Plan Review Details - Permit 02040697
Plan Review Stops For Permit 02040697
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-24 Cont ID  
Sent By jwitmer Date 2002-06-24 Time 19:55 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-06-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02040697
 ADD: 4812 S DIXIE HWY
 CONT: J P HURBON, INC
 TEL: (561)575-2461
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 JIM WITMER
 PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-17 Cont ID  
Sent By jwitmer Date 2002-04-17 Time 06:48 Rev Time 2.00
Received By jwitmer Date 2002-04-17 Time 06:48 Sent To  
Notes
2002-04-17 00:00:00BUILDING PLAN REVIEW
 PERMIT 02040697
 4812 S DIXIE
 CONT: J.P. HURBON, INC.
 575-2461
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 OCCUPANCY= A2 SMALL ASSEMBLY
 40'X48'= 1920 S F @ 15 F/PER=128 OCC.
  
 1)- FL BLD CODE 104.2.1.2 ADDITIONAL
 INFORMATION, A SEATING PLAN WITH ISLE
 WIDTHS AND DESIGNATE EGRESS DOORS.
 2)- FRONT ENTRY DOOR SWING NOT INDICATED
 FL BLD CODE 1012.1.2 EGRESS DOORS SHALL
 BE SIDE SWINGING AND (1) WHEN SERVING AN
 OCCUPANT LOAD OF 50 OR MORE THAN IT
 SHALL SWING IN THE DIRECTION OF EGRESS.
 3)- FL BLD CODE 1012.1.3 THE ELEVATION
 OF SURFACES ON BOTH SIDES OF A DOORWAY
 SHALL NOT VARY MORE THAN 1/2".THE ELEVA-
 TION SHALL BE MAINTAINED ON BOTH SIDES
 OF THE DOORWAY FOR A DISTANCE AT LEAST
 EQUAL TO THE WIDTH OF THE WIDEST LEAF.4)
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2002-06-25 Cont ID  
Sent By dpalmer Date 2002-06-25 Time 14:49 Rev Time 0.00
Received By dpalmer Date 2002-06-25 Time 14:49 Sent To  
Notes
2002-06-25 00:00:00SEPARATE PERMIT AND PLANS WERE BROUGHTIN
 FOR ELECTRICAL .

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-29 Cont ID  
Sent By dpalmer Date 2002-04-29 Time 19:19 Rev Time 0.00
Received By dpalmer Date 2002-04-29 Time 19:19 Sent To  
Notes
2002-04-29 00:00:00****************** UNSAT **************
  
 1)NOTE:PLEASE NOTE THAT ALL BRANCH
 CIRCUIT #`S ARE TO BE ON PLANS AND TO
 CORRELATE WITH A SUBMITTED PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO BE SUBMITTED FOR ALL NEW LOADS
 ADDED. 220 OF THE NEC. 215-5,220-3,220-
 -10,220-11,220-13. PLEASE NOTE ALL
 CONTINUOUS LOAD AT 125%. 215-2-3, 230-42
  
  
 3)NOTE: PLEASE NOTE THAT A CONTRACT
 NEEDS TO BE SUBMITTED TO VERIFY VALUE
 OF SCOPE OF WORK. 104.6.5 ADMIN CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-09 Cont ID  
Sent By mcarsill Date 2002-05-09 Time 13:45 Rev Time 0.00
Received By mcarsill Date 2002-05-09 Time 13:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-04-26 Cont ID  
Sent By pkrauss Date 2002-04-26 Time 11:27 Rev Time 0.30
Received By pkrauss Date 2002-04-26 Time 11:27 Sent To  
Notes
2002-04-26 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-06-21 Cont ID  
Sent By kstevens Date 2002-06-21 Time 06:29 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***