| Plan Review Stops For Permit 02040598 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-06-03 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-06-03 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-04-23 |
Time |
07:50 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-23 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 02030598 | | | 2200 FL MANGO, 401/402/403 | | | CONT: PURDY CONST | | | TEL: 655-6662 | | | | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | 1)- FL STATE STATUTE 61G1-16.003 PLANS | | | DESIGNED BY AN ARCHITECT FOR PUBLIC | | | RECORD SHALL HAVE THE DESIGN PROFESSION- | | | ALS NAME AND SEAL AFFIXED. | | | | | | 2)- PERMIT APPLICATION STATES THAT THESE | | | SPACES AREA FIRE SPRINKLERED, NO PLANS! | | | | | | 3)- PLANS INDICATE THE TENANT WALL FIRE | | | SEPERATION, NO UL RATING FOR FLOOR | | | ASSEMBLY? | | | | | | 4)- FL BLD CODE 4.13.6 PLANS HIGHLIGHTED | | | INDICATE AREAS OF CONCERN AS TO MANEUVER | | | ING AREAS AT DOORWAYS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096X8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-06-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-21 |
Time |
06:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-21 |
Time |
05:44 |
Sent To |
|
|
| Notes |
| 2002-06-21 00:00:00 | ************** REVISION/PROVISO ****** | | | | | | 1)NOTE: PLEASE SUBMIT A COMPLETE LOAD | | | CALCULATION OF EXISTING 1200A SERVICE | | | TO INCLUDE NEW LOAD ADDED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | | -ION IS CALLED IN. THERE WILL BE A | | | REVISION FEE DUE. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-05-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-31 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-31 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2002-05-31 00:00:00 | ********** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT PER NOTE ON | | | FIRST REVIEW. PLANS NEED TO SHOW | | | SERVICE LOCATION/ ON PLANS. PLEASE | | | SHOW PANEL LOCATION ON FLOOR PLANS. | | | PLEASE NOTE THERE IS STILL NO INFOR- | | | -MATION ON RISER. PLAN NOTE NOW MENTIONS | | | COMING FROM PRIMARY GUTTER??? SIZE, | | | LOAD ETC ETC?? NEEDS MORE INFORMAITN FOR | | | SUFF REVIEW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-04-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-04-11 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-04-11 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2002-04-11 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE CLARIFY SERVICE LOCATION? | | | PLEASE NOTE GROUPING OF MAINS AND/OR | | | FIRE SEPARATION BETWEEN UNITS A,B,C | | | AT 2HRS. | | | | | | 2)NOTE: PLEASE NOTE THAT PLANS ARE NOT | | | SEALED BY THE ARCH OF RECORD. FS/FAC | | | 481.221. | | | | | | 3)NOTE: PLEASE NOTE THAT AIC RATINGS | | | WERE SUBMITTED FOR PANELS, BUT NOT FOR | | | MAIN DISC`S. PLEASE SUBMIT. | | | | | | 4)NOTE: PLEASE PROVIDE ROOM IDENTIFICAT- | | | ION FOR FLOOR LAYOUT. | | | | | | 5)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS NEED TO BE SHOWN AT 125%. | | | 215-2/3, 230-42 ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-05-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-30 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-30 |
Time |
09:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-04-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-04-11 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-11 |
Time |
17:15 |
Sent To |
|
|
| Notes |
| 2002-04-11 00:00:00 | A) PLANS INDICATE THAT TENANT SPACES | | | ARE LOCATED ON THE SECOND FLOOR BUT | | | THE TENANT SPACES ARE IDENTIFIED AS | | | 401, 402, AND 403. | | | B) PLEASE INDICATE ON THE PLANS THE | | | HORIZONTAL FIRE SEPARATION BETWEEN THE | | | FIRST AND SECOND FLOOR. | | | C) AN ELEVATION FOR THE BUILDING WOULD | | | BE HELPFUL FOR ORIENTATION PURPOSES. | | | D) PLANS NOT SEALED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2002-06-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-12 |
Time |
09:48 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-06-12 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2002-06-12 00:00:00 | SPOKE WITH CONTRACTOR - TOOK MECH OFF | | | BUILDING PERMIT - MECH TO SUBMIT | | | SEPARATELY. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-06-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-10 |
Time |
15:58 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-06-10 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2002-06-10 00:00:00 | ******************DENIED**************** | | | | | | COMMENTS FROM PREVIOUS REVIEW NOT | | | ADDRESSED. | | | | | | NO MECHANICAL PLANS SUBMITTED FOR | | | REVIEW.INDICATE EQUIPMENT (NEW OR | | | EXISTING), DUCTWORK & GRILLES (NEW, | | | EXISTING, RELOCATED), CFM DISTRIBUTION. | | | PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER 62-89.SHOW CCOMPLIANCE FOR AIR | | | BALANCE AS PER 2001 FBC(M) 601.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-05-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-02 |
Time |
15:11 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-05-02 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2002-05-02 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR | | | REVIEW.INDICATE EQUIPMENT (NEW OR | | | EXISTING),DUCTWORK & GRILLES (NEW, | | | EXISTING, RELOCATED), CFM DISTRIBUTION. | | | PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER ASHRAE 62-89.SHOW COMPLIANCE FOR | | | AIR BALANCE AS PER 2001 FBC(M) 601.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-06-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-11 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-11 |
Time |
14:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-05-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-04 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-04 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2002-05-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING & CHAPT. 11 | | | | | | 1) ALL PLANS DESIGNED BY AN ARCHITECT | | | SHALL BE SEALED, SIGNED, & DATED - FS/ | | | FAC 481.221 - FS 61G1-16.003 IF USED FOR | | | PUBLIC RECORD. | | | 2) PLEASE SUPPLY ALL MEASUREMENTS FOR | | | TOILET ROOMS. | | | 3) PLEASE SHOW CLEAR FLOOR SPACE FOR ALL | | | HDCP FIXTURES. | | | 4) HDCP WATER CLOSETS SHALL BE 1'6" OFF | | | WALL, HDCP LAVS SHALL BE 1'3" OFF WALL. | | | HDCP W/C'S SHALL BE 17" TO 19" TO SEAT, | | | LAVS SHALL BE 2'10" TO FLOOD RIM LEVEL | | | ALL PIPING UNDER LAV TO BE INSULATED. | | | 5) WATER RISER DIAGRAM REQUIRED. | | | 6) PER MINIMUM FACILITIES TABLE 403.1 | | | A SERVICE SINK IS REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|