| Notes |
| 2002-05-02 00:00:00 | A) A MINIMUM OF A 2" PIPE IS TO BE | | | PROVIDED FOR VENTING. THIS PIPE IS TO | | | BE AT LEAST 12 FEET HIGH. | | | B) APPROPRIATE LABELS, WARNING SIGNS, | | | ARE TO BE PROVIDED FOR THE TANK. | | | C) THE TWO HOUR AREA IS TO BE FIRE | | | SPRINKLER PROTECTED. | | | D) SEPARATE PLANS ARE REQUIRED FOR | | | PIPING FROM THE FUEL TANK TO THE | | | GENERATOR. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|