Plan Review Details - Permit 02041045
Plan Review Stops For Permit 02041045
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-05-02 Cont ID  
Sent By mcarsill Date 2002-05-02 Time 08:39 Rev Time 0.00
Received By mcarsill Date 2002-05-02 Time 08:39 Sent To  
Notes
2002-05-02 00:00:001) PLANS MAKE REFERENCE TO HOOD WRAPPING
 BUT NO DOCUMENTATION WAS SUBMITTED WITH
 PLANS.
 2) PLEASE INDICATE ON THE PLANS THAT
 THE MAKE-UP AIR IS A MINIMUM OF 10 FEET
 FROM THE HOOD EXHAUST.
 3) GREASE EXHAUST DUCT IS TO BE A
 MINIMUM OF AT LEAST 10 FEET FROM
 ADJACENT BUILDING, PROPERTY LINES,
 ETC.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-22 Cont ID  
Sent By pkrauss Date 2002-04-22 Time 13:23 Rev Time 0.45
Received By pkrauss Date 2002-04-22 Time 13:20 Sent To  
Notes
2002-04-22 00:00:00 
 1.PROVIDE MANUFACTURER SUBMITTAL FOR
 THE 3M FASTWRAP+.
  
 2.INDICATE 1 OR 2 HR RATING.
  
 3.AS PER 2001 FBC, MECHANICAL 306.5,
 EQUIPMENT & APPLIANCES REQUIRING
 ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FT, SUCH ACCESS SHALL
 BE PROVIDED BY A PERMANENT APPROVED
 MEANS OF ACCESS.
  
 4.WHERE APPLIANCES ARE INSTALLED ON A
 ROOF HAVING A SLOPE OF 3 UNITS
 VERTICAL IN 12 UNIT HORIZONTAL OR
 GREATER, A LEVEL PLATFORM SHALL BE
 PROVIDED ON EACH SIDE OF THE
 APPLIANCE TO WHICH ACCESS IS
 REQUIRED.2001 FBC(M) 306.6.
  
 5.AS PER NFPA 96 4-8.2.1 (A), A MIN.
 OF 10 FT SEPARATION FROM THE OUTLET
 TO ADJACENT BUILDINGS, PROPERTY
 LINES, AND AIR INTAKES.
  
 6.SHOW COMPLIANCE WITH 2001 FBC(M)
 508.1.1, THE TEMPERATURE
 DIFFERENTIAL BETWEEN THE MAKEUP AIR
 AND THE AIR IN THE CONDITIONED SPACE
 SHALL NOT EXCEED 10 DEGREES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.