Plan Review Details - Permit 02040690
Plan Review Stops For Permit 02040690
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-08 Cont ID  
Sent By lsmith Date 2002-05-08 Time 13:14 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-23 Cont ID  
Sent By btrobaug Date 2002-05-23 Time 14:51 Rev Time 0.00
Received By btrobaug Date 2002-05-23 Time 14:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-24 Cont ID  
Sent By kstevens Date 2002-04-24 Time 08:45 Rev Time 0.00
Received By btrobaug Date 2002-04-24 Time 13:05 Sent To  
Notes
2002-04-24 00:00:00~~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE A LOAD CALCULATION FOR
 THE SERVICE THAT'S FEEDING THE POOL
 EQUIPMENT,AND SHOW ADDITIONAL LOAD.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-22 Cont ID  
Sent By kstevens Date 2002-05-22 Time 13:45 Rev Time 0.00
Received By kstevens Date 2002-05-22 Time 13:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-24 Cont ID  
Sent By kstevens Date 2002-04-24 Time 08:44 Rev Time 0.00
Received By kstevens Date 2002-04-24 Time 08:41 Sent To E
Notes
2002-04-24 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW.
 A)
 FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, ADD TO NOTES OR SUBMITTAL)
 B)
 FBC-2001 SEC 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 C)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 D)
 FBC-2001 SEC 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-15 Cont ID  
Sent By sgraham Date 2002-04-15 Time 13:04 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***