Plan Review Details - Permit 02040527
Plan Review Stops For Permit 02040527
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-01 Cont ID  
Sent By dpalmer Date 2002-05-01 Time 06:51 Rev Time 0.00
Received By dpalmer Date 2002-05-01 Time 06:51 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-19 Cont ID  
Sent By dpalmer Date 2002-04-19 Time 12:49 Rev Time 0.00
Received By dpalmer Date 2002-04-19 Time 12:49 Sent To P
Notes
2002-04-19 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE CODES ARTS
 REFERENCED ON PLANS ARE STILL SHOWN
 FROM THE 96 NEC. PLEASE CORRECT AND
 CORRELATE WITH THE 99 NEC.
  
 2 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 3 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 PLEASE NOTE THAT AIC RATING IS BEING
 SHOWN AS 22.00. MUST BE A MISPRINT.
 THIS IS JUST A NOTE SINCEPLANS ARE
 COMING BACK FOR CORRECTIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.'
 '
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-05 Cont ID  
Sent By pkrauss Date 2002-12-05 Time 16:44 Rev Time 0.25
Received By pkrauss Date 2002-12-05 Time 16:38 Sent To  
Notes
2002-12-05 00:00:00MECH REV PERMIT 02040548

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-20 Cont ID  
Sent By hmoser Date 2002-06-20 Time 19:45 Rev Time 0.50
Received By hmoser Date 2002-06-20 Time 19:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-25 Cont ID  
Sent By hmoser Date 2002-04-25 Time 19:48 Rev Time 0.50
Received By hmoser Date 2002-04-25 Time 19:48 Sent To  
Notes
2002-04-25 00:00:00PLAN DENIED
 CFM. ON PLANS DO NOT MATCH CFM. ON
 MANUAL J
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-29 Cont ID  
Sent By rmcdouga Date 2002-05-29 Time 16:41 Rev Time 0.33
Received By jleech Date 2002-05-29 Time 17:21 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-07-31 Cont ID  
Sent By rmcdouga Date 2002-07-31 Time 14:26 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-31 00:00:00************BUILDING PROVISO************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SUBMIT (2) COPIES OF A SOIL BEARING TEST
 PRIOR TO POURING THE FOUNDATION.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 EVALUATIONS FOR GLASS BLOCK. ONLY PART
 OF THE METRO-DADE PRODUCT APPROVAL WAS
 SUBMITTED.
  
 5) SUBMIT (2) COPIES OF STORM PANEL
 INSTALLATION SCHEDULES LISTING ALL OF
 THE OPENINGS THAT ARE BEING SHUTTERED.
 THE ONES THAT WERE SUBMITTED LISTED ONLY
 7 OF 10 OPENINGS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-07-01 Cont ID  
Sent By rmcdouga Date 2002-07-01 Time 13:37 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-01 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) STRUCTURE IS LOCATED IN AN 'A8' FLOOD
 ZONE. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 3) PROVIDE SOIL BEARING TEST REPORT PER
 CITY OF WPB AMENDMENTS TO 2001 FBC SEC.
 1804.2.2.
  
 4) PROVIDE AN ADDITIONAL COPY OF THE
 PRODUCT APPROVALS FOR THE FRONT DOOR AND
 THE GLASS BLOCK. TWO COPIES ARE REQUIRED
  
 5) PROVIDE THE TESTING INFORMATION FOR
 THE GLASS BLOCK INDICATING THAT IT HAS
 A FIRE RATING OF ONE HOUR.
  
 6) PROVIDE A DETAIL OF THE GABLE END ON
 THE ZERO LOT LINE INDICATING THAT THE
 ASSEMBLY HAS A ONE HOUR FIRE RATING FOR
 BOTH INTERNAL AND EXTERNAL FIRE EXPOSURE
  
 7) PROVIDE AN INSTALLATION SCHEDULE FOR
 THE STORM PANELS. THIS IS REQUIRED AT
 TIME OF PERMIT OR A SEPARATE PERMIT WITH
 ADDITIONAL FEES WILL BE REQUIRED.
  
 8) PLEASE CHANGE THE CALL SIZE OF THE
 EGRESS WINDOW (I) IN THE WINDOW SCHEDULE
 TO A 24-5 WHICH CORRESPONDS TO THE
 REVISED DIMENSIONS GIVEN.
  
 9) PLEASE CHANGE NOTE 6 UNDER GENERAL
 NOTES ON A2 TO REFERENCE THE 2001
 FLORIDA PLUMBING CODE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-05-29 Cont ID  
Sent By rmcdouga Date 2002-05-29 Time 16:01 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To P
Notes
2002-05-29 00:00:00SAME NOTES AS PERMIT # 02040521

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-29 Cont ID  
Sent By rmcdouga Date 2002-05-29 Time 15:56 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-05-29 00:00:00OK PER S.GRAHAM 4-9-02