Plan Review Details - Permit 02040719
Plan Review Stops For Permit 02040719
Review Stop P PLUMBING
Rev No 2 Status P Date 2002-04-18 Cont ID  
Sent By kstevens Date 2002-04-18 Time 18:04 Rev Time 0.00
Received By kstevens Date 2002-04-18 Time 18:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-12 Cont ID  
Sent By kstevens Date 2002-04-12 Time 10:53 Rev Time 0.00
Received By kstevens Date 2002-04-12 Time 10:53 Sent To  
Notes
2002-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUELGAS
 CODE SECS. 304.1 THRU 304.7.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 GAS CODE APPENDIX A. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC. 301.
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS