Plan Review Details - Permit 02040598
Plan Review Stops For Permit 02040598
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-03 Cont ID  
Sent By hpiskura Date 2002-06-03 Time 10:30 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-23 Cont ID  
Sent By jwitmer Date 2002-04-23 Time 07:50 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-23 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02030598
 2200 FL MANGO, 401/402/403
 CONT: PURDY CONST
 TEL: 655-6662
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 1)- FL STATE STATUTE 61G1-16.003 PLANS
 DESIGNED BY AN ARCHITECT FOR PUBLIC
 RECORD SHALL HAVE THE DESIGN PROFESSION-
 ALS NAME AND SEAL AFFIXED.
  
 2)- PERMIT APPLICATION STATES THAT THESE
 SPACES AREA FIRE SPRINKLERED, NO PLANS!
  
 3)- PLANS INDICATE THE TENANT WALL FIRE
 SEPERATION, NO UL RATING FOR FLOOR
 ASSEMBLY?
  
 4)- FL BLD CODE 4.13.6 PLANS HIGHLIGHTED
 INDICATE AREAS OF CONCERN AS TO MANEUVER
 ING AREAS AT DOORWAYS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-06-21 Cont ID  
Sent By dpalmer Date 2002-06-21 Time 06:07 Rev Time 0.00
Received By dpalmer Date 2002-06-21 Time 05:44 Sent To  
Notes
2002-06-21 00:00:00************** REVISION/PROVISO ******
  
 1)NOTE: PLEASE SUBMIT A COMPLETE LOAD
 CALCULATION OF EXISTING 1200A SERVICE
 TO INCLUDE NEW LOAD ADDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN. THERE WILL BE A
 REVISION FEE DUE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-05-31 Cont ID  
Sent By dpalmer Date 2002-05-31 Time 16:45 Rev Time 0.00
Received By dpalmer Date 2002-05-31 Time 16:45 Sent To  
Notes
2002-05-31 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PER NOTE ON
 FIRST REVIEW. PLANS NEED TO SHOW
 SERVICE LOCATION/ ON PLANS. PLEASE
 SHOW PANEL LOCATION ON FLOOR PLANS.
 PLEASE NOTE THERE IS STILL NO INFOR-
 -MATION ON RISER. PLAN NOTE NOW MENTIONS
 COMING FROM PRIMARY GUTTER??? SIZE,
 LOAD ETC ETC?? NEEDS MORE INFORMAITN FOR
 SUFF REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-11 Cont ID  
Sent By dpalmer Date 2002-04-11 Time 15:33 Rev Time 0.00
Received By dpalmer Date 2002-04-11 Time 15:33 Sent To  
Notes
2002-04-11 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY SERVICE LOCATION?
 PLEASE NOTE GROUPING OF MAINS AND/OR
 FIRE SEPARATION BETWEEN UNITS A,B,C
 AT 2HRS.
  
 2)NOTE: PLEASE NOTE THAT PLANS ARE NOT
 SEALED BY THE ARCH OF RECORD. FS/FAC
 481.221.
  
 3)NOTE: PLEASE NOTE THAT AIC RATINGS
 WERE SUBMITTED FOR PANELS, BUT NOT FOR
 MAIN DISC`S. PLEASE SUBMIT.
  
 4)NOTE: PLEASE PROVIDE ROOM IDENTIFICAT-
 ION FOR FLOOR LAYOUT.
  
 5)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%.
 215-2/3, 230-42 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-05-30 Cont ID  
Sent By mcarsill Date 2002-05-30 Time 09:49 Rev Time 0.00
Received By mcarsill Date 2002-05-30 Time 09:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-11 Cont ID  
Sent By mcarsill Date 2002-04-11 Time 17:15 Rev Time 0.00
Received By mcarsill Date 2002-04-11 Time 17:15 Sent To  
Notes
2002-04-11 00:00:00A) PLANS INDICATE THAT TENANT SPACES
 ARE LOCATED ON THE SECOND FLOOR BUT
 THE TENANT SPACES ARE IDENTIFIED AS
 401, 402, AND 403.
 B) PLEASE INDICATE ON THE PLANS THE
 HORIZONTAL FIRE SEPARATION BETWEEN THE
 FIRST AND SECOND FLOOR.
 C) AN ELEVATION FOR THE BUILDING WOULD
 BE HELPFUL FOR ORIENTATION PURPOSES.
 D) PLANS NOT SEALED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2002-06-12 Cont ID  
Sent By pkrauss Date 2002-06-12 Time 09:48 Rev Time 0.30
Received By pkrauss Date 2002-06-12 Time 09:48 Sent To  
Notes
2002-06-12 00:00:00SPOKE WITH CONTRACTOR - TOOK MECH OFF
 BUILDING PERMIT - MECH TO SUBMIT
 SEPARATELY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-06-10 Cont ID  
Sent By pkrauss Date 2002-06-10 Time 15:58 Rev Time 0.35
Received By pkrauss Date 2002-06-10 Time 15:58 Sent To  
Notes
2002-06-10 00:00:00******************DENIED****************
  
 COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED.
  
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.INDICATE EQUIPMENT (NEW OR
 EXISTING), DUCTWORK & GRILLES (NEW,
 EXISTING, RELOCATED), CFM DISTRIBUTION.
 PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 62-89.SHOW CCOMPLIANCE FOR AIR
 BALANCE AS PER 2001 FBC(M) 601.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-02 Cont ID  
Sent By pkrauss Date 2002-05-02 Time 15:11 Rev Time 0.40
Received By pkrauss Date 2002-05-02 Time 15:11 Sent To  
Notes
2002-05-02 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.INDICATE EQUIPMENT (NEW OR
 EXISTING),DUCTWORK & GRILLES (NEW,
 EXISTING, RELOCATED), CFM DISTRIBUTION.
 PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER ASHRAE 62-89.SHOW COMPLIANCE FOR
 AIR BALANCE AS PER 2001 FBC(M) 601.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-11 Cont ID  
Sent By kstevens Date 2002-06-11 Time 14:59 Rev Time 0.00
Received By kstevens Date 2002-06-11 Time 14:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-04 Cont ID  
Sent By kstevens Date 2002-05-04 Time 17:03 Rev Time 0.00
Received By kstevens Date 2002-05-04 Time 17:03 Sent To  
Notes
2002-05-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING & CHAPT. 11
  
 1) ALL PLANS DESIGNED BY AN ARCHITECT
 SHALL BE SEALED, SIGNED, & DATED - FS/
 FAC 481.221 - FS 61G1-16.003 IF USED FOR
 PUBLIC RECORD.
 2) PLEASE SUPPLY ALL MEASUREMENTS FOR
 TOILET ROOMS.
 3) PLEASE SHOW CLEAR FLOOR SPACE FOR ALL
 HDCP FIXTURES.
 4) HDCP WATER CLOSETS SHALL BE 1'6" OFF
 WALL, HDCP LAVS SHALL BE 1'3" OFF WALL.
 HDCP W/C'S SHALL BE 17" TO 19" TO SEAT,
 LAVS SHALL BE 2'10" TO FLOOD RIM LEVEL
 ALL PIPING UNDER LAV TO BE INSULATED.
 5) WATER RISER DIAGRAM REQUIRED.
 6) PER MINIMUM FACILITIES TABLE 403.1
 A SERVICE SINK IS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377