Plan Review Details - Permit 02041045
| Plan Review Stops For Permit 02041045 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-05-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-02 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-02 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2002-05-02 00:00:00 | 1) PLANS MAKE REFERENCE TO HOOD WRAPPING | | | BUT NO DOCUMENTATION WAS SUBMITTED WITH | | | PLANS. | | | 2) PLEASE INDICATE ON THE PLANS THAT | | | THE MAKE-UP AIR IS A MINIMUM OF 10 FEET | | | FROM THE HOOD EXHAUST. | | | 3) GREASE EXHAUST DUCT IS TO BE A | | | MINIMUM OF AT LEAST 10 FEET FROM | | | ADJACENT BUILDING, PROPERTY LINES, | | | ETC. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-22 |
Time |
13:23 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-04-22 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2002-04-22 00:00:00 | | | | 1.PROVIDE MANUFACTURER SUBMITTAL FOR | | | THE 3M FASTWRAP+. | | | | | | 2.INDICATE 1 OR 2 HR RATING. | | | | | | 3.AS PER 2001 FBC, MECHANICAL 306.5, | | | EQUIPMENT & APPLIANCES REQUIRING | | | ACCESS ARE INSTALLED ON ROOFS OR | | | ELEVATED STRUCTURES AT A HEIGHT | | | EXCEEDING 16 FT, SUCH ACCESS SHALL | | | BE PROVIDED BY A PERMANENT APPROVED | | | MEANS OF ACCESS. | | | | | | 4.WHERE APPLIANCES ARE INSTALLED ON A | | | ROOF HAVING A SLOPE OF 3 UNITS | | | VERTICAL IN 12 UNIT HORIZONTAL OR | | | GREATER, A LEVEL PLATFORM SHALL BE | | | PROVIDED ON EACH SIDE OF THE | | | APPLIANCE TO WHICH ACCESS IS | | | REQUIRED.2001 FBC(M) 306.6. | | | | | | 5.AS PER NFPA 96 4-8.2.1 (A), A MIN. | | | OF 10 FT SEPARATION FROM THE OUTLET | | | TO ADJACENT BUILDINGS, PROPERTY | | | LINES, AND AIR INTAKES. | | | | | | 6.SHOW COMPLIANCE WITH 2001 FBC(M) | | | 508.1.1, THE TEMPERATURE | | | DIFFERENTIAL BETWEEN THE MAKEUP AIR | | | AND THE AIR IN THE CONDITIONED SPACE | | | SHALL NOT EXCEED 10 DEGREES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|