06 Time 07:15 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-06 Cont ID  
Sent By kstevens Date 2002-05-03 Time 17:53 Rev Time 0.00
Received By btrobaug Date 2002-05-06 Time 07:15 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-12 Cont ID  
Sent By kstevens Date 2002-06-12 Time 13:41 Rev Time 0.00
Received By kstevens Date 2002-06-12 Time 13:41 Sent To  
Notes
2002-06-12 00:00:00PASSED/PROVISO
  
 1-1/2" VENT REQUIRED FOR MAIN DRAINS.
 ENGINEERING FOR 1 HP PUMP - 1.5 HP PUMP
 USED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-03 Cont ID  
Sent By kstevens Date 2002-05-03 Time 17:52 Rev Time 0.00
Received By kstevens Date 2002-05-03 Time 17:53 Sent To E
Notes
2002-05-03 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 2)
 FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 3)
 FBC-2001 SEC 424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL) - VENT SHALL BE
 1-1/2" OR AN ENGINEERING REPORT VERIFING
 THAT 1" VENT WILL WORK.
 4)
 FBC-2001 SEC 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 5)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 6)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 7)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-18 Cont ID  
Sent By sgraham Date 2002-04-18 Time 10:49 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***