Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-27 Cont ID  
Sent By dpalmer Date 2002-06-27 Time 13:29 Rev Time 0.00
Received By dpalmer Date 2002-06-27 Time 13:29 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-07 Cont ID  
Sent By dpalmer Date 2002-05-07 Time 20:31 Rev Time 0.00
Received By dpalmer Date 2002-05-07 Time 20:31 Sent To B
Notes
2002-05-07 00:00:00***************** UNSAT ***************
  
 1 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 2)NOTE: PLEASE CLARIFY, PLANS SHOW A
 MAIN DISCONNECT INSIDE WITH PANEL AND
 OUTSIDE WITH METER? WHICH ONE? PLEASE
 NOTE RISER DIAGRAM SHOWS MAIN OUTSIDE.
  
 3)NOTE: PLEASE NOTE THAT PANEL SCHEDULE
 SHOWS AN OVEN AND YET LOAD CALCULATIONS
 DO NOT INCLUDE OVEN. PLEASE INCLUDE.
  
 4)NOTE: PLEASENOTE OCP AND WIRE FOR
 AHU NEEDS TO BE SIZED FOR 10KW PER
 424-3B MIN125%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-80096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-18 Cont ID  
Sent By pkrauss Date 2002-12-18 Time 16:43 Rev Time 0.15
Received By pkrauss Date 2002-12-18 Time 16:43 Sent To  
Notes
2002-12-18 00:00:00MECH PERMIT 02040633
 REVISED ENERGY CALCS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-16 Cont ID  
Sent By pkrauss Date 2002-10-16 Time 14:27 Rev Time 0.35
Received By pkrauss Date 2002-10-16 Time 12:45 Sent To  
Notes
2002-10-16 00:00:00MECH REV PERMIT 02040633

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-06 Cont ID  
Sent By hmoser Date 2002-05-06 Time 18:38 Rev Time 0.50
Received By hmoser Date 2002-05-06 Time 18:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-27 Cont ID  
Sent By dpalmer Date 2002-06-27 Time 13:29 Rev Time 0.33
Received By jleech Date 2002-04-27 Time 07:32 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-07-01 Cont ID  
Sent By rmcdouga Date 2002-07-01 Time 08:40 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-05-17 Cont ID  
Sent By rmcdouga Date 2002-05-17 Time 11:01 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-05-17 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) INDICATE THE POSTITIVE AND NEGATIVE
 PRESSURES FOR THE SKYLIGHT ON THE PLANS.
  
 3)PLEASE REVIEW THE POSTIVE AND NEGATIVE
 PRESSURES THAT ARE GIVEN FOR THE DOORS
 AND WINDOWS THE APPEAR TO BE INCORRECT.
 (TOO HIGH)
  
 4) PLEASE REVIEW THE M.O. LISTED FOR THE
 1/2 33SH WINDOW, IT IS TOO LARGE.
  
 5) INDICATE ON THE PLANS THAT THE WELDED
 WIRE REINFORCEMENT FABRIC WILL BE
 SUPPORTED WITH APPROVED MATERIALS OR
 SUPPORTS PER 2001 FBC SEC. 1909.3.
  
 6) REVISE ITEM #2 ON A1 TO REFERENCE THE
 FLORIDA BUILDING CODE.
  
 7) THE CALCULATIONS FOR THE OPENINGS
 ALLOWED BY TABLE 600 CONTAINS SEVERAL
 ERRORS. THE AREA ALLOWED AS OPENINGS IS
 52.3 SQFT. AND OPENINGS TOTAL 54.4 SQFT.
 PLEASE CORRECT.
  
 8) PLEASE REVISE DETAIL 2 ON A4 TO SHOW
 TAPERED BUCKS EXTENDING BEYOND THE FACE
 OF WINDOW AND DOOR FRAMES TO PROVIDE
 FULL SUPPORT OF THE FRAME AND ANCHORS
 FOR WINDOW/DOOR FRAMES THROUGH THE 1X
 BUCKS AND INTO THE STRUCTURAL SUBSTRATE
 MATERIAL AS REQUIRED BY THE FBC SECTION
 1707.4.4.2.
  
 9) THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
 PLEASE UPDATE THE STRUCTURAL DESIGN
 INFORMATION ON S1.
  
 10) THE PARTY WALL DETAILS 6 & 8 ON S3
 SHOULD INDICATE THAT THE FIRE RETARDANT
 PLYWOOD IS REQUIRED TO EXTEND 4 FEET ON
 EACH SIDE THE WALLS PER 704.4(2) FBC.
  
 11) PLEASE UPDATE THE NOTES ON S4 TO
 REFERENCE THE 2001 FLORIDA BUILDING CODE
 THEY HAVE BEEN MARKED ON PLANS.
  
 12) THE SBCCI EVALUATION REPORT (PRODUCT
 APPROVAL) FOR KDI DOORS AND WINDOWS HAS
 BEEN UPDATED BY REPORT #9733A. PLEASE
 SUBMIT CURRENT REPORT.
  
 13) THE BUCK ATTACHMENT DETAILS DO NOT
 COMPLY WITH 1707.4.4.2 OF THE 2001 FBC.
 PLEASE SUBMIT REVISED DRAWINGS.
  
 14) PROVIDE ORIGINAL DATED, SIGNED AND
 SEALED COPY OF THE SINGLE HUNG WINDOW
 ANALYSIS CHART AND ENGINEER'S
 CALCULATIONS FOR KDI WINDOWS.
  
 15) THE PRODUCT APPROVAL FOR THE ENTEGRA
 ROOF TILE EXPIRED ON 10-01-01. SUBMIT
 CURRENT PRODUCT APPROVAL.
  
 16) PLEASE REVIEW THE OPENING SIZES ON
 THE STORM PANEL INSTALLATION SCHEDULE
 AND REVISE TO MATCH WINDOW OPENINGS AS
 NECESSARY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202
  
 TRUSSES UNSAT
  
 1) PLEASE REVIEW THE CONNECTOR FOR JOINT
 2 ON TRUSS TG1. THE TRUSS DRAWING LISTS
 AN UPLIFT OF 4381# AND THE PLANS SHOW A
 TA5 RATED FOR 2490#.
  
 2) THE STANDARD GABLE END DETAIL HAS THE
 INNCORRECT DESIGN CRITERIA. PLEASE
 UPDATE TO 2001 FLORIDA BUILDING CODE AND
 ASCE 7-98.