Plan Review Details - Permit 02040626
Plan Review Stops For Permit 02040626
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2002-06-14 Cont ID  
Sent By btrobaug Date 2002-06-10 Time 15:01 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-10 Cont ID  
Sent By btrobaug Date 2002-06-10 Time 15:01 Rev Time 0.00
Received By btrobaug Date 2002-06-07 Time 15:39 Sent To B
Notes
2002-06-10 00:00:00PROVISO
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING,AND MAKE THE
 NECESSARY CHANGES IN THE FIELD BEFORE
 CALLING INSPECTION.ALSO CORRECT AND
 SUBMIT "AS BUILTS" SHOWING CORRECTIONS.
  
 1} BREAKERS #14 & #16 ARE SHOWN AS "GFI
 KITCHEN RECEPT." APPLIANCE CIRCUITS ARE
 LISTED ON THE SCHEDULE AND SHOWN ON THE
 PLAN AS GFI,WHICH MEETS THE REQUIREMENTS
 OF THIS REVIEW.SPACES #14 AND #16
 SHOULD LIST "ARC FAULT BREAKER" PER
 210-12.
  
 2} THE #6 GROUND FROM THE METER TO THE
 FIRST MEANS OF DISCONNECT NEEDS TO BE
 REMOVED TO PREVENT PARALLEL PATHS TO
 GROUND WITH THE GROUNDED CONDUCTOR. SEE
 250-24(A)(5).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-07 Cont ID  
Sent By dpalmer Date 2002-05-07 Time 20:08 Rev Time 0.00
Received By dpalmer Date 2002-05-07 Time 20:08 Sent To B
Notes
2002-05-07 00:00:00************** UNSAT ****************
  
 1 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 2)NOTE: PLEASE NOTE GARAGE OUTLET TO BE
 SHOWN AS GFI/GFI PROTECTED. PER 210-8
  
 3)NOTE: PLEASE NOTE THAT PLANS ARE SHOW-
 ING A MAIN DISCONNECT NEXT TO METERCAN
 AND NEXT TO PANEL INSIDE GARAGE??
 PLEASE CLARIFY WHICH ONE? IF ANY? PLEASE
 NOTE THAT RISER DIAGRAM SHOWS MAIN DISC
 OUTSIDE.
  
 4)NOTE: PLEASE NOTE THAT MIN SIZING OF
 OCP AND WIRE FOR A 10KW AHU. PER 424-3B
  
 5)NOTE: PLEASE NOTE THAT AN OVEN AND
 COOKTOP IS SHOWN ON PANEL SCHEDULE AND
 ONLY THE COOKTOP IS ON LOAD CALCULATIONS
 PLEASE ADD TO LOAD CALCS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-19 Cont ID  
Sent By pkrauss Date 2002-12-19 Time 08:55 Rev Time 0.20
Received By pkrauss Date 2002-12-19 Time 08:55 Sent To  
Notes
2002-12-19 00:00:00MECH PERMIT 02040628
 REVISED ENERGY CALCS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-07 Cont ID  
Sent By hmoser Date 2002-05-07 Time 18:25 Rev Time 0.33
Received By hmoser Date 2002-05-07 Time 18:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-03 Cont ID  
Sent By kstevens Date 2002-05-03 Time 19:16 Rev Time 0.00
Received By kstevens Date 2002-05-03 Time 19:16 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-06-14 Cont ID  
Sent By rmcdouga Date 2002-06-14 Time 08:40 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-14 00:00:00************BUILDING PROVISO************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) PROVIDE DRAWINGS FOR THE 16 FOOT WIDE
 OVERHEAD GARAGE DOOR,THE ONES SUBMITTED
 WITH THE PRODUCT APPROVAL IS FOR A DOOR
 WITH A MAXIMUM WIDTH OF 9 FEET.
  
 TRUSS DRAWINGS ARE NO LONGER REQUIRED TO
 BE SUBMITTED FOR PLAN REVIEW. THEY WILL
 BE REVIEWED BY THE INSPECTOR IN THE
 FIELD.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-05-20 Cont ID  
Sent By rmcdouga Date 2002-05-20 Time 14:00 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-05-20 00:00:00BUILDING DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) PROVIDE AT LEAST ONE BATHROOM WITH A
 DOOR THAT HAS A 29 INCH CLEAR OPENING,
 AS REQUIRED BY THE 2001 FLORIDA
 BUILDING CODE CHAPTER 11.
  
 3) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES FOR THE SKYLIGHT AND THE GLASS
 BLOCK OPENINGS ON THE PLANS.
  
 4) THE 8'-0" PRIVACY WALL AND THE ONE
 HOUR RATED ACCESS PANEL ARE REQUIRED TO
 REMAIN DUE TO ZERO LOT LINE WITH THE
 ADJOINING LOT. (TABLE 600)
  
 5) PLEASE REVISE DETAIL 2 ON A4 TO SHOW
 TAPERED BUCKS THAT EXTEND BEYOND THE
 FACE OF THE WINDOW FRAME AND THE FRAME
 ANCHORS THROUGH THE 1X BUCK AND INTO THE
 STRUCTURAL SUBSTRATE MATERIAL AS
 REQUIRED BY FBC SEC. 1707.4.4.2.
  
 6) THE MINIMUM BUCK SIZE DESIGN
 CLARIFICATION DETAILS FOR THE KDI
 WINDOWS DO NOT COMPLY WITH THE 2001 FBC
 SECTION 1707.4.4.2. WHEN USING 1X BUCKS
 THE ANCHORS FOR THE FRAMES ARE REQUIRED
 TO ATTACH THROUGH THE BUCKS AND INTO THE
 STRUCTURAL SUBSTRATE MATERIAL. TAPERED
 BUCKS MUST EXTEND BEYOND THE FACE OF THE
 FRAMES TO PROVIDE FULL SUPPORT OF THE
 FRAME.
  
 7) PLEASE UPDATE THE DESIGN CRITERIA ON
 SHEET S1 TO THE 2001 FBC,(ASCE 7-98, 140
 MPH. THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 8) INDICATE ON THE PLANS THAT THE WELDED
 WIRE REINFORCEMENT FABRIC WILL BE
 SUPPORTED WITH APPROVED MATERIALS OR
 SUPPORTS PER THE 2001 FBC SEC. 1909.3.
  
 9) PLEASE REVISE GENERAL NOTES (3) & (4)
 ON S4 FROM STANDARD TO FLORIDA BUILDING
 CODE.
  
 10) SBCCI EVALUATION REPORT #9733 FOR
 KDI HAS BEEN REPLACED BY # 9733A. PLEASE
 SUBMIT CURRENT REPORT.
  
 11) PRODUCT APPROVAL FOR ENTEGRA ROOF
 TILE EXPIRED ON 10-01-01. PLEASE SUBMIT
 CURRENT APPROVAL.
  
 12) THE KEY PLAN AND INSTALLATION
 SCHEDULE SUBMITTED FOR THE STORM PANELS
 IS FOR A DIFFERENT MODEL (A). PLEASE
 SUBMIT THE ONES FOR MODEL "C".
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-25 Cont ID  
Sent By sgraham Date 2002-04-25 Time 09:07 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***