Plan Review Details - Permit 02040876
Plan Review Stops For Permit 02040876
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-04-30 Cont ID  
Sent By hpiskura Date 2002-04-30 Time 12:59 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-30 00:00:00PROVISO:ARCHITECT MUST PROVIDE WRITTEN
 VERIFICATION THAT DESIGN OF THIS PLAN
 IS IN COMPLIANCE WITH THE 2001 FLORIDA
 BUILDING CODE.ACCEPTANCE OF THIS
 REVIEW NOT WITH STANDING.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-26 Cont ID  
Sent By dpalmer Date 2002-06-26 Time 06:08 Rev Time 0.00
Received By dpalmer Date 2002-06-26 Time 06:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-29 Cont ID  
Sent By dpalmer Date 2002-04-29 Time 20:30 Rev Time 0.00
Received By dpalmer Date 2002-04-29 Time 20:29 Sent To  
Notes
2002-04-29 00:00:00*************** UNSAT *****************
  
 1 )NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
 PLEASE NOTE THAT ALL CONTINUOUS LOADS
 NEED TO BE SHOWN AT 125%. 230-42/215-2,3
  
  
 2)NOTE: PLEASE NOTE THAT WE ARE UNDER
 THE "99" NEC. PLEASE NOTE TAHT PLANS
 SHOW 1997? PLEASE ALSO NOTE THAT PLANS
 SHOW WRONG CODES FOR OTHER TRADES.
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
  
 3)NOTE: PLEASE NOTE TWO " 1TC" PANELS
 SHOWN ON MDP. (MISPRINT)
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 5661-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-07-17 Cont ID  
Sent By mcarsill Date 2003-07-17 Time 16:11 Rev Time 0.00
Received By mcarsill Date 2003-07-17 Time 16:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-10 Cont ID  
Sent By mcarsill Date 2002-05-10 Time 15:54 Rev Time 0.00
Received By mcarsill Date 2002-05-10 Time 15:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-25 Cont ID  
Sent By hmoser Date 2002-05-25 Time 10:46 Rev Time 0.75
Received By hmoser Date 2002-05-25 Time 10:46 Sent To  
Notes
2002-05-25 00:00:00CALLED LEFT MESSAGE TO PICKUP PLANS.
 PLANS IN BOX I
 H.M. 5/25/02

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-06 Cont ID  
Sent By kstevens Date 2002-07-06 Time 05:24 Rev Time 0.00
Received By kstevens Date 2002-07-06 Time 05:24 Sent To  
Notes
2002-07-06 00:00:00PASSED/PROVISO
  
 ALL WATER HAMMER ARRESTORS SHALL BE LO-
 CATED NEAR FIXTURES - NOT AT TOP OF DROP

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-11 Cont ID  
Sent By kstevens Date 2002-05-11 Time 10:17 Rev Time 0.00
Received By kstevens Date 2002-05-11 Time 09:35 Sent To  
Notes
2002-05-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A-0.1 APPLICABLE CODE ARE NOT
 STANTARD CODES BUT FLA. BLDG. CODES.
 PLEASE CHANGE REFERENCE.
 2) SHT A-2.2 DRINKING FOUNTAIN, EITHER
 HI-LOW DRINKING FOUNTAIN OR OTHER PROVI-
 SIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING PER FBC 11-4.1.3(10)
 3) SHT P-1 WATER RISER DIAGRAM, AIR
 CHAMBERS NOT APPROVED. WATER HAMMER ARR-
 ESTORS ARE REQUIRED FOR QUICK CLOSING
 VALVES (DISHWASHERS, ICE MAKERS, WASH
 MACHINES ECT). IF USED THEY SHALL BE LO-
 CATED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT AT TOP OF DROPS AS SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377